background image

InteliLite4 AMF20 Global Guide

391

ECU AIN 2

Value group

Engine

Related FW

1.3.0

Units

Depends on ECU value

Comm object

10154

Related applications

AMF, MRS

Description

This is one of the inputs, which are defined by ECU. Order of values depends on type of ECU.

Note:

Usually there are engine speed[RPM], fuel rate[L/h], coolant temperature[°C], intake

temperature[°C], oil pressure[bar], boost pressure[bar], load[%], oil temperature[°C] etc.

6

back to List of values

ECU AIN 3

Value group

Engine

Related FW

1.3.0

Units

Depends on ECU value

Comm object

10155

Related applications

AMF, MRS

Description

This is one of the inputs, which are defined by ECU. Order of values depends on type of ECU.

Note:

Usually there are engine speed[RPM], fuel rate[L/h], coolant temperature[°C], intake

temperature[°C], oil pressure[bar], boost pressure[bar], load[%], oil temperature[°C] etc.

6

back to List of values

ECU AIN 4

Value group

Engine

Related FW

1.3.0

Units

Depends on ECU value

Comm object

10156

Related applications

AMF, MRS

Description

This is one of the inputs, which are defined by ECU. Order of values depends on type of ECU.

Note:

Usually there are engine speed[RPM], fuel rate[L/h], coolant temperature[°C], intake

temperature[°C], oil pressure[bar], boost pressure[bar], load[%], oil temperature[°C] etc.

6

back to List of values

ECU AIN 5

Value group

Engine

Related FW

1.3.0

Units

Depends on ECU value

Comm object

10157

Related applications

AMF, MRS

Description

This is one of the inputs, which are defined by ECU. Order of values depends on type of ECU.

Note:

Usually there are engine speed[RPM], fuel rate[L/h], coolant temperature[°C], intake

temperature[°C], oil pressure[bar], boost pressure[bar], load[%], oil temperature[°C] etc.

6

back to List of values

Summary of Contents for InteliLite 4 AMF 20

Page 1: ... 246 012 111 E mail info comap control com www comap control com Global Guide InteliLite 4 AMF 20 Controller for single gen set applications SW version 1 3 0 1 Document information 5 2 System overview 11 3 Applications overview 20 4 Installation and wiring 22 5 Controller setup 61 6 Communication 178 7 Technical data 198 8 Appendix 199 ...

Page 2: ...InteliSCADA 14 2 5 Plug in Modules 15 2 5 1 CM3 Ethernet 15 2 5 2 CM2 4G GPS 15 2 5 3 CM RS232 485 15 2 5 4 EM BIO8 EFCP 16 2 6 CAN modules 16 2 6 1 Inteli IO8 8 16 2 6 2 Inteli AIN8 17 2 6 3 Inteli AIN8TC 17 2 6 4 Inteli AIO9 1 18 2 6 5 IGS PTM 18 2 6 6 IGL RA15 19 3 Applications overview 20 3 1 AMF Automatic Mains Failure Start 20 3 2 MRS Manual Remote Start 21 4 Installation and wiring 22 4 1 P...

Page 3: ...n states 111 5 5 10 Additional running engine indications 114 5 5 11 History log 114 5 5 12 Breaker control 116 5 5 13 Protections 119 5 5 14 Exercise timers 134 5 5 15 Voltage phase sequence detection 140 5 5 16 Load shedding 141 5 5 17 Dummy Load 142 5 5 18 Sensor curves 143 5 5 19 PLC 145 5 5 20 Geo fencing 151 5 5 21 After treatment Support 151 5 5 22 Alternate configuration 156 5 5 23 USB hos...

Page 4: ... PLC 510 8 2 Alarms 521 8 2 1 Alarm levels in the controller 521 8 2 2 Alarms level 1 521 8 2 3 Alarms level 2 552 8 3 Modules 576 8 3 1 Plug in modules 576 8 3 2 CAN modules 587 6 back to Table of contents InteliLite4 AMF20 Global Guide 4 ...

Page 5: ...mation that is used to illustrate how a specific function works 1 2 About this Global Guide This manual contains important instructions for InteliLite 4 family controllers which must be followed during installation and maintenance of the controllers This manual provides general information how to install and operate InteliLite 4 controllers This manual is dedicated for Operators of Gen sets Gen se...

Page 6: ...nse Agreement Terms and Conditions available on www comap control com Security Risk Disclaimer Pay attention to the following recommendations and measures to increase the level of security of ComAp products and services Please note that possible cyber attacks cannot be fully avoided by the below mentioned recommendations and set of measures already performed by ComAp but by following them the cybe...

Page 7: ... v1 and v2 in unprotected networks e g Internet 1 3 2 Used open source software Name of software License name License condition web address Mbed TLS Apache 2 0 license Aladin MD5 Zlib license EmbOS Segger License Agreement v 150515 license emFile Segger License Agreement license emUSB Device Segger License Agreement license emUSB Host Segger License Agreement license Tiny Mersenne Twister tinymt32...

Page 8: ...ry outputs can change state during and after software reprogramming before the controller is used again ensure that the proper configuration and setpoint settings are set in the controller The following instructions are for qualified personnel only To avoid personal injury do not perform any action not specified in related guides for product 1 5 Functions and protections Support of functions and p...

Page 9: ...ponsible Party 10 N Martingale Rd 400 60173 Schaumburg IL USA Tel 420 246 012 111 E mail info comap control com FCC Compliance Statement This device complies with Part 15 of the FCC Rules Operation is subject to the following two conditions 1 This device may not cause harmful interference and 2 this device must accept any interference received including interference that may cause undesired operat...

Page 10: ... Current measuring Diode Ethernet male Ethernet female Fuel solenoid Fuse Fuse switch Generator Generator schematic Grounding GSM GSM modem Jumper Load Mains Mains Mobile provider Passive current sensor Pick up Relay coil Relay coil of slow operating Resistor Resistor adjustable Resistive sensor RPTC RS 232 male RS 232 female Starter Switch manually operated Transformer USB type B male USB type B ...

Page 11: ...e This principle corresponds exactly to the physical definition of alternating voltage effective values Under normal circumstances the mains voltage should have a pure sinusoidal waveform However some nonlinear elements connected to the mains produce harmonic waveforms with frequencies of multiples of the basic mains frequency and this may result in deformation of the voltage waveforms The True RM...

Page 12: ...tputs functions to physical binary output terminals Assigning sensor characteristics curves and alarms to analog inputs Selection of peripheral modules which are connected to the controller and performing the same functions as mentioned above for them Selection of ECU type if an ECU is connected Changing the language of the controller interface Image 2 1 Principle of binary inputs and outputs conf...

Page 13: ...ion with the controller Offline or online controller configuration Controller firmware upgrade Reading writing adjustment of setpoints Reading of measured values Browsing of controller history records Exporting data into an XLS file Controller language translation 2 4 2 WebSupervisor Web based system for monitoring and controlling of controllers See more at the WebSupervisor webpage This tool prov...

Page 14: ... modern look and feel that has been developed with current web technologies See more in the InteliSCADA Global guide This tool provides the following functions Basic SCADA in a few minutes auto generated SCADA Broad range of instruments with easy and fast configuration Fully customizable SCADA diagram Browsing of all measured and computed values More than 200 images available Browsing of controlle...

Page 15: ...onnection no need of public and static IP address 2 5 2 CM2 4G GPS GSM 4G module GSM 4G Internet module and GPS locator Global 4G LTE module with 3G 2G backup Remote control and monitoring of the controller via InteliConfig WebSupervisor Active e mail and SMS support AirGate 2 technology support for easy connection no need of public and static IP address Tracking via GNSS GPS GLONASS module 2 5 3 ...

Page 16: ...8 binary outputs and 2 analog outputs or 16 binary inputs 0 binary outputs and 2 analog outputs via switches inside the controller Configuration 8 8 8 Binary inputs options pull up or pull down logic 8 Binary outputs options Low side switch LSS or High side switch HSS 2 Analog outputs options voltage 0 10 V current 0 20 mA and PWM 5 V adjustable frequency 200 Hz 2 4 kHz Configuration 16 0 16 Binar...

Page 17: ... 1 V 0 2 4 V 0 5 V 0 10 V Lambda probes Thermocouples are not supported the measuring loop was designed for lambda probes which caused non support of thermocouples Impulse RPM sensor RPM measuring pulses with frequency 4 Hz 10 kHz Impulse Possibility to measure pulses from electrometer flowmeter measurement of total consumption average fuel consumption 2 6 3 Inteli AIN8TC 8 Analog Channels Module ...

Page 18: ...og output 2 6 5 IGS PTM The unit offers the user the flexibility to configure the unit to have 8 binary inputs 8 binary outputs 4 analog inputs and 1 analog outputs Configurable 8 binary and 4 analog inputs Configurable 8 binary and 1 analog output LEDs indicate the state of binary inputs outputs Measures values from Pt100 and Ni100 sensors Analog inputs resistance range 0 250 Ω voltage range 0 10...

Page 19: ...r 15 programmable LEDs with configurable colors red green yellow Lamp test function with status LED Customizable labels Local horn output Maximal distance 200 m from the controller Up to 4 units can be connected to the controller UL certified 6 back to System overview ...

Page 20: ... contents 3 1 AMF Automatic Mains Failure Start The typical schematic of Automatic Mains Failure Start application is shown below The controller controls two breakers a mains breaker and a generator breaker Feedback from both breakers is not necessary InteliLite 4 controllers can also work without breaker feedback Image 3 1 AMF application overview ...

Page 21: ...ic of Manual Remote Start application is shown below The controller controls one breaker a generator breaker Feedback from the breaker is not necessary InteliLite 4 controllers can also work without breaker feedback Image 3 2 MRS application overview 6 back to Applications overview ...

Page 22: ...odule installation 58 4 6 Maintenance 59 6 back to Table of contents 4 1 Package content The package contains Controller Mounting holders Terminal blocks Note The package does not contain any communication or extension modules The required modules should be ordered separately 4 2 Controller installation 4 2 1 Dimensions Plug in module Note Dimension x depends on plug in module ...

Page 23: ...chboard door Requested cutout size is 187 132 mm Use the screw holders delivered with the controller to fix the controller into the door as described in pictures below Recommended torque for holders is 0 15 N m Panel door mounting Note Enclosure Type rating with mounting instruction For use on a Flat surface of a type 1 enclosure ...

Page 24: ...T39 L1 T43 L1 T47 BI2 T32 L2 T40 L2 T44 L2 T48 BI3 T33 L3 T41 L3 T45 L3 T49 BI4 T50 BI5 T51 BI6 Image 4 1 Terminal diagram for InteliLite 4 AMF 20 CAN1 ANALOG INPUTS BINARY OUTPUTS POWER SUPPLY D T27 L T22 N A T10 BO6 T01 BATT T28 COM T21 AI3 T09 BO5 T02 D T29 H T20 AI2 T08 BO4 T03 BATT T19 AI1 T07 BO3 USB 5 V T18 ACOM T06 BO2 USB HOST T23 5 V RPM T05 BO1 T17 RPM IN E STOP T16 RPM GND T04 ...

Page 25: ... wiring page 41 Mains voltage inputs 42 45 Voltage measurement AMF wiring page 33 Binary inputs 46 51 Binary inputs page 49 CAN1 H COM L CAN bus and RS485 wiring page 53 5 V 23 Analog inputs 18 22 Analog inputs page 51 RPM 16 17 Magnetic pick up page 48 Binary outputs 05 10 Binary Outputs page 50 E Stop 04 E Stop page 51 Power supply D Power supply page 27 USB Device USB page 58 USB Host USB HOST ...

Page 26: ...e wired with shielded cables especially when the length is more than 3 m Tightening torque allowable wire size and type for the Field Wiring Terminals For Mains Voltage Generator Voltage and Current terminals Specified tightening torque is 0 56 Nm 5 0 In lbs use only diameter 0 5 2 0 mm 12 26 AWG conductor rated for 90 C minimum For other controller field wiring terminals Specified tightening torq...

Page 27: ...s 36 V The controller s power supply terminals are protected against large pulse power disturbances When there is a potential risk of the controller being subjected to conditions outside its capabilities an outside protection device should be used It is necessary to ensure that potential difference between generator current COM terminal and battery terminal is maximally 2 V Therefore it is strongl...

Page 28: ...eparating diode The capacitor size depends on required time It shall be approximately thousands of μF The capacitor size should be 5 000 μF to withstand 150 ms voltage dip under following conditions Voltage before dip is 12 V after 150 ms the voltage recovers to min allowed voltage i e 8 V Diode should be able to withstand at least 1 kV Power supply fusing The controller should never be connected ...

Page 29: ...en set None Note The current measurement protections are active only when the Gen set is running If the CT Location is set to Load the Short Circuit BOC page 261 protection is enabled only when GCB is closed Current measurement wiring The number of CT s is automatically selected based on selected value of setpoint Connection type page 209 3Ph4Wire High Leg D 3Ph3Wire SplPhL1L2 SplPhL1L3 Mono Ph Ge...

Page 30: ...rrent COM terminal and power supply terminal is maximally 2 V To do so ground properly both terminals Image 4 4 3 phase application IMPORTANT It is necessary to ensure that potential difference between current COM terminal and power supply terminal is maximally 2 V To do so interconnect these two terminals Note This wiring is recommended for Indian market ...

Page 31: ...urrent COM terminal and power supply terminal is maximally 2 V To do so ground properly both terminals Image 4 6 SplPhL1L2 application IMPORTANT It is necessary to ensure that potential difference between current COM terminal and power supply terminal is maximally 2 V To do so interconnect these two terminals Note This wiring is recommended for Indian market ...

Page 32: ...To do so ground properly both terminals Image 4 8 SplPhL1L3 application IMPORTANT It is necessary to ensure that potential difference between current COM terminal and power supply terminal is maximally 2 V To do so interconnect these two terminals Note This wiring is recommended for Indian market IMPORTANT The second phase of split phase connection is connected to the terminal where the third phas...

Page 33: ...between current COM terminal and power supply terminal is maximally 2 V To do so interconnect these two terminals Note This wiring is recommended for Indian market Voltage measurement AMF wiring There are 6 voltage measurement Connection Type setpoint Connection type page 209 3Ph4Wire High Leg D 3Ph3Wire SplPhL1L2 SplPhL1L3 Mono Ph options each type matches to corresponding generator connection ty...

Page 34: ... Mono Ph Ph N voltage Connection Type 3 Phase 4 Wires Image 4 11 3 phase application with neutral Note Fuse on N wire is not obligatory but recommended Image 4 12 Typical 3 Phase 4 Wires generator wiring also known as 3ph High Y Note Connection type 277 480V 3 PHASE Nominal Voltage 3Ph High Y page 212 ...

Page 35: ... Phase 4 Wires generator wiring also known as 3ph Low Y Note Connection type 120 208V 3 PHASE Nominal Voltage 3Ph Low Y page 212 Connection Type High Leg D Image 4 14 High Leg Delta application Note Fuse on N wire is not obligatory but recommended ...

Page 36: ...0 Global Guide 36 Image 4 15 Typical High Leg D generator wiring Note Connection type 120 240V 3 PHASE Nominal Voltage High Leg D page 213 Connection Type 3 Phase 3 Wires Image 4 16 3 phase application without neutral ...

Page 37: ...teliLite4 AMF20 Global Guide 37 Image 4 17 Typical 3 Phase 3 Wires generator wiring Connection Type SplPhL1L2 Image 4 18 Split phase L1L2 application Note Fuse on N wire is not obligatory but recommended ...

Page 38: ...nteliLite4 AMF20 Global Guide 38 Image 4 19 Typical Split Phase generator wiring Image 4 20 Typical Split Phase generator wiring Note Connection type 120 240V 1 PHASE Nominal Voltage SplitPhase page 213 ...

Page 39: ...InteliLite4 AMF20 Global Guide 39 Connection Type SplPhL1L3 Image 4 21 Split phase L1L3 application Note Fuse on N wire is not obligatory but recommended Image 4 22 Typical Split Phase generator wiring ...

Page 40: ...Image 4 23 Typical Split Phase generator wiring Note Connection type 120 240V 1 PHASE Nominal Voltage SplitPhase page 213 Connection Type Mono Phase Image 4 24 Mono phase application Note Fuse on N wire is not obligatory but recommended ...

Page 41: ...ding generator connection type Note For fusing of voltage measurement input use T1A or T2A fuse The generator protections are evaluated from different voltages based on Connection type page 209 setting 3Ph 4W Ph Ph voltage Ph N voltage 3Ph 3W Ph Ph voltage High Leg D Ph Ph voltage Ph N voltage SplPhL1L2 Ph N voltage SplPhL1L3 Ph N voltage Mono Ph Ph N voltage Connection Type 3 Phase 4 Wires Image ...

Page 42: ... Wires generator wiring also known as 3ph High Y Note Connection type 277 480V 3 PHASE Nominal Voltage 3Ph High Y page 212 Image 4 28 3 Phase 4 Wires generator wiring also known as 3ph Low Y Note Connection type 120 208V 3 PHASE Nominal Voltage 3Ph Low Y page 212 ...

Page 43: ...InteliLite4 AMF20 Global Guide 43 Connection Type 3 Phase 3 Wires Image 4 29 3 phase application without neutral Image 4 30 Typical 3 Phase 3 Wires generator wiring ...

Page 44: ...nnection Type High Leg D Image 4 31 High Leg Delta application Note Fuse on N wire is not obligatory but recommended Image 4 32 Typical High Leg D generator wiring Note Connection type 120 240V 3 PHASE Nominal Voltage High Leg D page 213 ...

Page 45: ...InteliLite4 AMF20 Global Guide 45 Connection Type SplPhL1L2 Image 4 33 Split phase L1L2 application Note Fuse on N wire is not obligatory but recommended Image 4 34 Typical Split Phase generator wiring ...

Page 46: ...pe 120 240V 1 PHASE Nominal Voltage SplitPhase page 213 Connection Type SplPhL1L3 Image 4 36 Split phase L1L3 application Note Fuse on N wire is not obligatory but recommended IMPORTANT The second phase of split phase connection is connected to the terminal where the third phase is normally connected ...

Page 47: ...nteliLite4 AMF20 Global Guide 47 Image 4 37 Typical Split Phase generator wiring Image 4 38 Typical Split Phase generator wiring Note Connection type 120 240V 1 PHASE Nominal Voltage SplitPhase page 213 ...

