InteliLite 9 Global Guide
240
Setpoint group
Basic settings
Related FW
1.1.0
Range [units]
80 .. 20000 [V]
Default value
231 V
Alternative config
YES
Step
1 V
Comm object
12052
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Conditioned by the setpoint
Description
Nominal system voltage (phase to neutral).
Note:
This value is used when any other alternate configuration is not active.
Nominal Voltage Ph-N 1
Setpoint group
Basic settings
Related FW
1.1.0
Range [units]
80 .. 40000 [V]
Default value
400 V
Alternative config
YES
Step
1 V
Comm object
12055
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Conditioned by the setpoint
Description
Nominal system voltage (phase to phase).
Note:
This value is used when any other alternate configuration is not active.
Nominal Voltage Ph-Ph 1