7 Technical data
Power supply range
8-36 VDC
Power consumption
394 mA / 8 VDC
255 mA / 12 VDC
140 mA / 24 VDC
97 mA / 36 VDC
Fusing
Power terminal max. 3 A
E-Stop max.12 A
Fusing E-Stop
12 A
Max. Power
Dissipation
3,5 W
Power supply
Operating
temperature
-20 ˚C to +70 ˚C
Storage temperature
-30 ˚C to +70 ˚C
Protection degree
(front panel)
IP 65
Operating humidity
95 % w/o condensation
Vibration
5-25 Hz, ± 1,6 mm
25-100 Hz, a = 4 g
Shocks
a = 500 m/s
2
Surrounding air temperature rating 70°C
Suitable for pollution degree 3
Operating conditions
Max. output current
250 mA / 36 V
Charging fail
threshold
Adjustable
D+ terminal
Measurement inputs
3ph-n Gen voltage , 3ph-n
Mains
Measurement range
277 V
Max. allowed voltage
350 V
Accuracy
1 %
Frequency range
40-70 Hz (accuracy 0.1 Hz)
Input impedance
0,72 MΩ ph-ph , 0,36 MΩ ph-n
Voltage measurement
Measurement
inputs
3ph Gen current, 1ph Mains current
Measurement
range
5 A
Max. allowed
current
10 A
Accuracy
1,5 % for full temperature range (1 %
from 0 ˚C to 50 ˚C)
Input
impedance
< 0,1 Ω
Current measurement
Number
6, non-isolated
Close/Open
indication
0-2 VDC close contact
>6 VDC open contact
Binary inputs
Low
current
4 low current output, non-isolated
0,5 A
switching to positive supply terminal
High
current
2 high current output, non-isolated
5 A (60 °C), 4 A (70 °C)
switching to positive supply terminal
Binary outputs
Number
3, non-isolated
Resolution
0,1 Ω
Range
0-2500 Ω
Input impedance
800 Ω
Accuracy
±2 % from value in range
0-2500 Ω
±1,5 kΩ in range 2,5-15 kΩ
Analog inputs
Voltage input range
4 Vpk-pk to 50 Vpk-pk in
range 4 Hz to 1 kHz
6 Vpk-pk to 50 Vpk-pk in
range 1 kHz to 5 kHz
10 Vpk-pk to 50 Vpk-pk in
range 5 kHz to 10 kHz
Frequency input
range
4 Hz to 10 kHz
Frequency
measurement
tolerance
0,2 % from range 10 kHz
Magnetic pickup
InteliLite 9 Global Guide
137