Page 48: ...eed sensor pickup is the most common method of engine speed measurement To use this method mount the pickup opposite the engine flywheel connect the cable to the controller as shown on the picture below and adjust the setpoint Gear Teeth page 215 according to the number of teeth on the flywheel For the details about the pick up input parameters see Technical data on page 198 IMPORTANT To ensure pr...

Page 49: ...s not running RPM is measured from the generator voltage Gear Teeth 0 Controller is measuring some voltage value on input terminals due to open fusing If RPM 0 the controller will be put into a Not ready state and the engine will not be allowed to start 4 4 7 Binary inputs Use minimally 1 mm 2 cables for wiring of Binary inputs Image 4 41 Wiring binary inputs Note The name and function or alarm ty...

Page 50: ...ted signalization etc IMPORTANT Use suppression diodes on all relays and other inductive loads Image 4 42 Binary outputs wiring Note Every single low current binary output can provide up to 0 5 A of steady current IMPORTANT Binary output 1 and 2 is power up by E Stop terminal IMPORTANT When operating temperature is higher than 60 C it is strongly recommended to limit output current of high current...

Page 51: ...top wiring Note Recommended fusing is 10 A fuse Note Grey dashed line symbolizes internal connection between E Stop and binary outputs 1 and 2 Note For proper functionality of E Stop the terminal T04 must be always wired Terminal can be connected to battery or to terminal T03 BATT IMPORTANT Suppression diodes are not indicated but required 4 4 10 Analog inputs On each analog input there is the pos...

Page 52: ... supply terminal of the controller as well as one pole of each sensor Analog inputs are typically used for Oil Pressure Coolant Temperature and Fuel Level All of these parameters are connected with relevant protections Image 4 45 Grounded sensors Image 4 46 Isolated sensors Note Schematics show only analog input connection overview not actual wiring Note The name sensor characteristic and alarm ty...

Page 53: ...mage 4 48 Analog inputs as binary Note The name sensor characteristic and alarm types for each analog input have to be assigned during configuration Note Tristate and binary sensors are not suitable for Analog Switch functions Analog Voltage sensor Controller is equipped with 5 V terminal which can be used as power supply for a voltage analog sensor Image 4 49 Analog Voltage sensor Note Maximal cu...

Page 54: ...star is necessary The CAN bus must be terminated by 120Ω resistors at both ends using a cable with following parameters Cable type Shielded twisted pair Impedance 120 Ω Propagation velocity 75 delay 4 4 ns m Wire crosscut 0 25 mm 2 Attenuation 1MHz 2 dB 100 m Note Communication circuits shall be connected to communication circuits of Listed equipment Note A termination resistor at the CAN 120 Ω is...

Page 55: ...nly Shielding shall not be connected to CAN COM terminal For longer distances or in case of surge hazard connection out of building in case of storm etc Image 4 52 CAN bus wiring for longer distances Recommended PT5 HF 12DC ST1 1Protections recommended Phoenix Contact http www phoenixcontact com PT 5 HF 12DC ST with PT2x2 BE base element or Saltek http www saltek cz DM 012 2 R DJ ...

Page 56: ...inated by 120Ω resistors at both ends For shorter distances connection within one building Image 4 53 RS485 wiring for shorter distances For longer distances or in case of surge hazard connection out of building in case of storm etc Image 4 54 RS485 wiring for longer distances Recommended PT5HF 5DC ST2 Note Communication circuits shall be connected to communication circuits of Listed equipment 1Re...

Page 57: ...sion line into a known state By installing two 620Ω balancing resistors at one node on the transmission line a voltage divider is created that forces the voltage between the differential pair to be less than 200 mV which is the threshold for the receiver Install these resistors on only one node The figure below shows a transmission line using bias resistors Balancing resistors are placed directly ...

Page 58: ...s only for service purpose Binary inputs and outputs are in logical 0 Also plug in modules are not working 4 4 13 USB HOST USB Flash Drive can be connected into USB A connector Note For more information see USB host on page 157 6 back to Recommended wiring 4 5 Plug in module installation 4 5 1 Installation IMPORTANT Any manipulation with plug in module shall be done with disconnected power supply ...

Page 59: ...or each plug in module 4 6 Maintenance 4 6 1 Backup battery replacement This battery serves to maintain the run of RTC real time clock so that controller does not lose information about time and date when disconnected from power supply The internal backup battery lifetime is approx 6 years If replacement of backup battery is needed follow these instructions Connect the controller to a PC and save ...

Page 60: ... push the new battery into the holder using a finger Replace the rear cover Use slight pressure to lock the snaps into the housing Pay attention that the cover is in correct position and not upside down Replace the plug in modules and back cover Power the controller on adjust date and time and check all setpoints 6 back to Installation and wiring ...

Page 61: ...d Not Used BIN4 Not used Not Used BIN5 Switch controller to OFF mode REMOTE OFF PAGE 458 BIN6 Switch controller to TEST mode REMOTE TEST PAGE 460 5 1 2 Binary outputs Number Description Function BOUT1 Starter motor control STARTER PAGE 501 BOUT2 Fuel solenoid valve FUEL SOLENOID PAGE 477 BOUT3 Indication of breaker state GCB CLOSE OPEN PAGE 480 BOUT4 Indication of breaker state MCB CLOSE OPEN PAGE...

Page 62: ...s the connection of various PC tools to the controller If you require detailed information on each PC tool please use the included Help in those PC tools or download their Global Guides 5 2 1 USB You may connect to the controller using the USB port In this case standard USB A to B cable should be used Connection using InteliConfig Image 5 1 First screen of InteliConfig select connect to controller...

Page 63: ...ord are not mandatory 5 2 2 RS232 RS485 It is possible to connect to the controller using RS232 or RS485 direct connection serial port or USB to RS232 RS485 converter may be used The following settings should be checked in the controller COM1 Mode page 330 Direct Controller Address page 224 must be set Connection using InteliConfig Image 5 4 First screen of InteliConfig select connect to controlle...

Page 64: ... directly from the PC you use i e one LAN or WAN without any firewalls and other points that may not allow the connection The following settings should to be checked in the controller Controller Address page 224 must be set to the same value as in the PC tool IP Address Mode page 354 can be set to AUTOMATIC when there is DHCP service available Otherwise it should be set to FIXED IP Address page 35...

Page 65: ...nnection using InteliConfig Image 5 7 First screen of InteliConfig select connect to controller Image 5 8 Second screen of InteliConfig select Internet Ethernet Connection using WinScope 1000 Image 5 9 WinScope 1000 screen select Ethernet ...

Page 66: ...value Gateway IP page 356 can be set here when it is used AirGate Connection page 358 must be set to Enabled AirGate Address page 359 currently there is one AirGate server running at URL global airgate link enter this URL into the setpoint IMPORTANT AirGate Key has to be configured User with administrator rights has a possibility to set up or change AirGate Key via InteliConfig using Tools Access ...

Page 67: ...rGate Key adjusted in controller as per description above AirGate Server global airgate link 54441 Username Password use your credentials Object Description Not defined Indicated while the controller is actually not trying to connect to AirGate This is initial value of the status Wait to connect Indicated while the controller is waiting the repetition period before next attempt to connect to a nod...

Page 68: ...Note If you see this status message you have to adjust AirGate Key as per instructions above Connection using InteliConfig In order to connect to InteliConfig following information have to be filled out AirGate ID page 430 AirGate Server AirGate Address page 359 Controller Address page 224 User name and Password AirGate Key IMPORTANT AirGate Key has to be configured User with administrator rights ...

Page 69: ...e to be filled out AirGate ID page 430 AirGate Server AirGate Address page 359 Controller Address page 224 User name and Password Device Access Key AirGate Key Access code is required IMPORTANT AirGate Key has to be configured User with administrator rights has a possibility to set up or change AirGate Key via InteliConfig using Tools Access Administration Change AirGate Key ...

Page 70: ...InteliLite4 AMF20 Global Guide 70 Image 5 13 WinScope 1000 screen select AirGate ...

Page 71: ...5 3 6 Information screen 91 5 3 7 Language selection 93 5 3 8 Display contrast adjustment 94 5 3 1 Front panel elements Image 5 14 Operator interface of InteliLite 4 AMF 20 Control buttons Position Picture Description LEFT button Use this button to move left or to change the mode The button can change the mode only if the main screen with the indicator of currently selected mode is displayed ...

Page 72: ...button to move up or increase value PAGE button Use this button to switch over display pages DOWN button Use this button to move down or decrease value ENTER button Use this button to finish editing a setpoint or moving right in the history page START button Works in MAN mode only Press this button to initiate the start sequence of the engine STOP button Works in MAN mode only Press this button to...

Page 73: ... circuit breaker is closed MCB Status Consists of 3 green LEDs The middle green LED is on if MCB is closed It is driven by MCB CLOSE OPEN output or by MCB feedback signal Side green LEDs are on in case the mains status indicator is ok 5 3 2 Display screens and pages structure The displayed information is structured into pages and screens Use the PAGE button to switch over the pages The page Measur...

Page 74: ... 223 and Main Screen Line 2 page 223 Possibilities are RPM PF Run Hours ATT AIN1 Measurement Screens Note Use the Up and Down buttons to move between measurement pages Note Use the Up and Down buttons to move between measurement pages Note Use the Up and Down buttons to move between measurement pages ...

Page 75: ...and Down buttons to move between measurement pages Note Use the Up and Down buttons to move between measurement pages Note Use the Up and Down buttons to move between measurement pages Note Use the Up and Down buttons to move between measurement pages ...

Page 76: ...move between measurement pages Note Use the Up and Down buttons to move between measurement pages Note Use the Up and Down buttons to move between measurement pages Note Use the Up and Down buttons to move between measurement pages Note Available only with plug in module ...

Page 77: ...move between measurement pages Note Available only with plug in module Note Use the Up and Down buttons to move between measurement pages Note Use the Up and Down buttons to move between measurement pages Note Use the Up and Down buttons to move between measurement pages ...

Page 78: ...ment pages Note Use the Up and Down buttons to move between measurement pages Note Use the Up and Down buttons to move between measurement pages Note Available only with plug in module Note Use the Up and Down buttons to move between measurement pages Note Available only with plug in module ...

Page 79: ...n measurement pages Note Available only with plug in module Note Use the Up and Down buttons to move between measurement pages Note Available only with plug in module Note Use the Up and Down buttons to move between measurement pages Note Available only with ECU supported by TIER4F ...

Page 80: ...ges it is possible to switch seamlessly to the setpoint group page by pressing Page button Note There can be some additional screens and also some screens can be hidden Screen s visibility depends on actual configuration usage of extension or communication modules ECU etc Setpoint Screens Note From all measurement pages you can easily go to the setpoint group page by pressing the Page button ...

Page 81: ...ed setpoint Note Use the Left and the Right button to select required setpoint Note Use the Enter button to enter selected setpoint Note Use Up and Down button to set required value of selected setpoint Note Use the Enter button to confirm adjusted value of setpoint Note Use the Page button to discard changes to set setpoint to previous value and to return to the list of setpoints of selected grou...

Page 82: ...m setpoint group page we can fluently go to the history log pages by pressing the Page button Note Use the Up and the Down button to select required alarm reason Note Use the Enter button to move to the next page of history log Note Use the Up and the Down button to select required alarm reason Note Use the Enter button to move to the next page of history log ...

Page 83: ...and the Down button to select required alarm reason Note Use the Enter button to move to the next page of history log Note Use the Up and the Down button to select required alarm reason Note Use the Enter button to move to the next page of history log Note Use the Up and the Down button to select required alarm reason Note Use the Enter button to move to the next page of history log ...

Page 84: ...and the Down button to select required alarm reason Note Use the Enter button to move to the next page of history log Note Use the Up and the Down button to select required alarm reason Note Use the Enter button to move to the next page of history log Note Use the Up and the Down button to select required alarm reason Note Use the Enter button to move to the next page of history log ...

Page 85: ...Use the Enter button to move to the next page of history log Note Use the Up and the Down button to select required alarm reason Note Use the Enter button to move to the next page of history log Note Use the Up and the Down button to select required alarm reason Note Use Enter button to move to the first page of history log IMPORTANT The records are numbered in reverse order i e the latest newest ...

Page 86: ...ive alarms are displayed as white text on black background It means the alarm is still active i e the appropriate alarm conditions are still present Inactive alarms are displayed as black text on white background It means the alarm is not active i e the appropriate alarm conditions are gone Unconfirmed alarms are displayed with an asterisk This means the alarm is still not acknowledged confirmed E...

Page 87: ...cation module is plugged in the controller The purpose of alarm is to inform that the controller might be or is connected to an untrusted interface and cybersecurity rules are not fulfilled because there is default administrator password Wrn Password reset e mail address is not set appears in alarm list when there is no email address set and the administrator password is not the default one The pu...

Page 88: ... select Login Note Use the Enter button to enter Login Note Use the Up and the Down Button to change the digit Note Use the Left and the Right buttons to move between digits UserID Edit Note Use the Enter button to confirm the UserID or Page button to cancel entering Login ...

Page 89: ... the Right buttons to move between digits Note Use the Enter button to confirm the PIN and Login or the Page button to cancel entering the Login Note In case that invalid UserID or PIN are entered the controller shows Wrong Credentials screen Use the Enter button to enter Login again or the Page Button to go back to menu ...

Page 90: ...ll measurement pages you can fluently go to the setpoint group page by pressing the Page button Note Use the Enter button to enter setpoint group Login Note Use the Up and the Down Button to select Production Mode Note Use the Enter button to enter the Production Mode ...

Page 91: ...ce Disabled is confirmed by Enter button the option Enabled is no longer on the screen and therefore it is not possible to enable Production mode by HMI display screen Use InteliConfig to enable the Production mode 5 3 6 Information screen Note On Main measurement screen press the Enter and the Page button together The Enter button has to be pressed first ...

Page 92: ...InteliLite4 AMF20 Global Guide 92 Note Use the Page button to move to the next page Note Use the Page button to move to the next page Note Use the Up button to move back to main measurement screen ...

Page 93: ...e On Main measurement screen press the Enter and the Page button together The Enter button has to be pressed first Note Use the Page button to move to the next page Note Use the Page button to move to the next page Note Use the Page button to move to the next page ...

Page 94: ...tton to confirm the selected language 5 3 8 Display contrast adjustment Note On any measurement screen press the Enter and the Up button together for higher contrast Note On any measurement screen press the Enter and the Down button together for lower contrast Note After setting the contrast no another action is needed ...

Page 95: ...not shared between display and control unit setpoint Backlight Timeout page 219 Controller language and Controller user mode 5 4 2 IL4 RD Firmware installation The IL4 RD Remote display firmware is installed in the same way as any other InteliLite 4 firmware using the InteliConfig PC tool Reverting the Remote display controller back to regular Gen set controller is carried out the same way Note In...

Page 96: ... 5 4 4 Interconnection variants RS232 It is necessary to use CM RS232 485 communication module on both the Master controller and the Remote display COM 1 communication channel is used with these settings COM 1 Mode Direct COM 1 Communication Speed 57600 or 115200 bps Controller Address 1 32 The maximal distance between Master controller and Remote display is 10 m for RS 232 connection It is recomm...

Page 97: ...er Controller with Two Remote Displays It is possible to combine two of the previous methods of interconnection and connect two Remote display to one Master controller concurrently All parameters and settings are the same as mentioned above Note Onboard RS485 and CM 232 485 communication module can be used to achieve both remote displays being connected via RS485 for IL4 MRS16 and IL4 AMF25 Note I...

Page 98: ...nt screens Setpoint screens and History Log display the same data as the Master controller The front panel buttons on both controllers work the same way All remote display LEDs show the same state as corresponding LEDs on Master controller User can switch screens enter or set password adjust setpoints change language change Configuration Level change display contrast and view history records Note ...

Page 99: ...ity Remote Display IL4 RD FW is able to be uploaded into the following controllers InteliLite 4 AMF25 InteliLite 4 AMF20 InteliLite 4 AMF9 InteliLite 4 AMF8 InteliLite 4 MRS16 Note All controllers from IL4 family can act as Remote Display of master controller and will always be compatible with each other Note If IL4 MRS16 is used as a Remote Display in AMF application the user won t be able to see...

Page 100: ...eo fencing 151 5 5 21 After treatment Support 151 5 5 22 Alternate configuration 156 5 5 23 USB host 157 5 5 24 Firewall 161 5 5 25 E Stop 161 5 5 26 ECU Frequency selection 162 5 5 27 User setpoints 162 6 back to Controller setup 5 5 1 Operating Modes Selecting the operating mode is done with the Left and the Right buttons on the front panel or by changing the Controller Mode page 216 setpoint fr...

Page 101: ...is running GCB can be closed Also MCB can be closed and opened manually using the MCB button regardless of whether the mains is present or not No auto start is performed Note The controller provides interlock between GCB and MCB it means it is never possible to close both CB together AUTO mode AMF The controller does not respond to the buttons Start Stop MCB ON OFF and GCB ON OFF Engine start stop...

Page 102: ...is given by binary input Remote Start Stop page 459 5 5 2 Start stop sequence State Condition of the transition Action Next state Ready Start request PRESTART PAGE 496 on Prestart Time page 227 counter started Prestart RPM 2 or Oil pressure Starting Oil Pressure page 228 or Generator voltage 10V or D voltage is higher than D Threshold page 243 Stop Stop fail OFF Mode selected or Shutdown alarm act...

Page 103: ...ed Running any shutdown condition FUEL SOLENOID PAGE 477 off STOP SOLENOID PAGE 502 on Shutdown Running Stop request READY TO LOAD PAGE 498 off Cooling Time page 240 counter started Cooling RPM 0 or any other shutdown condition READY TO LOAD PAGE 498 off FUEL SOLENOID PAGE 477 off Shutdown GCB CLOSE OPEN PAGE 480 closed Loaded Loaded GCB CLOSE OPEN PAGE 480 opened Running RPM 0 or any other shutdo...

Page 104: ...nergized The engine speed exceeds the value of Starting RPM page 227 or One of the Additional running engine indications page 114 signals is active The controller remains in the Starting phase until the engine speed exceeds the value of Starting RPM page 227 after which it is considered started and the Idle period will follow The maximum duration that the output STARTER PAGE 501 is energized is de...

Page 105: ...InteliLite4 AMF20 Global Guide 105 Image 5 15 Flowchart of start of diesel engine GAS engine The setpoint Fuel Solenoid page 225 must be switched to the Gas position ...

