Image 8.15 Transfer Delay 2
IMPORTANT: This is a fixed parameter, it isn't possible to adjust it in any manner. This
parameter isn't visible either in controller or in PC tools.
Setpoint group
AMF settings
Related FW
1.1.0
Fixed value
1.0 s
Description
Delay after mains returns to MCB closing, if the gen-set is not running(e.g. is in start-up procedure)
IMPORTANT: This is a fixed parameter, it isn't possible to adjust it in any manner. This
parameter isn't visible either in controller or in PC tools.
MCB Close Delay
Subgroup: AMF Voltage Conditions
Setpoint group
AMF settings
Related FW
1.1.0
Range [units]
.. 150 [%]
Default value
110 %
Alternative config
NO
Step
1 % of
Nominal Voltage Ph-Ph (page 149)
Comm object
8305
Related applications
AMF
Config level
Standard
Setpoint visibility
Conditioned by the setpoint
Description
Threshold for mains overvoltage. All three phases are checked. Maximum out of three is used.
Mains Overvoltage