
InteliLite 9 Global Guide
244
Setpoint group
Basic settings
Related FW
1.1.0
Range [units]
45 .. 65 [Hz]
Default value
50 Hz
Alternative config
YES
Step
1 Hz
Comm object
9914
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Always
Description
Nominal system frequency (usually 50 or 60 Hz).
Note:
This value is used when binary input
is active.
Nominal Frequency 2
Setpoint group
Basic settings
Related FW
1.1.0
Range [units]
80 .. 20000 [V]
Default value
231 V
Alternative config
YES
Step
1 V
Comm object
12053
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Conditioned by the setpoint
Description
Nominal system voltage (phase to neutral).
Note:
This value is used when binary input
is active.
Nominal Voltage Ph-N 2
Setpoint group
Basic settings
Related FW
1.1.0
Range [units]
80 .. 40000 [V]
Default value
400 V
Alternative config
YES
Step
1 V
Comm object
12056
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Conditioned by the setpoint
Description
Nominal system voltage (phase to phase).
Note:
This value is used when binary input
is active.
Nominal Voltage Ph-Ph 2