Page 106: ...Pickup must be used in any case The maximum duration that the output STARTER PAGE 501 is energized is determined by the setpoint Maximum Cranking Time page 226 If the engine does not start within this period outputs STARTER PAGE 501 and FUEL SOLENOID PAGE 477 are de energized and a pause with length determined by Cranking Fail Pause page 226 will follow PRESTART PAGE 496 GLOW PLUGS PAGE 484 and IG...

Page 107: ...InteliLite4 AMF20 Global Guide 107 Image 5 16 Flowchart of start of gas engine ...

Page 108: ...its for the generator voltage and frequency are given by setpoints in the Group Generator settings page 260 Note The value of the Minimal Stabilization Time page 237 setpoint has to be lower than the value of Maximal Stabilization Time page 238 setpoint 5 5 5 Connecting to load When the Stabilization page 108 phase is finished the Gen set can be connected to the load The command for connecting the...

Page 109: ... GCB CLOSE OPEN PAGE 480 on Island operation Emergency Start Delay page 269 elapsed MCB Opens On page 283 Gen Run Engine start sequence performed then MCB CLOSE OPEN PAGE 490 off time delay Transfer Delay page 270 performed and GCB CLOSE OPEN PAGE 480 on Island operation Island operation Mains voltage and frequency OK Mains Return Delay page 269 timer started Mains return Mains return Mains failed...

Page 110: ...ins Overfrequency page 277 The alarm Wrn MCB Fail page 539 is not active if the MCB FEEDBACK PAGE 453 matches the expected position given by the MCB CLOSE OPEN PAGE 490 This condition is not required if MCB is open MCB FEEDBACK PAGE 453 is inactive Phase rotation is correct The AMF procedure When the mains failure is detected the following steps are performed If the setpoint MCB Opens On page 283 ...

Page 111: ...opped but at least for the duration of Stop Time page 240 If the Stop Time page 240 has elapsed and the engine has still not stopped the STOP SOLENOID PAGE 502 is de energized for 5 s and then energized again for Stop Time page 240 This is repeated until the engine is stopped The output Ignition page 487 is continuously energized until the engine is stopped Stopped Gen set evaluation The Gen set i...

Page 112: ...gical 0 or D terminal active reached D Threshold page 243 of supply voltage for minimum 1 s or Generator voltage 25 of Nominal Voltage Ph N page 211 or Nominal Voltage Ph Ph page 211 any phase Note Any of these condition will disconnect starter of the engine however for transition to next state RPM needs to be higher than Starting RPM page 227 Engine running conditions Engine speed RPM Starting RP...

Page 113: ...lay 1 s For detected RPM there is no delay Stop engine conditions If no engine running conditions are validated then the controller will wait extra 12 s before leaving the Machine Stop state and releasing the STOP SOLENOID PAGE 502 output Image 5 17 Engine stops in Stop Time page 240 If the total stopping time will exceed setpoint Stop Time page 240 then the Wrn Stop Fail page 537 and binary outpu...

Page 114: ...ble the function The pickup is not used and frequency is not detected on the pickup input Connect the pickup input to the W terminal of the charging alternator if you do not use pickup and the W terminal is available If not leave the input unconnected Oil pressure Starting Oil Pressure page 228 setpoint The oil pressure is evaluated from the analog input or from the ECU if an ECU is configured Bin...

Page 115: ... Vg12 Generator voltage Ph12 Generator Voltage Vg23 Generator voltage Ph23 Generator Voltage Vg31 Generator voltage Ph31 Generator Current Ig1 Generator current Ph1 Generator Current Ig2 Generator current Ph2 Generator Current Ig3 Generator current Ph3 Mains Frequency Mfrq Mains Frequency Mains Voltage Vm1 Mains voltage Ph1 Mains Voltage Vm2 Mains voltage Ph2 Mains Voltage Vm3 Mains voltage Ph3 Ma...

Page 116: ...dervoltage coil for fast opening After opening the breaker there is an internal delay before closing the breaker Delay is 6 seconds 5 seconds for OFF coil and 1 second for UV coil After these 6 seconds breaker can be closed again There is no delay when opening a breaker Breaker control outputs Close Open An output for control of a contactor Its state represents the breaker position requested by th...

Page 117: ...n page 283 Mains Fail Mains Undervoltage Delay page 276 1 If a 230 V motor driven circuit breaker is used on the MCB position and an undervoltage coil is not fitted it is not possible to open the breaker after the mains have failed because there is no power for the motor drive until the Gen set is started and providing voltage Adjusting the setpoint MCB Opens On page 283 Gen Run will prevent trigg...

Page 118: ...age 5 20 Breaker failure breaker close open in steady position open Image 5 21 Breaker failure breaker close open in steady position close When binary output breaker close open opens there is 5 sec delay for breaker failure detection Image 5 22 Breaker failure breaker close open opens When binary output breaker close open closes there is 5 sec delay for breaker failure detection ...

Page 119: ...er close open closes 5 5 13 Protections Fixed Protections Fixed protections are built in protections for Generator Engine Mains or for other functionalities battery voltage fuel theft D etc Their purpose is to inform or perform actions when the malfunction is detected ...

Page 120: ... activation Action CB open Action Gen set stop SD Override blocking Common LBO History Record Only 1 Hst Alarm List Indication 1 ALI Warning 1 Wrn AL COMMON WRN PAGE 467 Shutdown 2 Sd AL COMMON SD PAGE 467 Breaker Open Cool Down 2 BOC AL COMMON BOC PAGE 466 Shutdown Override 2 Sd InteliLite4 AMF20 Global Guide 120 ...

Page 121: ...ey are recorded into alarm list or history It only blocks their actions Shutdown Override blocks all level 2 Sd BOC fixed protection It does not block level 1 Wrn AHI Hist or protection of type Sd Override Some generators or engine protections have an option to DISABLE the protection The setting is done by using the setpoint which is associated to the fixed protection Each setpoint offers these op...

Page 122: ...ge 567 BOC Gen Voltage Unbalance Ph Ph page 567 Alarms Protection name Frequency Mains Overfrequency page 551 Mains Underfrequency page 551 Others ALI Mains Ph L1 Inverted page 549 ALI Mains Ph L2 Inverted page 549 ALI Mains Ph L3 Inverted page 549 ALI Mains Ph Rotation Opposite page 550 Voltage Mains L1 Overvoltage page 568 Mains L1 Undervoltage page 568 Mains L2 Overvoltage page 569 Mains L2 Und...

Page 123: ...nputs Controller Modules Values ECU Generator Mains others Statistics Binary inputs Controller Modules ECU Binary outputs PLC Protection states LBOs Source Type Name of activation Description Analog Over Limit Protection is activated if value is over limit Over Limit Fls Protection is activated if value is over limit or in a fault state Under Limit Protection is activated if value is under limit U...

Page 124: ... open Action Gen set stop SD Override blocking Common LBO History Record Only 1 Hst Alarm List Indication 1 ALI Alarmlist indication history record 1 AHI Warning 1 Wrn AL COMMON WRN PAGE 467 Shutdown 2 Sd AL COMMON SD PAGE 467 Breaker Open Cool Down 2 BOC AL COMMON BOC PAGE 466 Shutdown Override 2 Sd InteliLite4 AMF20 Global Guide 124 ...

Page 125: ...ON FORCE DISABLE PAGE 455 or by LBI SD OVERRIDE PAGE 460 Electrical Protection The protection is blocked depending on engine state It is unblocked once Maximal Stabilization Time page 238 is elapsed or GCB is closed It can also be blocked by LBI SD OVERRIDE PAGE 460 Protection blocking Note LBI SD OVERRIDE PAGE 460 Shutdown Override does not block evaluation of user protection conditions and their...

Page 126: ...elete selected protection by clicking on the icon Edit selected protection by clicking on the icon Adding analog protection Selecting the input source see User Protections on page 123 Selecting the protection type see Fixed Protection types on page 120 Selecting the protection activation see Protection activation on page 123 Selecting the block type see Protection blocking on page 125 Selecting if...

Page 127: ...l Text input for Alarm History message If user protection state is checked then created user protection has LBO located in Bin Values in the Group User Protection States page 422 Adding binary protection Selecting the input source see User Protections on page 123 Selecting the protection type see Fixed Protection types on page 120 Selecting the protection activation see Protection activation on pa...

Page 128: ...CTIONS STATES 2 PAGE 421 FIXED PROTECTIONS STATES 3 PAGE 421 FIXED PROTECTIONS STATES 4 PAGE 421 FIXED PROTECTIONS STATES 5 PAGE 422 User protections states During the Configuration of protections in InteliConfig page 126 you can decide whether you want to add user protection state for the protection The name is the same as the alarm s message User protection states are in a group of 32 values Not...

Page 129: ...g to this category This category is not configurable to binary and analog input alarms The alarm is evaluated only when LBI PROTECTION FORCE DISABLE PAGE 455 is not active If an alarm is being evaluated and the appropriate alarm condition is fulfilled the delay of evaluation will start to run The delay is adjustable by a setpoint in the case of built in alarms analog input alarms or is adjusted vi...

Page 130: ...ppears for the alarmist automatically as soon as the cause disappears Standard alarm outputs HORN PAGE 486 and ALARM PAGE 469 are not activated History record only Hst The event is recorded into the history Standard alarm outputs HORN PAGE 486 and ALARM PAGE 469 are not activated Alarm types Level 2 The level 2 alarm indicates that a critical level of the respective value or parameter has been rea...

Page 131: ... number In this case the lower limit is set as one half of the RL point of the sensor curve characteristic Image 5 27 Sensor failure detection principle Remote alarm messaging If the communication plug in module is connected to the controller the controller can send SMS messages CM RS232 485 module and emails CM2 4G GPS or CM3 Ethernet modules at the moment when a new alarm appears in the Alarm li...

Page 132: ...iagnostic Trouble Code which contains information about the subsystem where the alarm occurred the alarm type and the alarm occurrence counter The most common fault codes are translated into text form Other fault codes are displayed as a numeric code and the engine fault codes list must be used to determine the reason Built in alarms Events specification Protection type Description Wrn Battery Ove...

Page 133: ...otection is active Protection evaluation starts 5 seconds after reaching Starting RPM page 227 Emergency Stop SD If the input Emergency Stop is active shutdown is immediately activated E Stop SD If the input E Stop is active shutdown is immediately activated GCB Fail SD Failure of generator circuit breaker MCB Fail WRN Failure of mains circuit breaker Sd RPM Measurement Fail SD Failure of magnetic...

Page 134: ...mer 1 Duration page 294 Timer 1 Repeated page 295 Timer 1 Repeat Day page 295 Timer 1 Day page 296 Timer 1 Repeated Day In Week page 296 Timer 1 Repeat Day In Month page 296 Timer 1 Repeat Week In Month page 297 Timer 1 Refresh Period page 298 Timer 1 Weekends page 299 Timer 1 Setup page 293 There are up to 4 Timers available in the InteliLite 4 For more information see Group Scheduler on page 289...

Page 135: ...terface In controller go to the Scheduler setpoint group Select the function of timer via Timer 1 Function page 292 setpoint Then go to Timer 1 Setup and press the Enter button In Timer 1 Repetition page 294 setpoint select Once mode Then adjust Timer 1 First Occur Date page 293 Timer 1 First Occur Time page 294 and Timer 1 Duration page 294 Note Use the Left and the Right buttons to move between ...

Page 136: ...go to the Scheduler setpoint group Select the function of timer via Timer 1 Function page 292 setpoint Then go to Timer 1 Setup and press the Enter button In Timer 1 Repetition page 294 setpoint select Repeated mode Then adjust Timer 1 First Occur Date page 293 Timer 1 First Occur Time page 294 and Timer 1 Duration page 294 In setpoint Timer 1 Repeated page 295 select Daily and adjust Timer 1 Refr...

Page 137: ...roller go to the Scheduler setpoint group Select the function of timer via Timer 1 Function page 292 setpoint Then go to Timer 1 Setup and press the Enter button In Timer 1 Repetition page 294 setpoint select Repeated mode Then adjust Timer 1 First Occur Date page 293 Timer 1 First Occur Time page 294 and Timer 1 Duration page 294 In setpoint Timer 1 Repeated page 295 select Weekly and adjust Time...

Page 138: ... settings adjust date and time of first occurrence of timer Also adjust the duration of each occurrence of timer Then select the type of monthly repetition and the xth day of repetition Timer 1 Repeat Day In Month page 296 Than select the xth month of repetition Example On image example first start of timer will be 1 1 2016 at 12 00 Duration will be 1 hour Timer will be activated again every 2nd d...

Page 139: ...eated mode Then adjust Timer 1 First Occur Date page 293 Timer 1 First Occur Time page 294 and Timer 1 Duration page 294 In setpoint Timer 1 Repeated page 295 select Monthly and adjust type of monthly repetition via Timer 1 Repeat Day page 295 Timer 1 Refresh Period page 298 xth month of repetition and Timer 1 Repeat Day In Month page 296 concrete day in repeated months The second type of monthly ...

Page 140: ...r will be activated again every 4th hour for 1 hour Set up via controller interface In controller go to the Scheduler setpoint group Select the function of timer via Timer 1 Function page 292 setpoint Then go to Timer 1 Setup and press the Enter button In Timer 1 Repetition page 294 setpoint select Repeated mode Then adjust Timer 1 First Occur Date page 293 Timer 1 First Occur Time page 294 and Ti...

Page 141: ...dding Status page 418 Stage LBO Stage 1 LOAD SHEDDING STAGE 1 PAGE 489 Stage 2 LOAD SHEDDING STAGE 2 PAGE 489 Load shedding outputs How the Load shedding controls the Load shedding outputs The load shedding function is active in all controller modes except OFF Load shedding has 2 steps and each step is linked with its own binary output LOAD SHEDDING STAGE 1 PAGE 489 LOAD SHEDDING STAGE 2 PAGE 489 ...

Page 142: ...ges up to the highest one configured User can configure any number of these either in PLC or as LBO but if just Dummy Load Stage 1 and Dummy Load Stage 5 are configured Dummy Load On Delay page 288 will trigger five times anyway when going from Dummy Load Stage 1 to Dummy Load Stage 5 Whenever controller checks conditions and Dummy Load function is triggered it will do the following depending on t...

Page 143: ...o timer for DUMMY LOAD STAGE 3 PAGE 473 IMPORTANT Check how big your load bank is and set the Dummy Load On page 287 and Dummy Load Off page 288 setpoints to correct levels so that when dummy load is activated power will not immediately go over the Dummy Load Off page 288 5 5 18 Sensor curves Background of the sensor calibration To correct measuring error of each analog input pressure temperature ...

Page 144: ...1000 Ω General line 6 0 1000 Ω General line 7 0 1000 Ω General line 8 0 1000 Ω General line 9 0 1000 Ω General line 10 0 1000 Ω General line 11 0 1000 Ω General line 12 0 1000 Ω General line 13 0 1000 Ω Note Curves can be modified via InteliConfig Some standard curves are also prepared in InteliConfig IMPORTANT For right behavior of function Total Fuel Consumption curve for analog input FUEL LEVEL...

Page 145: ...the editor If the currently opened archive does not contain any PLC program then an empty drawing is created automatically when you select the PLC Editor The procedure of creation of a PLC drawing program contains the following essential steps Adjust the sheet to your needs See Working with sheets page 146 for more information Add PLC blocks into the sheets See Adding PLC blocks page 146 for more ...

Page 146: ...e and intuitive Follow the procedure below to add PLC block Select the required block from the list of available PLC blocks at the left and drag it into the sheet Double click on the block and adjust the properties of the block See List of PLC blocks page 510 for more information about blocks Connect the block inputs and outputs by drawing wires in the sheet See Define inputs and outputs page 147 ...

Page 147: ...press delete button Also the delete selection function can be used Note To see context help for selected PLC block just press the F1 button Define inputs and outputs Image 5 40 Blank sheet of PLC Editor Inputs Sheet inputs are located at the left side of a sheet Follow the procedure below to add or edit an input ...

Page 148: ... source from the following categories Ana values this category contains all analog values available in the controller as analog inputs electrical values values from ECU etc All setpoints this category contains all setpoints of the controller except the dedicated PLC setpoints Names resolutions and dimensions of these setpoints can not be modified Image 5 41 PLC inputs Outputs Sheet output is locat...

Page 149: ...ow to create wire Situate the mouse pointer over the starting point of the wire If the area under the mouse pointer is a connection point the pointer will change color fill of pointer will be white Press and hold the left mouse button and drag the wire to the destination of required connection point If you point over a valid connection point the connection point will be marked with a red circle Re...

Page 150: ...00 ms The blocks are executed in order according to block numbers item numbers which are indicated in each block Block numbers are assigned automatically according to their position on sheet Image 5 43 PLC execution logic IMPORTANT Please always check that the blocks are ordered correctly especially if you use direct feedbacks from outputs to inputs within one sheet Wrong order may lead to incorre...

Page 151: ...to set two concentric geo circles within which the unit is allowed to be located Each geo circle is defined as a circular geographic area with its center common for both geo circles named Home Position This point is adjusted via setpoints Home Latitude page 324 and Home Longitude page 325 and radius named Fence Radius adjusted via setpoints Fence 1 Radius page 327 and Fence 2 Radius page 329 The P...

Page 152: ...ng a blank screen inactive lamps are represented by dotted icons For no active lamp the screen shows all dotted icons Please see examples below Image 5 44 Example of active After treatment screen Image 5 45 Example of inactive After treatment screen Universal lamps icons Universal lamp icons are shown on the After Treatment screen Based on specific value read in specific frame with specific SPN ev...

Page 153: ...CU Wait To Start page 533 ECU WAIT TO START PAGE 475 ECU WAIT TO START BLINK PAGE 446 ECU WAIT TO START FAST BLINK PAGE 446 ECU WAIT TO START SOLID PAGE 447 ATT DPF Lamp Wrn ATT DPF Lamp page 534 ATT DPF LAMP PAGE 470 ATT DPF LAMP BLINK PAGE 440 ATT DPF LAMP FAST BLINK PAGE 441 ATT DPF LAMP SOLID PAGE 441 ATT HEST Lamp Wrn ATT HEST Lamp page 534 ATT HEST LAMP PAGE 470 ATT HEST LAMP BLINK PAGE 441 ...

