InteliLite 9 Global Guide
353
LAI: C
Related FW
1.1.0
Related applications
AMF, MRS
Comm object
67
Description
Logical analog input designed for coolant temperature value received from analog sensor. For more
information about wiring of analog inputs
. Limits for this protection are
adjusted by setpoints
Coolant Temperature Wrn (page 181)
and
Coolant Temperature Sd (page 182)
. Delay is
adjusted by setpoint
Coolant Temperature Delay (page 182)
Monitoring
Analog value is only measured and displayed on the LCD screen but not used for
protection.
HistRecOnl
Analog value is only measured and displayed on the LCD screen but not used for
protection. History record is made if value is out of the limits.
Wrn
Analog value is used for warning protection only.
Wrn+Stp
Analog value is used for warning and slow stop protection
Stp
Analog value is used for slow stop protection
Wrn + BOC
Analog value is used for warning and BOC (Breaker Open and Cooling) protection.
BOC
Analog value is used for BOC (Breaker Open and Cooling) protection.
Wrn + Sd
Analog value is used for warning and shutdown protection.
Sd
Analog value is used for shutdown protection.
Protection types
Note:
This parameter has to be adjusted via InteliConfig.
Under limit
Alarm is activated when value of analog input is under adjusted limits
Over limit
Alarm is activated when value of analog input is over adjusted limits
Under limit + fls
Alarm is activated when value of analog input is under adjusted limits. If sensor fail
is detected then the alarm with higher level is activate as well.
Over limit + fls
Alarm is activated when value of analog input is over adjusted limits. If sensor fail
is detected then the alarm with higher level is activate as well.
Alarm
Example:
Protection type is Wrn + Sd. When sensor fail is detected then Sd alarm will be act
Sensor fail alarm will be activated.
Note:
This parameter has to be adjusted via InteliConfig.
IMPORTANT: Value from analog input has higher priority than value from ECU.
Coolant Temp