Page 154: ...amps during prestart is located in InteliConfig Controller Configuration Modules ECU module Electronic control unit settings Note Aftertreatment support can be disabled Aftertreatment HMI Screen is hidden and alarms related to aftertreatment are not shown Use the checkbox Disable aftertreatment support located in InteliConfig Controller Configuration Modules ECU module Electronic control unit sett...

Page 155: ...ECUs however do not include LBI ATT INTERLOCK PAGE 443 and closing just LBI ATT FORCE REGEN PAGE 441 is enough to start the regeneration process Some engines may require the regeneration to run on higher RPM than is normally expected For this reason we recommend to adjust Overspeed Limit setpoint The exact process and conditions for each particular engine should be studied carefully from the engin...

Page 156: ...3 sets of alternate configurations in a controller Configuration set 1 Configuration set 2 Configuration set 3 Nominal Power Split Phase 1 page 377 Nominal Power 1 page 376 Nominal RPM 1 page 372 Nominal Frequency 1 page 373 Nominal Voltage Ph N 1 page 373 Nominal Voltage Ph Ph 1 page 373 Nominal Current 1 page 374 Connection Type 1 page 374 ECU Speed Adjustment 1 page 376 Nominal Power Split Phas...

Page 157: ...lash drive following steps have to be followed Download and install latest psi package from www comap control com Use InteliConfig Tools USB Flash Export Export Manager There must be 4 files generated or copied on USB flash drive Note M N P B stands for number 0 9 The following functions are supported Firmware upload Access level 3 is required Configuration upload Access level 3 is required Firmwa...

Page 158: ... for more information see Configuration download on page 160 New configuration the configuration created in InteliConfig for the purpose of uploading it into the controller using the USB memory stick The new configuration is recognized due to its name The name must contain the specific string InteliLite4 Genset name M N P B ail4 Note M N P B stands for number 0 9 Compatible firmware the firmware v...

Page 159: ...re loaded is made Confirming file txt on USB Flash Drive is made Name SN_YYMMDDHHMM Content Serial number Year Date Time Upgrade to the FW Name of the new FW successful Confirmation pop up message Controller programming successful Configuration upload Point 1 controller detects that USB Flash Drive has been inserted If the communication via USB B is running the controller will not detect the USB m...

Page 160: ...ive Controller automatically selects the compatible firmware with the highest version Point 7 Pop up message Do you want to update firmware and configuration Point 8 Configuration and firmware upload Current archive is download to USB flash drive Name SN_YYMMDDHHMM New firmware is uploaded into the controller New configuration is uploaded into the controller History record Firmware loaded and Conf...

Page 161: ...ll If the rules are not set up properly and the connection is made remotely loss of connection can happen 5 5 25 E Stop Binary outputs for the control of some essential functions are internally wired as safe meaning that their deactivation is directly bound with the dedicated Input E STOP not evaluated as the LBI in the controller These BO are fully configurable and are used e g for the Starter an...

Page 162: ...nformation about connection see E Stop on page 51 5 5 26 ECU Frequency selection Value Ecu freq select is calculated from Nominal Frequency page 215 setpoint The sequence for frequency change is executed automatically engine must be in still condition in the following steps 1 Starting of the engine is blocked state Not Ready 2 LBO ECU Power relay is activated 3 Wait 5 s 4 LBO Stop Pulse is set for...

Page 163: ...t number CO can be found via InteliConfig Tools tab Generate Cfg image COM User setpoints can be used to manage User protections and PLC Add User setpoint Delete selected User setpoint Edit selected User setpoint Image 5 49 Setting parameters of a user setpoint ...

Page 164: ... requires a user to be logged in When a task read data write data control is to be performed the access level of the user who is currently logged in must be higher or equal to the access level required for the particular task User must have their user account defined by the administrator of the controller before the user can log in into the controller and perform monitoring control or configuratio...

Page 165: ...display when connected via Ethernet PIN 4 digit password to be used together with UID Access level Determines Access to controller data page 173 User account must have the following properties Implicit account At trusted interfaces there is an implicit user automatically logged in at any time if no other explicit user is logged in at the respective interface This allows terminal devices e g intern...

Page 166: ...ber of the controller Example 12345678 When the controller is being configured for operation the desired user accounts including the administrator account should be created and then the factory default account can be deleted IMPORTANT Adjust the backup e mail address before you delete the default administrator account This address is used as second authentication factor in password reset request a...

Page 167: ... the user management dialog is opened IMPORTANT The total available number of accounts in the controller is 5 Adding an account Click on the button in the lower left corner of the user management window then provide the account properties as described in User accounts page 165 Note Rules for the User accounts page 165 credentials apply and some items are optional Deleting an account Select the acc...

Page 168: ...le to change user name or UID Instead of this create a new account with the required changes and delete the original one Cloning accounts Cloning feature allows user to clone user accounts together with controller firmware and configuration Note If the archive where the save of the clone is made is configured with the plug in module it s firmware can also be a part of the clone Save the clone To p...

Page 169: ...s section These newly created accounts are stored in the clone At least one user with administrator rights level 3 must be defined Recovery Email address has to be set AirGateKey is not mandatory but recommended when the AirGate connection is used to access the controller Image 5 51 Create accounts Package protection Set up password for clone file Create clone To load the clone to the controller c...

Page 170: ... clone 1 Select required clone and click on Next button 2 Following window appears Image 5 53 Create clone 3 Select required connection type 4 Fill in the password in case the clone was saved by selected Package protection option 5 Click on Clone button ...

Page 171: ...appears Image 5 54 ImEx Clone Exporting clone It is possible to export clone from InteliConfig software into any location To export the clone click on the Export clone icon Following window appears Image 5 55 Save as clone 1 Type required clone name into File name bar 2 Choose required folder 3 Click on Save button ...

Page 172: ... e g e mail to inform about that situation The exact behavior of the controller depends on the situation Password protection 1 If a user performs five consecutive attempts to login using username password providing correct username but incorrect password the respective user account is blocked for a time period of 1 minute The attempts count regardless of the interface from which it is performed 2 ...

Page 173: ... object and operation There are 4 access levels available level 0 to level 3 Level 3 is administrator level and users who have this level have full control over the controller Reading data The access level required for reading data from controller is fixedly adjusted to 0 That means reading of data except some system objects is available for any user Writing data The access level required to write...

Page 174: ...ontroller for entering the password has no influence on controller Gen set operation Note Permanent blocking cannot occur accidentally just by user mistake It can be practically triggered only by a focused activity Resetting the administrator password If the administrator password is lost or controller is permanently locked due to brute force attack protection proceed according to a procedure desc...

Page 175: ...InteliLite4 AMF20 Global Guide 175 Reset password procedure 1 Connect InteliConfig 2 Get the password reset request code and send it via e mail to support comap control com ...

Page 176: ...InteliLite4 AMF20 Global Guide 176 3 Once you receive the reply from ComAp copy the code from the e mail all characters inside the box as indicated below ...

Page 177: ... communication New technology CCS is used for an authentication and an encryption of the ComAp protocol via Internet ethernet AirGate This technology is based on strong and proven cryptographic algorithms and has successfully passed penetration tests and cybersecurity audit 6 back to Controller setup ...

Page 178: ...n of the modules see Plug in module installation on page 58 RS232 interface uses COM1 Mode page 330 port of the controller Use a cross wired serial communication cable with DB9 female connectors and signals Rx Tx GND Note Also USB RS232 convertor can be used Image 6 1 Cross wired RS232 cable is used Image 6 2 Cross wired RS232 cable and USB is used Connection via RS485 A plug in communication modu...

Page 179: ... time via AirGate only two remote clients at the same time Eight remote clients can be connected at the same time six direct IP clients and two AirGate clients To connect your PC tool to the controller use the INTERNET connection type and just put the CM3 Ethernet IP address into the Gen set address box in the PC tool Image 6 4 Ethernet cable is used Connection via USB USB interface uses HID profi...

Page 180: ... the remaining network infrastructure The static IP used in the controller must be selected in accordance with the local network in which CM3 Ethernet is connected The static IP used in the controller must be excluded from the pool of addresses which is assigned by DHCP server which is in charge of the respective local network The local infrastructure must generally allow using devices with manual...

Page 181: ...c IP address is not possible Only two remote clients can be connected at the same time This connection type is active if AirGate connection is enabled Setpoint AirGate Address page 359 must contain AirGate server address It can be entered in text form as well as numeric form There is a public AirGate server available at the address global airgate link Once the controller is connected to the Intern...

Page 182: ...Mains Returned Load on Mains Load on Gen set Test On Load Message structure Gen set Name hh mm ss dd mm yyyy hh mm ss Mains Fail hh mm ss AMF Start hh mm ss Load on Gen set hh mm ss Mains Returned hh mm ss Load on Mains hh mm ss AMF Stop Alarm SMS The InteliLite 4 controller equipped with the CM2 4G GPS communication module is able to send Alarm SMS according to the setting of setpoints Wrn Messag...

Page 183: ... Controller Name XXX Serial number XXX SW branch XXX SW version XXX Application XXX Appl version XXX Date dd mm yyyy Time hh mm ss Alarm list Alarm 1 Alarm 2 Alarm 3 Events hh mm ss Event 1 hh mm ss Event 2 hh mm ss Event 3 Alarm Email The InteliLite 4 controller equipped with the CM3 Ethernet communication module is able to send Alarm Emails according to the setting of setpoints Wrn Message page ...

Page 184: ...nication 6 2 1 SNMP SNMP is an UDP based client server protocol used for providing data and events into a supervisory system building management system The controller plays the role of a SNMP Agent while the supervisory system plays the role of a SNMP Manager CM3 Ethernet module is required for SNMP function Supported versions SNMP v1 and SNMP v2 The SNMP Agent function is to be enabled by the set...

Page 185: ...version type and configuration GroupW contains write only objects NotificationData group contains objects that are accessible only as bindings of the notification messages SMI version In InteliConfig the MIB table may be exported in two different formats SMI v1 and SMI v2 The format which shall be used for export depends on the SNMP Manager and the SMI version that it supports Typically SMI v1 is ...

Page 186: ...t system or for remote monitoring via 3rd party monitoring tools MODBUS RTU can be used on serial interfaces via on board RS485 connector or via CM RS232 485 communication module The MODBUS RTU server must be activated by switching the setpoint COM1 Mode page 330 or COM2 Mode page 332 into the Modbus position The serial speed for MODBUS RTU communication is adjusted by the setpoint COM1 MODBUS Com...

Page 187: ...ultiple data types in the controller but only one data type in MODBUS the register which is 2 byte long a mapping table is necessary to compose and decompose the MODBUS messages correctly Data type Meaning Number of registers Data maping Integer8 1 byte signed integer 1 MSB sign extension LSB value Unsigned8 1 byte unsigned integer 1 MSB 0 LSB value Integer16 2 byte signed integer 1 MSB value MSB ...

Page 188: ...e of the 4 character LongStr Zero terminated string of max 31 ASCII characters 16 MSB1 ASCII value of the 1 character LSB1 ASCII value of the 2 character MSB2 ASCII value of the 3 character LSB2 ASCII value of the 4 character Date Date dd mm yy 2 MSB1 BCD dd LSB1 BCD mm MSB2 BCD yy LSB2 0 Time Time hh mm ss 2 MSB1 BCD hh LSB1 BCD mm MSB2 BCD ss LSB2 0 Alarm An item of the Alarmlist 27 MSB1 reserve...

Page 189: ...trollers regardless of the configuration Register addresses Number of registers Access Data type Meaning 4200 4201 2 read write Time RTC Time in BCD code 4202 4203 2 read write Date RTC Date in BCD code 4204 1 read write Unsigned8 Index of the language that is used for text data provided by MODBUS e g alarmlist messages 4205 4206 2 read Unsigned32 Last application error To be read after the device...

Page 190: ...ter addresses 4207 4208 Use function 16 2 Write the command code into the register 44210 register address 4209 Use function 6 3 Optional Read the command return value from the registers 44208 44209 register addresses 4207 4208 Use function 3 4 If the command was executed the return value is as listed in the table If the command was accepted but there was an error during execution the return value ...

Page 191: ... Values Allowed Modbus functions 03 04 Register address Com Obj Name Dimension Type Len Dec Min Max Group 01053 8213 BatteryVoltage V Integer 2 1 0 400 Controller I O Request Numbers in Hex 01 03 04 1D 00 01 15 3C Controller address Modbus function Register address 041Dhex 1053dec Number of registers CRC Response Numbers in Hex 01 03 02 00 F0 B8 00 Controller address Modbus function Length of data...

Page 192: ...e Len Dec Min Max Group 01227 9018 Nominal Power kW Integer 2 0 0 32767 Generator Request Numbers in Hex 01 03 04 CC 00 01 45 05 Controller address Modbus function Register address 04CChex 1228dec Number of registers CRC Response Numbers in Hex 01 03 02 00 C8 B9 D2 Controller address Modbus function Length of data 02hex 2 bytes read Data 00C8hex 200dec CRC Read nominal power is 200 kW ...

Page 193: ...Numbers in Hex 01 03 04 2C 00 01 44 F3 Controller address Modbus function Register address 042Chex 1068dec Number of registers CRC Response Numbers in Hex 01 03 02 00 12 38 49 Controller address Modbus function Length of data 02hex 2 bytes read Data 0012hex 00010010bin CRC Binary inputs is 00010010 This means Binary input 2 and binary input 5 are active Note You can use Modbus function 4 instead o...

Page 194: ...ack Controller I O 00002 Value 8235 Binary Inputs 3 Emergency Stop Controller I O We will read state of MCB Feedback binary input Request Numbers in Hex 01 01 00 01 00 01 AC 0A Controller address Modbus function Register address 0001hex 0001dec Number of registers CRC Response Numbers in Hex 01 01 01 01 90 48 Controller address Modbus function Length of data 01hex 1 byte read Data 01hex active CRC...

Page 195: ...e Table List of commands and arguments page 190 Action Command code Argument Return value Engine start 0x01 0x01FE0000 0x000001FF Engine stop 0x01 0x02FD0000 0x000002FE Request 1 2 Numbers in Hex 01 10 10 6F 00 03 06 Controller address Modbus function 10hex 16dec Register address 106Fhex 4207dec Number of registers Data length in bytes Request 2 2 Numbers in Hex 01 FE 00 00 00 01 68 0B Argument Co...

Page 196: ...ex 01 06 0B C0 00 00 8B D2 Controller address Modbus function Register address 0BC0hex 3008dec Allways zero CRC Written setpoint nominal power is 100 kW CRC calculation The check field allows the receiver to check the validity of the message The check field value is the Cyclical Redundancy Check CRC based on the polynomial x 16 x 15 x 2 1 CRC is counted from all message bytes preceding the check f...

Page 197: ...tifier usually 0 Length of data bytes following Controller address Modbus function Register address 041Dhex 1053dec Number of registers Response Numbers in Hex 00 00 00 00 00 05 01 03 02 00 F0 transaction identifier usually 0 protocol identifier usually 0 Length of data bytes following Controller address Modbus function Length of data 02hex 2 bytes read Data 00F0hex 240dec We read a value of 240 f...

Page 198: ...output Type Build in monochromatic 3 2 Resolution 132 64 px Display USB Device Non isolated type B connector USB Host Non isolated type A connector CAN 1 Non isolated 250 50 kbps Terminator impedance 120 Ω Communications Measurement inputs 3ph Gen current Measurement range 5 A Max allowed current 10 A Accuracy 20 mA for 0 2 A 1 of value for 2 5 A Input impedance 0 1 Ω Current measurement Dedicated...

Page 199: ...ment Setpoints are organized into groups according to their meaning Setpoints can be adjusted from the controller front panel PC MODBUS etc All setpoints can be protected by a password against unauthorized changes Password protection can be assigned to the setpoints during the configuration procedure IMPORTANT Do not write setpoints repeatedly e g power control from a PLC by repeated writing of ba...

Page 200: ... Manual 219 Backlight Timeout 219 Horn Timeout 220 Fail Safe Binary State 220 Zero Power Mode 221 Run Hours Source 221 User Logging Record 222 Mains Voltage Detection in MRS 222 Subgroup Phase Rotation 223 Phase Rotation 223 Subgroup HMI Settings 223 Main Screen Line 1 223 Main Screen Line 2 223 Screen Filter 224 Group Communication Settings 224 Subgroup Controller Address 224 Controller Address 2...

Page 201: ...5 ECU Speed Adjustment 255 Group Maintenance Timers 256 Subgroup Maintenance Timer 1 256 Maintenance Timer 1 RunHours 256 Maintenance Timer 1 Interval 256 Maintenance Timer 1 Protection 257 Subgroup Maintenance Timer 2 257 Maintenance Timer 2 RunHours 257 Maintenance Timer 2 Interval 258 Maintenance Timer 2 Protection 258 Subgroup Maintenance Timer 3 259 Maintenance Timer 3 RunHours 259 Maintenanc...

Page 202: ...Reconnection Level 285 Load Reconnection Delay 286 Auto Load Reconnection 286 Subgroup Dummy Load 287 Dummy Load Active 287 Dummy Load On 287 Dummy Load On Delay 288 Dummy Load Off 288 Dummy Load Off Delay 288 Group Scheduler 289 Subgroup Time Date 289 Time 289 Date 289 Time Stamp Period 290 DST Switching Mode 290 DST Period Rule 291 Time Mode 291 Subgroup Timer 1 292 Timer 1 Function 292 Timer 1 ...

Page 203: ...4 Geo Fencing 324 Subgroup Position 324 Home Latitude 324 Home Longitude 325 Subgroup Fence 1 326 Fence 1 Protection 326 Fence 1 Radius 327 Fence 1 Delay 327 Subgroup Fence 2 328 Fence 2 Protection 328 Fence 2 Radius 329 Fence 2 Delay 329 Group Plug In Modules 329 Subgroup Slot A 329 Slot A 329 Subgroup Slot B 330 Slot B 330 Group CM RS232 485 330 Subgroup COM1 Setting 330 COM1 Mode 330 COM1 Commu...

Page 204: ...S IP Address 2 357 IP Firewall 358 Subgroup AirGate Settings 358 AirGate Connection 358 AirGate Address 359 AirGate Port 359 Subgroup ComAp Client Settings 360 Direct Connection 360 Direct Connection Port 360 ComAp Client Inactivity Timeout 361 Subgroup MODBUS Settings 361 MODBUS Server 361 MODBUS Client Inactivity Timeout 361 Subgroup SNMP Settings 362 SNMP Agent 362 SNMP Trap Format 362 SNMP Tra...

Page 205: ...Frequency 2 378 Nominal Voltage Ph N 2 378 Nominal Voltage Ph Ph 2 378 Nominal Current 2 379 Connection type 2 379 ECU Speed Adjustment 2 381 Nominal Power 2 381 Nominal Power Split Phase 2 382 Subgroup Configuration 3 382 Nominal RPM 3 382 Nominal Frequency 3 383 Nominal Voltage Ph N 3 383 Nominal Voltage Ph Ph 3 383 Nominal Current 3 384 Connection type 3 384 ECU Speed Adjustment 3 386 Nominal P...

Page 206: ...n real will represent 1 hour 6 back to List of setpoints Subgroup Power settings Nominal Power Setpoint group Basic settings Related FW 1 3 0 Range units 1 5 000 kW Default value 200 kW Alternative config YES Step 1 kW Comm object 8276 Related applications AMF MRS Config level Standard Setpoint visibility Always Description Nominal power of the Gen set Generator Overload BOC page 260 protection is...

Page 207: ...s setpoint against editing you also have to lock setpoint Nominal Power Split Phase 1 page 377 Nominal Power Split Phase 2 page 382 and Nominal Power Split Phase 3 page 387 6 back to List of setpoints Subgroup Current settings Nominal Current Setpoint group Basic settings Related FW 1 3 0 Range units 1 10 000 A Default value 350 A Alternative config YES Step 1 A Comm object 8275 Related applicatio...

Page 208: ...nfig level Standard Setpoint visibility Always Description Current transformers ratio of Gen set 6 back to List of setpoints Gen CT Ratio Sec Setpoint group Basic settings Related FW 1 3 0 Range units 1A 5A Default value 5A Alternative config NO Step Comm object 10556 Related applications AMF MRS Config level Standard Setpoint visibility Always Description Current transformers ratio of Gen set 6 b...

Page 209: ... is hidden Statistics screens values Gen set kWh Gen set kVArh Mains kWh and Mains kWArh are hidden Main screen kW meter is replaced by generator voltage meter Generator L1 N voltage is displayed for Monopahse Splitphase L1L2 Splitphase L1L3 and High Leg delta connection types Generator L1 L2 voltage is displayed for 3ph3w and 3ph4w connection types Group Load is hidden Group Statistics values Gen...

Page 210: ...n Open Delta Ungrounded Wye Corner Grounded Delta Split Phase Delta Three phase voltage measurement L1 L2 L3 with 120 phase shift No neutral is available 3x CT Current Transformer 3Ph4Wire Grounded Star Grounded Wye connection 3PY Three phase voltage measurement L1 L2 L3 with 120 phase shift 3x CT Current Transformer High Leg D High Leg Delta connection Three phase voltage measurement L1 L2 L3 3x ...

Page 211: ...nt against editing you also have to lock setpoint Nominal Voltage Ph N 1 page 373 Nominal Voltage Ph N 2 page 378 and Nominal Voltage Ph N 3 page 383 6 back to List of setpoints Nominal Voltage Ph Ph Setpoint group Basic settings Related FW 1 3 0 Range units 80 40 000 V Default value 400 V Alternative config YES Step 1 V Comm object 11657 Related applications AMF MRS Config level Standard Setpoint...

Page 212: ...oltage is lower than 300 V in all three phases and phase neutral voltage is lower than or equal to 160 V in all three phases 6 back to List of setpoints Nominal Voltage 3Ph High Y Setpoint group Basic settings Related FW 1 3 0 Range units 80 20 000 V Default value 277 V Alternative config YES Step 1 V Comm object 20812 Related applications AMF MRS Config level Standard Setpoint visibility Visible ...

Page 213: ...tion type page 209 is High Leg D Set this setpoint to 120 V with high leg delta system which works with the high leg voltage 208 V L2 N 6 back to List of setpoints Nominal Voltage SplitPhase Setpoint group Basic settings Related FW 1 3 0 Range units 80 20 000 V Default value 120 V Alternative config YES Step 1 V Comm object 20814 Related applications AMF MRS Config level Standard Setpoint visibili...

Page 214: ...nt group Basic settings Related FW 1 3 0 Range units 0 1 500 0 V V Default value 1 0 V V Alternative config NO Step 0 1 V V Comm object 9579 Related applications AMF MRS Config level Advanced Setpoint visibility Always Description Generator voltage potential transformers ratio If no VTs are used adjust this setpoint to 1 6 back to List of setpoints Mains VT Ratio Setpoint group Basic settings Rela...

Page 215: ...Frequency 3 page 383 6 back to List of setpoints Gear Teeth Setpoint group Basic settings Related FW 1 3 0 Range units FGen RPM 1 500 Default value FGen RPM Alternative config NO Step 1 Comm object 8252 Related applications AMF MRS Config level Advanced Setpoint visibility Always Description Number of teeth on the engine flywheel where the pick up is installed Set to zero if no pick up is used and...

Page 216: ...72 Nominal RPM 2 page 377 and Nominal RPM 3 page 382 6 back to List of setpoints Subgroup Controller settings Controller Mode Setpoint group Basic settings Related FW 1 3 0 Range units OFF MAN AUTO TEST Default value OFF Alternative config NO Step Comm object 8315 Related applications AMF MRS Config level Advanced Setpoint visibility Always Description This setpoint can be used for changing the Co...

Page 217: ...activation of LBI controller is switched into value selected via setpoint Power On Mode 6 back to List of setpoints Default Application Select Setpoint group Basic settings Related FW 1 3 0 Range units AMF MRS Default value AMF Alternative config NO Step Comm object 12157 Related applications AMF MRS Config level Advanced Setpoint visibility Always Description This setpoint defines the controller ...

Page 218: ...Controller always accept the GCB FEEDBACK PAGE 450 without of issuing any alarm When the Sd protection shuts down the engine the GCB stays closed The BOC protection does not open the GCB controller goes to cooling when the BOC protection is tripped GCB stays closed until opened externally IMPORTANT Gen set with closed GCB is not blocked against starting No Button GCB button and LBI GCB button are ...

Page 219: ...eset button is pressed This is a safety function that prevents the Gen set starting again automatically in specific cases when fault reset button is pressed 6 back to List of setpoints Backlight Timeout Setpoint group Basic settings Related FW 1 3 0 Range units Disabled 1 255 min Default value Disabled Alternative config NO Step 1 min Comm object 10121 Related applications AMF MRS Config level Adv...

Page 220: ... starts again from the beginning if a new alarm appears before previous Horn timeout has elapsed 6 back to List of setpoints Fail Safe Binary State Setpoint group Basic settings Related FW 1 3 0 Range units Default value Last valid state Alternative config NO Step Comm object 21215 Related applications AMF MRS Config level Standard Setpoint visibility Always Description This setpoint adjusts behav...

Page 221: ...s USB power present USB cable plagued the controller is able to turn off when there is no user interaction but wake up is not possible USB power has to be cut off USB cable un plugged 6 back to List of setpoints Run Hours Source Setpoint group Basic settings Related FW 1 3 0 Range units AUTO ECU INTERNAL Default value AUTO Alternative config NO Step Comm object 13345 Related applications AMF MRS C...

Page 222: ...to history 6 back to List of setpoints Mains Voltage Detection in MRS Setpoint group Protections Related FW 1 3 0 Range units Enabled Disabled Default value Enabled Alternative config NO Step Comm object 16070 Related applications MRS Config level Advanced Setpoint visibility Only in MRS application Description This setpoint enables disables Mains Voltage Detected page 535 alarm Enabled Normal beh...

Page 223: ...Line 1 Setpoint group Basic settings Related FW 1 3 0 Range units RPM PF Run Hours ATT AIN1 Default value PF Alternative config NO Step Comm object 13346 Related applications AMF MRS Config level Advanced Setpoint visibility Always Description This setpoint adjusts line 1 on Main screen 6 back to List of setpoints Main Screen Line 2 Setpoint group Basic settings Related FW 1 3 0 Range units RPM PF...

Page 224: ...ngs Subgroup Controller Address Controller Address Setpoint group Communication Settings Related FW 1 3 0 Range units 1 32 Default value 1 Alternative config NO Step 1 Comm object 24537 Related applications AMF MRS Config level Standard Setpoint visibility Always Description Controller identification number It is possible to set controller address different from the default value 1 so that more co...

Page 225: ...usted via setpoint Fuel Solenoid Lead page 235 The output is deactivated if Emergency Stop comes or Gen set is stopped and in pause between repeated starts Gas Output is activated together with binary output IGNITION PAGE 487 if RPM is over the 30 RPM fixed value Output is deactivated after stop command or in pause between repeated start 6 back to List of setpoints Cranking Attempts Setpoint group...

Page 226: ...scription Maximum time limit of cranking time 6 back to List of setpoints Cranking Fail Pause Setpoint group Engine settings Related FW 1 3 0 Range units 5 60 s DefaultFixed value 8 s Alternative config NO Step 1 s Comm object 8257 Related applications AMF MRS Config level Advanced Setpoint visibility Always Description Pause between Cranking Attempts page 225 PRESTART PAGE 496 output is active in...

Page 227: ...t to zero if you want to leave the output PRESTART PAGE 496 open Image 8 1 Prestart Time 6 back to List of setpoints Starting RPM Setpoint group Engine settings Related FW 1 3 0 Range units 5 50 Default value 25 Alternative config NO Step 1 of Nominal RPM page 216 Comm object 8254 Related applications AMF MRS Config level Advanced Setpoint visibility Always Description This setpoint defines the fi...

Page 228: ...e value value from CU analog Oil Pressure value from ECU analog Oil pressure and state of binary input Oil Pressure is not used for disengagement of starter and for engine running evaluation IMPORTANT Value from analog input has higher priority than value from ECU 6 back to List of setpoints Glow Plugs Time Setpoint group Engine settings Related FW 1 3 0 Range units 0 0 Prestart Time page 227 s De...

Page 229: ...ed Fixed Time Temp Based Default value Disabled Alternative config NO Step Comm object 15717 Related applications AMF MRS Config level Advanced Setpoint visibility Only when LBO CHOKE PAGE 471 is configured Description This setpoint defines choke function behavior Disabled Choke function is disabled and logical binary output CHOKE PAGE 471 is activated under no circumstances Fixed Time Choke time ...

Page 230: ...tpoint Choke Function page 229 Fixed Time Description Defines time logical binary output CHOKE PAGE 471 is activated for when fixed time is used When setpoint Choke Function page 229 is set to Temp Based value Choke Time value have no effect Note If setpoint Choke Lead page 234 is set to nonzero value total time the CHOKE output is activated still matches value set by Choke Time setpoint This mean...

Page 231: ...GE 471 is configured and setpoint Choke Function page 229 Temp Based Description This setpoint adjust the base temperature for Choke function When temperature will be higher than this setpoint Choke Time will be always 0 When temperature will be lower than this setpoint Choke Time will be calculated by curve adjusted via setpoint Choke Increment page 232 When setpoint Choke Function page 229 is se...

Page 232: ... output CHOKE PAGE 471 Calculated time depends on engine coolant temperature Setpoint adjust curve which is used for calculating actual Choke Time When setpoint Choke Function page 229 is set to Fixed Time value setpoint Choke Increment has no effect Note If setpoint Choke Lead page 234 is set to nonzero value total time the CHOKE output is activated still matches calculated value based on actual ...

Page 233: ...71 is configured Description This setpoint adjust threshold level for deactivation of CHOKE PAGE 471 binary output When generator voltage is higher than this level then logical binary output CHOKE is deactivated In multiphase system it is sufficient to deactivate CHOKE LBO when at least one voltage crosses this threshold In case setpoint Choke Voltage is set to Disabled value no voltage is taken i...

Page 234: ...int visibility Only when LBO CHOKE PAGE 471 is configured Description This setpoint adjust the lead of logical binary output CHOKE CHOKE PAGE 471 is activated before logical binary output STARTER PAGE 501 Note In case Choke Lead is longer than 8 s cranking fail pause Choke Lead will be limited to 8 s cranking fail pause time This limitation is applied only for cranking fail pause Choke Lead in Pre...

Page 235: ...int Image 8 2 Fuel Solenoid Lead Note LBO PRESTART PAGE 496 goes to logical zero when Fuel Solenoid Lead goes to logical one Note This setpoint is used only for diesel Fuel Solenoid page 225 6 back to List of setpoints Idle Time Setpoint group Engine settings Related FW 1 3 0 Range units 0 600 s Default value 12 s Alternative config NO Step 1 s Comm object 9097 Related applications AMF MRS Config ...

Page 236: ...This output can be used for switching the governor between idle and nominal speed Note When controller is in the MAN mode it is possible to finish the Idle Time count down by pushing the Start button Image 8 3 Idle Time 1 Image 8 4 Idle Time 2 6 back to List of setpoints ...

Page 237: ... Related applications AMF MRS Config level Standard Setpoint visibility Always Description When the Gen set has been started and the idle timer has elapsed the controller will wait for a period adjusted by this setpoint before closing GCB even if the generator voltage and frequency are already in limits Note When starting the engine setpoint should be set 300 s Image 8 5 Minimal Stabilization Time...

Page 238: ...applications AMF MRS Config level Advanced Setpoint visibility Always Description When the Gen set has been started and the idle timer has elapsed the generator voltage and frequency must get within limits within this period of time otherwise an appropriate shutdown alarm generator voltage and or frequency is issued Note When starting the engine setpoint should be set 300 s Image 8 6 Maximal Stabi...

Page 239: ...on gets unblocked after delay Run Only Block Delay 6 back to List of setpoints Subgroup Stopping Cooling Speed Setpoint group Engine settings Related FW 1 3 0 Range units Idle Nominal Default value Nominal Alternative config NO Step Comm object 10046 Related applications AMF MRS Config level Advanced Setpoint visibility Always Description Selects the function of the binary output IDLE NOMINAL PAGE...

Page 240: ...fore stop 6 back to List of setpoints Stop Time Setpoint group Engine settings Related FW 1 3 0 Range units 0 600 s Default value 60 s Alternative config NO Step 1 s Comm object 9815 Related applications AMF MRS Config level Advanced Setpoint visibility Always Description Under normal conditions the engine must certainly stop within this period after the FUEL SOLENOID PAGE 477 has been de energize...

Page 241: ...gine after cooling pump Binary output START BUTTON STATE PAGE 471 is active when the engine starts deactivates after timer set in this setpoint elapses timer starts counting down as soon as engine switches to stop phase 6 back to List of setpoints Subgroup D Function D Function Setpoint group Engine settings Related FW 1 3 0 Range units Enabled ChargeFail Disabled Default value Disabled Alternativ...

Page 242: ... fail detection ChargeFail The D terminal is used for charge fail detection only Disabled The D terminal is not used Image 8 9 D Function 1 Image 8 10 D Function 2 Note Delay of this function is adjusted via D Delay page 243 setpoint threshold of this function is adjusted via D Level setpoint 6 back to List of setpoints ...

Page 243: ...960 Related applications AMF MRS Config level Advanced Setpoint visibility Only if setpoint D Function page 241 is not set to Disabled value Description This setpoint adjusts delay for D Function page 241 This delay is used for Alarm Wrn Charging Alternator Fail page 537 For engine running condition disengagement of starter 6 back to List of setpoints D Alarm Type Setpoint group Engine settings Re...

Page 244: ...1 Comm object 11033 Related applications AMF MRS Config level Standard Setpoint visibility Always Description The rise up threshold for overspeed protection The time for which this level is accepted is defined as Starting Overspeed Time page 245 This period starts to be counted once the RPM exceeds the value Starting RPM page 227 The threshold Overspeed Sd page 244 starts to be valid once this per...

Page 245: ...ys Description Time when Starting Overspeed Sd page 244 level is used for overspeed protection This time starts countdown when starting RPM are reached 6 back to List of setpoints Starting Overspeed Protection Setpoint group Engine settings Related FW 1 3 0 Range units OverSpd Sd NextStartAt Default value OverSpd Sd Alternative config NO Step Comm object 15808 Related applications AMF MRS Config l...

Page 246: ...Description Threshold for underspeed protection Relative to the nominal speed 6 back to List of setpoints Oil Pressure Delay Setpoint group User Setpoints Related FW 1 3 0 Range units 0 0 3600 0 s Default value 3 0 s Alternative config NO Step 0 1 s Comm object 65535 Related applications AMF MRS Config level Standard Setpoint visibility Always Description Delay for Wrn Oil Pressure page 551 Sd Oil...

Page 247: ... FW 1 3 0 Range units 0 0 3600 0 s Default value 5 0 s Alternative config NO Step 0 1 s Comm object 65532 Related applications AMF MRS Config level Standard Setpoint visibility Always Description Delay for Wrn Coolant Temp page 536 BOC Coolant Temp page 565 user protection 6 back to List of setpoints Coolant Temp Wrn Setpoint group User Setpoints Related FW 1 3 0 Range units 16 120 C Default value...

Page 248: ...lated FW 1 3 0 Range units 0 0 3600 0 s Default value 0 0 s Alternative config NO Step 0 1 s Comm object 65529 Related applications AMF MRS Config level Standard Setpoint visibility Always Description Delay for Wrn Coolant Temp Low page 536 user protection 6 back to List of setpoints Coolant Temp Low Wrn Setpoint group User Setpoints Related FW 1 3 0 Range units 16 120 C Default value 5 C Alternat...

Page 249: ...nt group User Setpoints Related FW 1 3 0 Range units 0 100 Default value 20 Alternative config NO Step 1 Comm object 65526 Related applications AMF MRS Config level Standard Setpoint visibility Always Description Threshold for Wrn Fuel Level page 536 user protection 6 back to List of setpoints Fuel Level BOC Setpoint group User Setpoints Related FW 1 3 0 Range units 0 100 Default value 10 Alternat...

Page 250: ...nfig level Advanced Setpoint visibility All the time Description Threshold level for switching the binary output FUEL PUMP PAGE 477 on Image 8 13 Fuel Pump On IMPORTANT When binary input FUEL PUMP ON OFF PAGE 449 is configured then binary output FUEL PUMP PAGE 477 is control by this binary input Setpoints Fuel Pump On and Fuel Pump Off page 251 are not evaluated Note Value from analog input has hi...

Page 251: ... Advanced Setpoint visibility All the time Description Threshold level for switching the binary output FUEL PUMP PAGE 477 off Image 8 14 Fuel Pump Off IMPORTANT When binary input FUEL PUMP ON OFF PAGE 449 is configured then binary output FUEL PUMP PAGE 477 is control by this binary input Setpoints Fuel Pump On page 250 and Fuel Pump Off are not evaluated Note Value from analog input has higher pri...

Page 252: ...ed and the FUEL PUMP PAGE 477 will be turned off Alarm AL Fuel Transfer Failed page 536 will be displayed but this alarm becomes immediately inactive and it will be possible to delete this message by the Fault reset button If the fault is deleted the controller will initiate the transfer again 6 back to List of setpoints Subgroup Battery Protections Battery Undervoltage Setpoint group Engine setti...

Page 253: ...ry voltage 6 back to List of setpoints Battery Voltage Delay Setpoint group Engine settings Related FW 1 3 0 Range units 0 600 s DefaultFixed value 5 s Alternative config NO Step 1 s Comm object 8383 Related applications AMF MRS Config level Standard Setpoint visibility Always Description Delay for Battery Undervoltage page 252 and Battery Overvoltage page 253 protection IMPORTANT This is a fixed ...

Page 254: ...counter is reset to 0 Both counter value and input pulses counter are stored in the nonvolatile memory 6 back to List of setpoints Conversion Coefficient Pulse 2 Setpoint group Engine settings Related FW 1 3 0 Range units 0 1 000 Default value 1 Alternative config NO Step 1 Comm object 10995 Related applications AMF MRS Config level Advanced Setpoint visibility Only if LBI PULSE COUNTER 2 PAGE 456...

Page 255: ...ION ON PULSE PAGE 504 or VENTILATION OFF PULSE PAGE 504 at the moment when logical binary output VENTILATION PAGE 504 is activated or deactivated respectively 6 back to List of setpoints Subgroup ECU Settings ECU Speed Adjustment Setpoint group Engine settings Related FW 1 3 0 Range units 0 100 Default value 50 Alternative config NO Step 1 Comm object 9948 Related applications AMF MRS Config level...

Page 256: ...nance Timer 1 Interval Setpoint group Maintenance Timers Related FW 1 3 0 Range units 1 36 month Disabled Default value Disabled Alternative config NO Step 1 month Comm object 20583 Related applications AMF MRS Config level Standard Setpoint visibility Always Description Maintenance timer counts down all the time setting is done in months but actual Maintenance Timer 1 Interval page 413 value is d...

Page 257: ...ntenance Timer 2 Maintenance Timer 2 RunHours Setpoint group Maintenance Timers Related FW 1 3 0 Range units 0 9 999 h Disabled Default value Disabled Alternative config NO Step 1 h Comm object 13854 Related applications AMF MRS Config level Standard Setpoint visibility Always Description Maintenance timer counts down when engine is running If it reaches zero an alarm appears but the timer still c...

Page 258: ...en the maintenance function is disabled and counter does not count and the counter value disappears from controllers statistics Reset of the timer can be done by adjusting this setpoint again Setting of the setpoint does not change when the reset is done only the Maintenance Timer 2 Interval page 413 value changes to reflect reset of the maintenance timer 6 back to List of setpoints Maintenance Ti...

Page 259: ...3 Interval Setpoint group Maintenance Timers Related FW 1 3 0 Range units 1 36 month Disabled Default value Disabled Alternative config NO Step 1 month Comm object 20585 Related applications AMF MRS Config level Standard Setpoint visibility Always Description Maintenance timer counts down all the time setting is done in months but actual Maintenance Timer 3 Interval page 414 value is displayed and...

Page 260: ...l page 259 6 back to List of setpoints Group Generator settings Subgroup Overload Protection Overload BOC Setpoint group Generator settings Related FW 1 3 0 Range units Overload Wrn page 261 200 Default value 120 Alternative config NO Step 1 of Nominal Power page 206 Comm object 8280 Related applications AMF MRS Config level Standard Setpoint visibility Always Description Threshold level for overl...

Page 261: ... 5 0 s Alternative config NO Step 0 1 s Comm object 8281 Related applications AMF MRS Config level Standard Setpoint visibility Always Description Delay for protections Overload BOC page 260 and Overload Wrn page 261 6 back to List of setpoints Subgroup Current Protection Short Circuit BOC Setpoint group Generator settings Related FW 1 3 0 Range units 100 500 Default value 250 Alternative config N...

Page 262: ...e config NO Step 0 1 s Comm object 8283 Related applications AMF MRS Config level Standard Setpoint visibility Always Description IDMT curve shape selection IDMT is very inverse over current protection Reaction time is not constant but depends on over current level according to the following formula Note Reaction time is limited to 3600 s 60 minutes IDMT protection is not active for Reaction time ...

Page 263: ...e page 209 Description Threshold for generator current asymmetry unbalance Protection is BOC Breaker Open and Gen set Cooldown Note When there is no control of breakers the type of protection is Sd not BOC 6 back to List of setpoints Current Unbalance BOC Delay Setpoint group Generator settings Related FW 1 3 0 Range units 0 0 600 0 s Default value 5 0 s Alternative config NO Step 0 1 s Comm objec...

Page 264: ...e is used Note Phase to phase and phase to neutral voltages are used for this protection 6 back to List of setpoints Generator Overvoltage Wrn Setpoint group Generator settings Related FW 1 3 0 Range units Generator Undervoltage Wrn page 265 Generator Overvoltage Sd page 264 Default value 110 Alternative config NO Step 1 of Nominal Voltage Ph N page 211 or Nominal Voltage Ph Ph page 211 Comm objec...

Page 265: ...to phase and phase to neutral voltages are used for this protection 6 back to List of setpoints Generator Undervoltage BOC Setpoint group Generator settings Related FW 1 3 0 Range units 0 Generator Undervoltage Wrn page 265 Default value 70 Alternative config NO Step 1 of Nominal Voltage Ph N page 211 or Nominal Voltage Ph Ph page 211 Comm object 8293 Related applications AMF MRS Config level Stan...

Page 266: ...tage Ph Ph page 211 or Nominal Voltage Ph N page 211 Default value 10 Alternative config NO Step 1 Comm object 8288 Related applications AMF MRS Config level Advanced Setpoint visibility Conditioned by the setpoint Connection type page 209 Description Threshold for generator voltage unbalance alarm Note When there is no control of breakers the type of protection is Sd not BOC 6 back to List of set...

Page 267: ...ngs Related FW 1 3 0 Range units Generator Underfrequency Wrn page 267 Generator Overfrequency BOC page 267 Default value 110 0 Alternative config NO Step 0 1 of Nominal Frequency page 215 Comm object 9688 Related applications AMF MRS Config level Standard Setpoint visibility Always Description Threshold for generator phase L1 overfrequency 6 back to List of setpoints Generator Underfrequency Wrn ...

Page 268: ...L1 underfrequency Note When there is no control of breakers the type of protection is Sd not BOC 6 back to List of setpoints Generator Frequency Delay Setpoint group Generator settings Related FW 1 3 0 Range units 0 0 600 0 s Default value 3 0 s Alternative config NO Step 0 1 s Comm object 8297 Related applications AMF MRS Config level Standard Setpoint visibility Always Description Delay for Gene...

Page 269: ...ption Delay after the mains failure to the start command of the Gen set Image 8 16 Emergency Start Delay 6 back to List of setpoints Mains Return Delay Setpoint group Mains Settings Related FW 1 3 0 Range units 1 3 600 s Default value 20 s Alternative config NO Step 1 s Comm object 8302 Related applications AMF Config level Standard Setpoint visibility Conditioned by the setpoint Default Applicati...

Page 270: ...units 0 0 600 0 s Default value 1 0 s Alternative config NO Step 0 1 s Comm object 8303 Related applications AMF Config level Standard Setpoint visibility Conditioned by the setpoint Default Application Select page 217 Description Transition Delay between power sources Delay after GCB opening to MCB closing during the return procedure Delay after MCB opening to GCB closing if the setpoint MCB Open...

Page 271: ...must be set to sum of MCB opening Delay time Delay used in dual operation function This delay is used when load from first Gen set is transferred to second Gen set Delay starts to countdown when GCB of first Gen set is open When this delay countdown GCB of second Gen set is closed This delay is important for correct function of external interlock Image 8 18 Transfer Delay 2 6 back to List of setpo...

Page 272: ... 274 150 Default value 110 Alternative config NO Step 1 of Nominal Voltage Ph Ph page 211 Comm object 8305 Related applications AMF Config level Standard Setpoint visibility Conditioned by the setpoint Default Application Select page 217 Description Threshold for Mains overvoltage All three phases are checked Maximum out of three is used 6 back to List of setpoints ...

Page 273: ...272 Default value 105 Alternative config NO Step 1 Comm object 14132 Related applications AMF Config level Standard Setpoint visibility Conditioned by the setpoint Default Application Select page 217 Description Threshold defines the level of turning off Mains overvoltage protection Image 8 19 Mains Overvoltage Hys 6 back to List of setpoints ...

Page 274: ...0 Alternative config YES Step 1 of Nominal Voltage Ph Ph page 211 Comm object 8307 Related applications AMF Config level Standard Setpoint visibility Conditioned by the setpoint Default Application Select page 217 Description Threshold for Mains undervoltage All three phases are checked Minimum voltage out of three phases is used 6 back to List of setpoints ...

Page 275: ... 100 Default value 65 Alternative config NO Step 1 Comm object 14130 Related applications AMF Config level Standard Setpoint visibility Conditioned by the setpoint Default Application Select page 217 Description Threshold defines the level of turning off Mains undervoltage protection Image 8 20 Mains Undervoltage Hys 6 back to List of setpoints ...

Page 276: ...Default value 2 0 s Alternative config YES Step 0 1 s Comm object 8308 Related applications AMF Config level Standard Setpoint visibility Conditioned by the setpoint Default Application Select page 217 Description Delay for Mains Undervoltage page 274 protection 6 back to List of setpoints Mains Voltage Unbalance Setpoint group Mains Settings Related FW 1 3 0 Range units 1 150 of Nominal Voltage P...

Page 277: ...escription Delay for Mains Voltage Unbalance page 276 protection 6 back to List of setpoints Subgroup Mains Frequency Limits Mains Overfrequency Setpoint group Mains Settings Related FW 1 3 0 Range units Mains Underfrequency page 279 150 Default value 102 0 Alternative config NO Step 1 0 of Nominal Frequency page 215 Comm object 8310 Related applications AMF Config level Standard Setpoint visibili...

Page 278: ...7 Default value 102 0 Alternative config NO Step 0 1 Comm object 14134 Related applications AMF Config level Standard Setpoint visibility Conditioned by the setpoint Default Application Select page 217 Description Threshold defines the level of turning off Mains overfrequency protection Image 8 21 Mains Overfrequency Hys 6 back to List of setpoints ...

Page 279: ...Overfrequency page 277 Default value 98 0 Alternative config NO Step 1 0 of Nominal Frequency page 215 Comm object 8312 Related applications AMF Config level Standard Setpoint visibility Conditioned by the setpoint Default Application Select page 217 Description Threshold for Mains underfrequency 6 back to List of setpoints ...

Page 280: ...00 Default value 98 0 Alternative config NO Step 0 1 Comm object 14135 Related applications AMF Config level Standard Setpoint visibility Conditioned by the setpoint Default Application Select page 217 Description Threshold defines the level of turning off Mains underfrequency protection Image 8 22 Mains Underfrequency Hys 6 back to List of setpoints ...

Page 281: ... object 9590 Related applications AMF Config level Advanced Setpoint visibility Conditioned by the setpoint Default Application Select page 217 Description Setpoint adjust the behavior of closing MCB when the mains returns Manual Controller remains in AUT mode and the manual return to Mains is done via MCB button Manual Restore page 544 message is displayed in alarmlist to notify operator it will ...

Page 282: ...ult Application Select page 217 Description The setpoint influences the behavior of the output MCB CLOSE OPEN PAGE 490 Close On When the output MCB CLOSE OPEN PAGE 490 is active MCB should be closed Close Off When the output MCB CLOSE OPEN PAGE 490 is active MCB should be opened Image 8 23 MCB Logic 1 Image 8 24 MCB Logic 2 6 back to List of setpoints ...

Page 283: ...ening MCB in AUTO mode when there is mains fail Mains Fail The command to open the MCB is given immediately after mains fail condition is evaluated If the mains will return into parameters after MCB was opened and before GCB is closed timer MCB Close Delay page 270 is applied before MCB closing Gen Run MCB will be opened when engine will be running and it will be possible to transfer load from Mai...

Page 284: ... outputs are activated deactivated one by one in island operation All Loadshedding outputs are tripped once the Gen set comes into the island operation from NO LOAD operation MCB and GCB were opened Gen set started and GCB closed 6 back to List of setpoints Load Shedding Level Setpoint group Load Management Related FW 1 3 0 Range units Load Reconnection Level 200 of Nominal Power page 206 Default ...

Page 285: ...me the controller proceeds to the next Load shedding stage the next binary output Load Shedding Stage 1 2 is active 6 back to List of setpoints Subgroup Load Reconnection Settings Load Reconnection Level Setpoint group Load Management Related FW 1 3 0 Range units 0 Load Shedding Level page 284 Default value 20 Alternative config NO Step 1 Comm object 8890 Related applications AMF MRS Config level ...

Page 286: ...oints Auto Load Reconnection Setpoint group Load Management Related FW 1 3 0 Range units Disabled Enabled Default value Enabled Alternative config NO Step Comm object 9649 Related applications AMF MRS Config level Advanced Setpoint visibility Visible only if Load Shedding Active page 284 is enabled Description Switch between manual and automatic reconnection of shedded load Disabled Rising edge on...

Page 287: ...no dummy load will be activated when in parallel with mains 6 back to List of setpoints Dummy Load On Setpoint group Load Management Related FW 1 3 0 Range units 0 0 Dummy Load Off page 288 Default value 20 Alternative config YES Step 0 1 Comm object 11772 Related applications AMF MRS Config level Advanced Setpoint visibility If Dummy Load Active page 287 is not set to disabled Description This se...

Page 288: ...ig YES Step 0 1 Comm object 11773 Related applications AMF MRS Config level Advanced Setpoint visibility If Dummy Load Active page 287 is not set to disabled Description This setpoint determines power level which when exceeded will trigger Dummy Load Function to remove activate power bank stages by deactivating additional Dummy Load Level LBOs 6 back to List of setpoints Dummy Load Off Delay Setpo...

Page 289: ...MF MRS Config level Standard Setpoint visibility Always Description Real time clock adjustment Note RTC has backup battery 6 back to List of setpoints Date Setpoint group Scheduler Related FW 1 3 0 Range units DD MM YYYY Default value 1 1 2015 Alternative config NO Step Comm object 24553 Related applications AMF MRS Config level Standard Setpoint visibility Always Description Actual date adjustmen...

Page 290: ...ications AMF MRS Config level Standard Setpoint visibility Always Description Switches the mode of Daylight Saving Time DST AUTO Activation deactivation of the DST and changing of the RTC Time value accordingly is performed automatically by the controller The user always sees valid local time without any action from his side MANUAL Activation and deactivation of the DST is performed manually by th...

Page 291: ...st Sunday in April 03 00 local time last Sunday in October AUSTRALIA 02 00 local time 1 st Sunday in October 03 00 local time 1 st Sunday in April NEW ZEALAND 02 00 local time last Sunday in September 03 00 local time 1 st Sunday in April CHILE 00 00 local time 1 st Sunday in September 00 00 local time 1 st Sunday in April PARAGUAY 00 00 local time 1 st Sunday in October 00 00 local time 4 th Sund...

Page 292: ...ates timer whenever it is powered up even in period where timer should be already running Disable The Timer is disabled Manual On LBO Timer is active but the Timer itself is disabled Note This function serves for testing purposes No Func There is no any other function only binary output of timer is activated Mode OFF When this option is chosen then the binary output of timer is internally connecte...

Page 293: ...1 Repeated page 295 Timer 1 Repeat Day page 295 Timer 1 Day page 296 Timer 1 Repeated Day In Week page 296 Timer 1 Repeat Day In Month page 296 Timer 1 Repeat Week In Month page 297 Timer 1 Refresh Period page 298 Timer 1 Weekends page 299 6 back to List of setpoints Timer 1 First Occur Date Setpoint group Scheduler Related FW 1 3 0 Range units DD MM YYYY Default value 01 01 2000 Alternative confi...

Page 294: ...ated applications AMF MRS Config level Standard Setpoint visibility Conditioned by the setpoint Timer 1 Function page 292 Description Timer 1 Function page 292 duration time 6 back to List of setpoints Timer 1 Repetition Setpoint group Scheduler Related FW 1 3 0 Range units Off Once Repeated Default value Off Alternative config NO Step Comm object 0 Related applications AMF MRS Config level Standa...

Page 295: ... day every month or in chosen days of chosen week of month Short Period Timer 1 Function page 292 is repeated in adjusted period 6 back to List of setpoints Timer 1 Repeat Day Setpoint group Scheduler Related FW 1 3 0 Range units Repeated Day Repeated Day In Week Default value Repeated Day Alternative config NO Step Comm object 0 Related applications AMF MRS Config level Standard Setpoint visibili...

Page 296: ...day Thursday Friday Saturday Sunday Default value All OFF Alternative config NO Step Comm object 0 Related applications AMF MRS Config level Standard Setpoint visibility Conditioned by the setpoint Timer 1 Function page 292 Description Use this setpoint to select the day of week when timer will be activated Note More day can be selected Timer will be activated on the day which happened like the fi...

Page 297: ...Default value 1 week Alternative config NO Step 1 week Comm object 0 Related applications AMF MRS Config level Standard Setpoint visibility Conditioned by the setpoint Timer 1 Function page 292 Description This setpoint adjust the week of month in which the Timer 1 Function page 292 will be activated 6 back to List of setpoints ...

Page 298: ... have weekly repetition and you set this setpoint to 2 then every second week from first occurrence of Timer 1 Function page 292 the Timer 1 Function page 292 will be activated in selected days adjusted by Timer 1 Day page 296 Monthly Range units 1 12 month This setpoint adjust that every X month the timer will be activated Example If you have monthly repetition and you set this setpoint to 2 then...

Page 299: ...ge 292 on weekends Including Timer 1 Function page 292 counter is running on the weekends and Timer 1 Function page 292 can be active Skip Timer 1 Function page 292 counter is running on the weekends but Timer 1 Function page 292 isn t active Postpone Timer 1 Function page 292 counter isn t running on the weekends and Timer 1 Function page 292 isn t active If the activation of timer is counted on ...

Page 300: ...ivates timer whenever it is powered up even in period where timer should be already running Disable The Timer is disabled Manual On LBO Timer is active but the Timer itself is disabled Note This function serves for testing purposes No Func There is no any other function only binary output of timer is activated Mode OFF When this option is chosen then the binary output of timer is internally connec...

Page 301: ...2 Repeated page 303 Timer 2 Repeat Day page 303 Timer 2 Day page 304 Timer 2 Repeated Day In Week page 304 Timer 2 Repeat Day In Month page 304 Timer 2 Repeat Week In Month page 305 Timer 2 Refresh Period page 306 Timer 2 Weekends page 307 6 back to List of setpoints Timer 2 First Occur Date Setpoint group Scheduler Related FW 1 3 0 Range units DD MM YYYY Default value 01 01 2000 Alternative confi...

Page 302: ...ated applications AMF MRS Config level Standard Setpoint visibility Conditioned by the setpoint Timer 2 Function page 300 Description Timer 2 Function page 300 duration time 6 back to List of setpoints Timer 2 Repetition Setpoint group Scheduler Related FW 1 3 0 Range units Off Once Repeated Default value Off Alternative config NO Step Comm object 0 Related applications AMF MRS Config level Standa...

Page 303: ... day every month or in chosen days of chosen week of month Short Period Timer 2 Function page 300 is repeated in adjusted period 6 back to List of setpoints Timer 2 Repeat Day Setpoint group Scheduler Related FW 1 3 0 Range units Repeated Day Repeated Day In Week Default value Repeated Day Alternative config NO Step Comm object 0 Related applications AMF MRS Config level Standard Setpoint visibili...

Page 304: ...day Thursday Friday Saturday Sunday Default value All OFF Alternative config NO Step Comm object 0 Related applications AMF MRS Config level Standard Setpoint visibility Conditioned by the setpoint Timer 2 Function page 300 Description Use this setpoint to select the day of week when timer will be activated Note More day can be selected Timer will be activated on the day which happened like the fi...

Page 305: ...Default value 1 week Alternative config NO Step 1 week Comm object 0 Related applications AMF MRS Config level Standard Setpoint visibility Conditioned by the setpoint Timer 2 Function page 300 Description This setpoint adjust the week of month in which the Timer 2 Function page 300 will be activated 6 back to List of setpoints ...

Page 306: ... have weekly repetition and you set this setpoint to 2 then every second week from first occurrence of Timer 2 Function page 300 the Timer 2 Function page 300 will be activated in selected days adjusted by Timer 2 Day page 304 Monthly Range units 1 12 month This setpoint adjust that every X month the timer will be activated Example If you have monthly repetition and you set this setpoint to 2 then...

Page 307: ...ge 300 on weekends Including Timer 2 Function page 300 counter is running on the weekends and Timer 2 Function page 300 can be active Skip Timer 2 Function page 300 counter is running on the weekends but Timer 2 Function page 300 isn t active Postpone Timer 2 Function page 300 counter isn t running on the weekends and Timer 2 Function page 300 isn t active If the activation of timer is counted on ...

Page 308: ...ates timer whenever it is powered up even in period where timer should be already running Disable The Timer is disabled Manual On LBO Timer is active but the Timer itself is disabled Note This function serves for testing purposes No Func There is no any other function only binary output of timer is activated Mode OFF When this option is chosen then the binary output of timer is internally connecte...

Page 309: ...11 Timer 3 Repeat Day page 311 Timer 3 Day page 312 Timer 3 Repeated Day In Week page 312 Timer 3 Repeat Day In Month page 312 Timer 3 Repeat Week In Month page 313 Timer 3 Refresh Period page 314 Timer 3 Weekends page 315 6 back to List of setpoints Timer 3 First Occur Date Setpoint group Scheduler Related FW 1 3 0 Range units DD MM YYYY Default value 01 01 2000 Alternative config NO Step Comm ob...

Page 310: ...ated applications AMF MRS Config level Standard Setpoint visibility Conditioned by the setpoint Timer 3 Function page 308 Description Timer 3 Function page 308 duration time 6 back to List of setpoints Timer 3 Repetition Setpoint group Scheduler Related FW 1 3 0 Range units Off Once Repeated Default value Off Alternative config NO Step Comm object 0 Related applications AMF MRS Config level Standa...

Page 311: ... day every month or in chosen days of chosen week of month Short Period Timer 3 Function page 308 is repeated in adjusted period 6 back to List of setpoints Timer 3 Repeat Day Setpoint group Scheduler Related FW 1 3 0 Range units Repeated Day Repeated Day In Week Default value Repeated Day Alternative config NO Step Comm object 0 Related applications AMF MRS Config level Standard Setpoint visibili...

Page 312: ...day Thursday Friday Saturday Sunday Default value All OFF Alternative config NO Step Comm object 0 Related applications AMF MRS Config level Standard Setpoint visibility Conditioned by the setpoint Timer 3 Function page 308 Description Use this setpoint to select the day of week when timer will be activated Note More day can be selected Timer will be activated on the day which happened like the fi...

Page 313: ...Default value 1 week Alternative config NO Step 1 week Comm object 0 Related applications AMF MRS Config level Standard Setpoint visibility Conditioned by the setpoint Timer 3 Function page 308 Description This setpoint adjust the week of month in which the Timer 3 Function page 308 will be activated 6 back to List of setpoints ...

Page 314: ... have weekly repetition and you set this setpoint to 3 then every second week from first occurrence of Timer 3 Function page 308 the Timer 3 Function page 308 will be activated in selected days adjusted by Timer 3 Day page 312 Monthly Range units 1 12 month This setpoint adjust that every X month the timer will be activated Example If you have monthly repetition and you set this setpoint to 3 then...

Page 315: ...ge 308 on weekends Including Timer 3 Function page 308 counter is running on the weekends and Timer 3 Function page 308 can be active Skip Timer 3 Function page 308 counter is running on the weekends but Timer 3 Function page 308 isn t active Postpone Timer 3 Function page 308 counter isn t running on the weekends and Timer 3 Function page 308 isn t active If the activation of timer is counted on ...

Page 316: ...ates timer whenever it is powered up even in period where timer should be already running Disable The Timer is disabled Manual On LBO Timer is active but the Timer itself is disabled Note This function serves for testing purposes No Func There is no any other function only binary output of timer is activated Mode OFF When this option is chosen then the binary output of timer is internally connecte...

Page 317: ...4 Repeated page 319 Timer 4 Repeat Day page 319 Timer 4 Day page 320 Timer 4 Repeated Day In Week page 320 Timer 4 Repeat Day In Month page 320 Timer 4 Repeat Week In Month page 321 Timer 4 Refresh Period page 322 Timer 4 Weekends page 323 6 back to List of setpoints Timer 4 First Occur Date Setpoint group Scheduler Related FW 1 3 0 Range units DD MM YYYY Default value 01 01 2000 Alternative confi...

Page 318: ...ated applications AMF MRS Config level Standard Setpoint visibility Conditioned by the setpoint Timer 4 Function page 316 Description Timer 4 Function page 316 duration time 6 back to List of setpoints Timer 4 Repetition Setpoint group Scheduler Related FW 1 3 0 Range units Off Once Repeated Default value Off Alternative config NO Step Comm object 0 Related applications AMF MRS Config level Standa...

Page 319: ... day every month or in chosen days of chosen week of month Short Period Timer 4 Function page 316 is repeated in adjusted period 6 back to List of setpoints Timer 4 Repeat Day Setpoint group Scheduler Related FW 1 3 0 Range units Repeated Day Repeated Day In Week Default value Repeated Day Alternative config NO Step Comm object 0 Related applications AMF MRS Config level Standard Setpoint visibili...

Page 320: ...day Thursday Friday Saturday Sunday Default value All OFF Alternative config NO Step Comm object 0 Related applications AMF MRS Config level Standard Setpoint visibility Conditioned by the setpoint Timer 4 Function page 316 Description Use this setpoint to select the day of week when timer will be activated Note More day can be selected Timer will be activated on the day which happened like the fi...

Page 321: ...Default value 1 week Alternative config NO Step 1 week Comm object 0 Related applications AMF MRS Config level Standard Setpoint visibility Conditioned by the setpoint Timer 4 Function page 316 Description This setpoint adjust the week of month in which the Timer 4 Function page 316 will be activated 6 back to List of setpoints ...

Page 322: ... have weekly repetition and you set this setpoint to 4 then every second week from first occurrence of Timer 4 Function page 316 the Timer 4 Function page 316 will be activated in selected days adjusted by Timer 4 Day page 320 Monthly Range units 1 12 month This setpoint adjust that every X month the timer will be activated Example If you have monthly repetition and you set this setpoint to 4 then...

Page 323: ...ge 316 on weekends Including Timer 4 Function page 316 counter is running on the weekends and Timer 4 Function page 316 can be active Skip Timer 4 Function page 316 counter is running on the weekends but Timer 4 Function page 316 isn t active Postpone Timer 4 Function page 316 counter isn t running on the weekends and Timer 4 Function page 316 isn t active If the activation of timer is counted on ...

Page 324: ...is active 6 back to List of setpoints Subgroup Position Home Latitude Setpoint group Geo Fencing Related FW 1 3 0 Range units 90 0000 90 0000 Default value 0 0000 Alternative config NO Step 0 0001 Comm object 14606 Related applications AMF MRS Config level Standard Setpoint visibility Only if relevant module is installed Description This setpoint adjust latitude of home position Home is position w...

Page 325: ...f home position Home is position where gen set should runs Positions on east hemisphere have positive value position on west hemisphere have negative value Note This value with Home Latitude page 324 are used for counting Fence 1 Radius page 327 and Fence 2 Radius page 329 Note This value can be also obtained automatically via logical binary input GEO HOME POSITION PAGE 450 In case of activation o...

Page 326: ...n of gen set is only measured and displayed on the LCD screen but not used for protection History record is made if position is out of Fence 1 Radius page 327 Wrn Position of Gen set is used for warning protection only Protection is activated when position of the Gen set is out of Fence 1 Radius page 327 Sd Position of Gen set is used for shutdown protection Protection is activated when position o...

Page 327: ...his area Fence 1 Protection page 326 is activated after Fence 1 Delay page 327 Note The center of this circle area is defined by Home position setpoints Home Longitude page 325 and Home Latitude page 324 6 back to List of setpoints Fence 1 Delay Setpoint group Geo Fencing Related FW 1 3 0 Range units 0 3600 s Default value 0 s Alternative config NO Step 1 s Comm object 11682 Related applications A...

Page 328: ...n of gen set is only measured and displayed on the LCD screen but not used for protection History record is made if position is out of Fence 2 Radius page 329 Wrn Position of Gen set is used for warning protection only Protection is activated when position of the Gen set is out of Fence 2 Radius page 329 Sd Position of Gen set is used for shutdown protection Protection is activated when position o...

Page 329: ...position setpoints Home Longitude page 325 and Home Latitude page 324 6 back to List of setpoints Fence 2 Delay Setpoint group Geo Fencing Related FW 1 3 0 Range units 0 3600 s Default value 0 s Alternative config NO Step 1 s Comm object 14609 Related applications AMF MRS Config level Standard Setpoint visibility Only if relevant module is installed Description Delay for Fence 2 Protection page 32...

Page 330: ...lot B 6 back to List of setpoints Group CM RS232 485 Subgroup COM1 Setting COM1 Mode Setpoint group CM RS232 485 Related FW 1 3 0 Range units Direct MODBUS DualSlave Dual Master Default value Direct Alternative config NO Step Comm object 24522 Related applications AMF MRS Config level Standard Setpoint visibility Only if relevant module is installed Description Communication protocol switch for th...

Page 331: ...communication speed of controller part of line can be adjusted here Speed of second part of line has to be adjusted to the same value 6 back to List of setpoints COM1 MODBUS Communication Speed Setpoint group CM RS232 485 Related FW 1 3 0 Range units 9600 19200 38400 57600 115200 bps Default value 9600 bps Alternative config NO Step Comm object 24477 Related applications AMF MRS Config level Stand...

Page 332: ... Dual operation protocol slave function DualMaster Dual operation protocol master function 6 back to List of setpoints COM2 Communication Speed Setpoint group CM RS232 485 Related FW 1 3 0 Range units 9600 19200 38400 57600 115200 bps Default value 57600 bps Alternative config NO Step Comm object 24340 Related applications AMF MRS Config level Standard Setpoint visibility Only if relevant module i...

Page 333: ... COM2 Mode page 332 Description If the MODBUS mode is selected on COM2 channel the MODBUS communication speed can be adjusted here 6 back to List of setpoints Group CM 4G GPS Subgroup Cellular Interface Internet Connection Setpoint group CM 4G GPS Related FW 1 3 0 Range units Enabled Disabled Default value Enabled Alternative config NO Step Comm object 24315 Related applications AMF MRS Config lev...

Page 334: ... setpoint adjusts preferred connection type of CM2 4G GPS module 6 back to List of setpoints Access Point Name Setpoint group CM 4G GPS Related FW 1 3 0 Range units 0 31 characters Default value internet Alternative config NO Step Comm object 24363 Related applications AMF MRS Config level Standard Setpoint visibility Only if relevant module is installed conditioned by the setpoint Internet Connec...

Page 335: ... with function that periodically checks the data connection over the cellular network is working This function is based on periodical sending of ICMP messages known as ping to reliable servers in the internet and checking of their responses If there is not any response received from any of the servers at least one setpoint Connection Check IP1 IP2 IP3 is filled with IP address for certain time per...

Page 336: ... with function that periodically checks the data connection over the cellular network is working This function is based on periodical sending of ICMP messages known as ping to reliable servers in the internet and checking of their responses If there is not any response received from any of the servers at least one setpoint Connection Check IP1 IP2 IP3 is filled with IP address for certain time per...

Page 337: ... with function that periodically checks the data connection over the cellular network is working This function is based on periodical sending of ICMP messages known as ping to reliable servers in the internet and checking of their responses If there is not any response received from any of the servers at least one setpoint Connection Check IP1 IP2 IP3 is filled with IP address for certain time per...

Page 338: ...ve e g internet access policy related issue if local DNS server addresses automatically obtained from a DHCP server do not work 6 back to List of setpoints DNS IP Address 1 Setpoint group CM 4G GPS Related FW 1 3 0 Range units Valid IP address Default value 8 8 8 8 Alternative config NO Step Comm object 24314 Related applications AMF MRS Config level Standard Setpoint visibility Only if relevant m...

Page 339: ...ses and server names into correct IP addresses If DNS Mode page 338 is AUTOMATIC this setpoint is inactive The DNS server IP address is assigned by the DHCP server 6 back to List of setpoints IP Firewall Setpoint group CM 4G GPS Related FW 1 3 0 Range units ENABLED DISABLED Default value DISABLED Alternative config NO Step Comm object 23959 Related applications AMF MRS Config level Standard Setpoi...

Page 340: ... AirGate service Internet enabled SIM card must be used The AirGate server address is adjusted by the setpoint AirGate Address page 359 IMPORTANT When this setpoint is changed the controller has to be restarted to apply changes 6 back to List of setpoints AirGate Address Setpoint group CM 4G GPS CM Ethernet Related FW 1 3 0 Range units Default value global airgate link Alternative config NO Step C...

Page 341: ...se port 54440 for standard ComAp AirGate service 6 back to List of setpoints Subgroup ComAp Client Settings Direct Connection Setpoint group CM 4G GPS Related FW 1 3 0 Range units Disabled Enabled Default value Enabled Alternative config NO Step Comm object 23961 Related applications AMF MRS Config level Standard Setpoint visibility Only if relevant module is installed Description Use this to enab...

Page 342: ...ction if Direct Connection is ENABLED 6 back to List of setpoints ComAp Client Inactivity Timeout Setpoint group CM Ethernet CM 4G GPS Related FW 1 3 0 Range units 0 600 s Default value 60 s Alternative config NO Step 1 s Comm object 24098 Related applications AMF MRS Config level Standard Setpoint visibility Only if relevant module is installed Description Connection TCP socket is closed by contr...

Page 343: ...e is connected to AirGate the AirGate SMTP server at global airgate link may be used Ports 25 and 9925 are supported After controller connects to AirGate for the first time or with new public IP address it may not be able to send emails for first 5 10 minutes 6 back to List of setpoints SMTP Sender Address Setpoint group CM 4G GPS Related FW 1 3 0 Range units 0 31 characters Default value Alternat...

Page 344: ... SMTP server Leave the setpoint blank if the SMTP server does not require authentication 6 back to List of setpoints SMTP User Password Setpoint group CM 4G GPS Related FW 1 3 0 Range units 0 15 characters Default value Alternative config NO Step Comm object 24312 Related applications AMF MRS Config level Standard Setpoint visibility Only if relevant module is installed Description Use this setpoi...

Page 345: ...yption is used STARTTLS Communication is started without encryption and then is switched to TLS encryption TLS Communication runs in TLS encryption 6 back to List of setpoints Email Address 1 Setpoint group CM 4G GPS CM Ethernet Related FW 1 3 0 Range units 0 63 characters Default value Alternative config NO Step Comm object 24298 Related applications AMF MRS Config level Standard Setpoint visibil...

Page 346: ... mails shall be sent Leave this setpoint blank if alarm and event email should not be send 6 back to List of setpoints Email Address 3 Setpoint group CM 4G GPS CM Ethernet Related FW 1 3 0 Range units 0 63 characters Default value Alternative config NO Step Comm object 24145 Related applications AMF MRS Config level Standard Setpoint visibility Only if relevant module is installed Description Ente...

Page 347: ...mails shall be sent Leave this setpoint blank if alarm and event email should not be send 6 back to List of setpoints Subgroup Message Settings E mail SMS Language Setpoint group CM 4G GPS CM Ethernet Related FW 1 3 0 Range units Depends on CU languages Default value English Alternative config NO Step Comm object 24299 Related applications AMF MRS Config level Standard Setpoint visibility Only if ...

Page 348: ...s or disables Event Messages This setpoint is common for CM3 Ethernet and CM2 4G GPS modules 6 back to List of setpoints Wrn Message Setpoint group CM 4G GPS CM Ethernet Related FW 1 3 0 Range units ON OFF Default value ON Alternative config NO Step Comm object 8482 Related applications AMF MRS Config level Standard Setpoint visibility Only if relevant module is installed Description This setpoint...

Page 349: ...les or disables BOC Messages This setpoint is common for CM3 Ethernet and CM2 4G GPS modules 6 back to List of setpoints Sd Message Setpoint group CM 4G GPS CM Ethernet Related FW 1 3 0 Range units ON OFF Default value ON Alternative config NO Step Comm object 8484 Related applications AMF MRS Config level Standard Setpoint visibility Only if relevant module is installed Description This setpoint ...

Page 350: ...followed by the country prefix IMPORTANT Telephone number has to be entered without spaces 6 back to List of setpoints Telephone Number 2 Setpoint group CM 4G GPS Related FW 1 3 0 Range units 0 31 characters Default value Alternative config NO Step Comm object 24295 Related applications AMF MRS Config level Standard Setpoint visibility Only if relevant module is installed Description Enter in this...

Page 351: ...followed by the country prefix IMPORTANT Telephone number has to be entered without spaces 6 back to List of setpoints Telephone Number 4 Setpoint group CM 4G GPS Related FW 1 3 0 Range units 0 31 characters Default value Alternative config NO Step Comm object 24142 Related applications AMF MRS Config level Standard Setpoint visibility Only if relevant module is installed Description Enter in this...

Page 352: ...ynchronization NTP Clock Sync Setpoint group CM 4G GPS Related FW 1 3 0 Range units DISABLED ENABLED Default value DISABLED Alternative config NO Step Comm object 23964 Related applications AMF MRS Config level Standard Setpoint visibility Only if relevant module is installed Description This setpoint is used to enable disable controller time synchronization with exact time from an NTP server 6 ba...

Page 353: ...ack to List of setpoints Time Zone Setpoint group CM 4G GPS CM Ethernet Related FW 1 3 0 Range units GMT 12 00 GMT 13 00 hours Default value GMT 1 00 hour Alternative config NO Step Comm object 24366 Related applications AMF MRS Config level Standard Setpoint visibility Only if relevant module is installed Description This setpoint is used to select the time zone where the controller is located Se...

Page 354: ... setpoints IP Addr NetMask GateIP DNS IP Address This method should be used for a classic Ethernet or internet connection When this type of connection opens the controller is specified by its IP address This means that it would be inconvenient if the IP address were not fixed static AUTOMATIC The Ethernet connection setting is obtained automatically from the DHCP server The obtained settings are t...

Page 355: ...the DHCP server If IP Address Mode page 354 is DISABLED Ethernet terminal is disabled Note Only valid IP address can be inserted 6 back to List of setpoints Subnet Mask Setpoint group CM Ethernet Related FW 1 3 0 Range units Valid IP address Default value 255 255 255 0 Alternative config NO Step Comm object 23949 Related applications AMF MRS Config level Standard Setpoint visibility Only if releva...

Page 356: ...354 is DISABLED Ethernet terminal is disabled A gateway is a device which connects the respective segment with the other segments and or Internet 6 back to List of setpoints DNS Mode Setpoint group CM Ethernet Related FW 1 3 0 Range units Automatic Manual Default value Automatic Alternative config NO Step Comm object 23921 Related applications AMF MRS Config level Standard Setpoint visibility Only...

Page 357: ...d by the DHCP server If IP Address Mode page 354 is DISABLED Ethernet terminal is disabled 6 back to List of setpoints DNS IP Address 2 Setpoint group CM Ethernet Related FW 1 3 0 Range units Valid IP address Default value 8 8 8 8 Alternative config NO Step Comm object 23946 Related applications AMF MRS Config level Standard Setpoint visibility Only if relevant module is installed Description The ...

Page 358: ...ion Setpoint group CM Ethernet Related FW 1 3 0 Range units DISABLED ENABLED Default value ENABLED Alternative config NO Step Comm object 23935 Related applications AMF MRS Config level Standard Setpoint visibility Only if relevant module is installed Description This setpoint selects the AirGate connection mode DISABLED This is a standard mode in which the controller listens to the incoming traff...

Page 359: ...s used for entering the domain name or IP address of the AirGate server Use the free AirGate server provided by ComAp at global airgate link 6 back to List of setpoints AirGate Port Setpoint group CM Ethernet Related FW 1 3 0 Range units 1 65535 Default value 23 Alternative config NO Step 1 Comm object 23919 Related applications AMF MRS Config level Standard Setpoint visibility Only if relevant mo...

Page 360: ...on of a ComAp client e g InteliConfig to the IP address of the controller Note For Direct connection the controller IP address must be reachable from the client IP address 6 back to List of setpoints Direct Connection Port Setpoint group CM Ethernet Related FW 1 3 0 Range units 1 65535 Default value 23 Alternative config NO Step Comm object 23918 Related applications AMF MRS Config level Standard ...

Page 361: ...tpoint group CM Ethernet Related FW 1 3 0 Range units DISABLED ENABLED Default value Disabled Alternative config NO Step Comm object 23937 Related applications AMF MRS Config level Standard Setpoint visibility Only if relevant module is installed Description Enable or disable Modbus communication via ethernet interface 6 back to List of setpoints MODBUS Client Inactivity Timeout Setpoint group CM ...

Page 362: ...f v2Inform Default value v1Trap Alternative config NO Step Comm object 23922 Related applications AMF MRS Config level Standard Setpoint visibility Only if relevant module is installed Description This setpoint adjusts type of SNMP traps 6 back to List of setpoints SNMP Traps IP Address 1 Setpoint group CM Ethernet Related FW 1 3 0 Range units Valid IP address Default value DISABLED Alternative co...

Page 363: ...ts 0 31 characters Default value public Alternative config NO Step Comm object 23941 Related applications AMF MRS Config level Standard Setpoint visibility Only if relevant module is installed conditioned by the setpoint SNMP Agent page 362 Description SNMP Community String only for reading 6 back to List of setpoints SNMP WR Community String Setpoint group CM Ethernet Related FW 1 3 0 Range units...

Page 364: ...e is connected to AirGate the AirGate SMTP server at global airgate link may be used Ports 25 and 9925 are supported After controller connects to AirGate for the first time or with new public IP address it may not be able to send emails for first 5 10 minutes 6 back to List of setpoints SMTP Sender Address Setpoint group CM Ethernet Related FW 1 3 0 Range units 0 31 characters Default value Altern...

Page 365: ...SMTP server Leave the setpoint blank if the SMTP server does not require authentication 6 back to List of setpoints SMTP User Password Setpoint group CM Ethernet Related FW 1 3 0 Range units 0 15 characters Default value Alternative config NO Step Comm object 23945 Related applications AMF MRS Config level Standard Setpoint visibility Only if relevant module is installed Description Use this setpo...

Page 366: ...ryption is used STARTTLS Communication is started without encryption and then is switched to TLS encryption TLS Communication runs in TLS encryption 6 back to List of setpoints Email Address 1 Setpoint group CM 4G GPS CM Ethernet Related FW 1 3 0 Range units 0 63 characters Default value Alternative config NO Step Comm object 24298 Related applications AMF MRS Config level Standard Setpoint visibi...

Page 367: ... mails shall be sent Leave this setpoint blank if alarm and event email should not be send 6 back to List of setpoints Email Address 3 Setpoint group CM 4G GPS CM Ethernet Related FW 1 3 0 Range units 0 63 characters Default value Alternative config NO Step Comm object 24145 Related applications AMF MRS Config level Standard Setpoint visibility Only if relevant module is installed Description Ente...

Page 368: ... alarm and event e mails shall be sent Leave this setpoint blank if alarm and event email should not be send 6 back to List of setpoints Subgroup Messages Settings BOC Message Setpoint group CM 4G GPS CM Ethernet Related FW 1 3 0 Range units ON OFF Default value ON Alternative config NO Step Comm object 10566 Related applications AMF MRS Config level Standard Setpoint visibility Only if relevant m...

Page 369: ...point to set the language of SMS and e mail This setpoint is common for CM3 Ethernet and CM2 4G GPS modules 6 back to List of setpoints Event Message Setpoint group CM 4G GPS CM Ethernet Related FW 1 3 0 Range units ON OFF Default value ON Alternative config NO Step Comm object 10926 Related applications AMF MRS Config level Standard Setpoint visibility Only if relevant module is installed Descrip...

Page 370: ...s or disables Sd Message This setpoint is common for CM3 Ethernet and CM2 4G GPS modules 6 back to List of setpoints Wrn Message Setpoint group CM 4G GPS CM Ethernet Related FW 1 3 0 Range units ON OFF Default value ON Alternative config NO Step Comm object 8482 Related applications AMF MRS Config level Standard Setpoint visibility Only if relevant module is installed Description This setpoint ena...

Page 371: ...ity Only if relevant module is installed Description This setpoint is used to enable disable controller time synchronization with exact time from an NTP server 6 back to List of setpoints NTP Server Setpoint group CM Ethernet Related FW 1 3 0 Range units Default value pool ntp org Alternative config NO Step Comm object 23933 Related applications AMF MRS Config level Standard Setpoint visibility On...

Page 372: ...sk bar if you are not sure about your time zone Note If the time zone is not selected properly the active e mails may contain incorrect information about sending time which may result in confusion when the respective problem actually occurred 6 back to List of setpoints Group Alternate Config Subgroup Configuration 1 Nominal RPM 1 Setpoint group Alternate Config Related FW 1 3 0 Range units 100 40...

Page 373: ...onfig YES Step 1 V Comm object 12052 Related applications AMF MRS Config level Standard Setpoint visibility Conditioned by the setpoint Connection type page 209 Description Nominal system voltage phase to neutral Note This value is used when any other alternate configuration is not active 6 back to List of setpoints Nominal Voltage Ph Ph 1 Setpoint group Alternate Config Related FW 1 3 0 Range uni...

Page 374: ...o List of setpoints Connection Type 1 Setpoint group Alternate Config Related FW 1 3 0 Range units Mono Phase SplPhL1L2 SplPhL1L3 3Ph3Wire 3Ph4Wire High Leg D Autodetect Default value 3Ph4Wire Alternative config YES Step Comm object 12058 Related applications AMF MRS Config level Standard Setpoint visibility Always Description Connection type Mono Phase Single phase voltage measurement L1 N 1x CT ...

Page 375: ...urrent Transformer High Leg D High Leg Delta connection Three phase voltage measurement L1 L2 L3 3x CT Current Transformer Autodetect High Leg Delta L1 100 V L1 140 V L2 140 V L3 100 V L3 140 V 3Ph Low Y L1 160 V L2 160 V L3 160 V 3Ph High Y L1 160 V L2 160 V L3 160 V SplPhL1L3 L1 100 V L2 20 V L3 100 V SplPhL1L2 L1 100 V L2 100 V L3 20 V Mono Phase L1 100 V L2 20 V L3 20 V Voltage Autodetect shut...

Page 376: ...figuration is not active 6 back to List of setpoints Nominal Power 1 Setpoint group Alternate Config Related FW 1 3 0 Range units 1 5 000 kW Default value 200 kW Alternative config YES Step 1 kW Comm object 12046 Related applications AMF MRS Config level Standard Setpoint visibility Always Description Nominal power of the Gen set Generator Overload BOC page 260 protection is based on this setpoint...

Page 377: ...point is used when setpoint Connection type page 209 is adjusted to Autodetect and Autodetect detects connection type as Monophase or SplitphaseL1L2 or SplitphaseL1L3 Note This value is used when any other alternate configuration is not active 6 back to List of setpoints Subgroup Configuration 2 Nominal RPM 2 Setpoint group Alternate Config Related FW 1 3 0 Range units 100 4000 RPM Default value 1...

Page 378: ...fig YES Step 1 V Comm object 12053 Related applications AMF MRS Config level Standard Setpoint visibility Conditioned by the setpoint Connection type 2 page 379 Description Nominal system voltage phase to neutral Note This value is used when binary input ALTERNATE CONFIG 2 PAGE 439 is active 6 back to List of setpoints Nominal Voltage Ph Ph 2 Setpoint group Alternate Config Related FW 1 3 0 Range ...

Page 379: ...to List of setpoints Connection type 2 Setpoint group Alternate Config Related FW 1 3 0 Range units Mono Phase SplPhL1L2 SplPhL1L3 3Ph3Wire 3Ph4Wire High Leg D Autodetect Default value 3Ph4Wire Alternative config YES Step Comm object 12059 Related applications AMF MRS Config level Standard Setpoint visibility Always Description Connection type Mono Phase Single phase voltage measurement L1 N 1x CT...

Page 380: ...rent Transformer High Leg D High Leg Delta connection Three phase voltage measurement L1 L2 L3 3x CT Current Transformer Autodetect High Leg Delta L1 100 V L1 140 V L2 140 V L3 100 V L3 140 V 3Ph Low Y L1 160 V L2 160 V L3 160 V 3Ph High Y L1 160 V L2 160 V L3 160 V SplPhL1L3 L1 100 V L2 20 V L3 100 V SplPhL1L2 L1 100 V L2 100 V L3 20 V Mono Phase L1 100 V L2 20 V L3 20 V Voltage Autodetect shutdo...

Page 381: ...IG 2 PAGE 439 is active 6 back to List of setpoints Nominal Power 2 Setpoint group Alternate Config Related FW 1 3 0 Range units 1 5 000 kW Default value 200 kW Alternative config YES Step 1 kW Comm object 12047 Related applications AMF MRS Config level Standard Setpoint visibility Always Description Nominal power of the Gen set Generator Overload BOC page 260 protection is based on this setpoint ...

Page 382: ...int is used when setpoint Connection type 2 page 379 is adjusted to Autodetect and Autodetect detects connection type as Monophase or SplitphaseL1L2 or SplitphaseL1L3 Note This value is used when binary input ALTERNATE CONFIG 2 PAGE 439 is active 6 back to List of setpoints Subgroup Configuration 3 Nominal RPM 3 Setpoint group Alternate Config Related FW 1 3 0 Range units 100 4 000 RPM Default val...

Page 383: ...fig YES Step 1 V Comm object 12054 Related applications AMF MRS Config level Standard Setpoint visibility Conditioned by the setpoint Connection type 3 page 384 Description Nominal system voltage phase to neutral Note This value is used when binary input ALTERNATE CONFIG 3 PAGE 439 is active 6 back to List of setpoints Nominal Voltage Ph Ph 3 Setpoint group Alternate Config Related FW 1 3 0 Range ...

Page 384: ... to List of setpoints Connection type 3 Setpoint group Alternate Config Related FW 1 3 0 Range units Mono Phase SplPhL1L2 SplPhL1L3 3Ph3Wire 3Ph4Wire High Leg D Autodetect Default value 3Ph4Wire Alternative config YES Step Comm object 12060 Related applications AMF MRS Config level Standard Setpoint visibility Always Description Connection type Mono Phase Single phase voltage measurement L1 N 1x C...

Page 385: ...rent Transformer High Leg D High Leg Delta connection Three phase voltage measurement L1 L2 L3 3x CT Current Transformer Autodetect High Leg Delta L1 100 V L1 140 V L2 140 V L3 100 V L3 140 V 3Ph Low Y L1 160 V L2 160 V L3 160 V 3Ph High Y L1 160 V L2 160 V L3 160 V SplPhL1L3 L1 100 V L2 20 V L3 100 V SplPhL1L2 L1 100 V L2 100 V L3 20 V Mono Phase L1 100 V L2 20 V L3 20 V Voltage Autodetect shutdo...

Page 386: ...IG 3 PAGE 439 is active 6 back to List of setpoints Nominal Power 3 Setpoint group Alternate Config Related FW 1 3 0 Range units 1 5 000 kW Default value 200 kW Alternative config YES Step 1 kW Comm object 12048 Related applications AMF MRS Config level Standard Setpoint visibility Always Description Nominal power of the Gen set Generator Overload BOC page 260 protection is based on this setpoint ...

Page 387: ...8 1 3 Values What values are Values or quantities are analog or binary data objects measured or computed by the controller that are intended for reading from the controller screen PC MODBUS etc Values are organized into groups according to their meaning For a full list of values go to the chapter List of values page 388 Invalid flag If valid data is not available for a particular value the invalid...

Page 388: ...inal Voltage 402 Generator Power Factor 402 Group Load 403 Load P 403 Load P L1 403 Load P L2 403 Load P L3 403 Load Q 403 Load Q L1 404 Load Q L2 404 Load Q L3 404 Load S 404 Load S L1 404 Load S L2 405 Load S L3 405 Load Power Factor 405 Load Character 405 Load Power Factor L1 405 Load Character L1 406 Load Power Factor L2 406 Load Character L2 406 Load Power Factor L3 406 Load Character L3 407 ...

Page 389: ...s 1 422 Group CM 4G GPS 422 Signal Strength 422 Network Status 422 Last Email Result 423 Network Name 424 Network Mode 424 GPS Status 424 Latitude 424 Longitude 425 Active Satellites 425 Speed 425 HomePosDist 425 AirGate Status 426 AirGate ID 426 AirGate Servicing Node 426 Current IP Address 427 Primary DNS 427 Secondary DNS 427 Modem Status 427 Group CM Ethernet 428 ETH Interface Status 428 Curre...

Page 390: ...ulated from setpoint Nominal Frequency page 215 If is Nominal Frequency page 215 in range from 45 Hz to 54 Hz is considered as 50 Hz application The value is set to 0 If is Nominal Frequency page 215 in range from 55 Hz to 65 Hz is considered as 60 Hz application The value is set to 1 6 back to List of values ECU AIN 1 Value group Engine Related FW 1 3 0 Units Depends on ECU value Comm object 1015...

Page 391: ...erature C intake temperature C oil pressure bar boost pressure bar load oil temperature C etc 6 back to List of values ECU AIN 4 Value group Engine Related FW 1 3 0 Units Depends on ECU value Comm object 10156 Related applications AMF MRS Description This is one of the inputs which are defined by ECU Order of values depends on type of ECU Note Usually there are engine speed RPM fuel rate L h coola...

Page 392: ...erature C intake temperature C oil pressure bar boost pressure bar load oil temperature C etc 6 back to List of values ECU AIN 8 Value group Engine Related FW 1 3 0 Units Depends on ECU value Comm object 10160 Related applications AMF MRS Description This is one of the inputs which are defined by ECU Order of values depends on type of ECU Note Usually there are engine speed RPM fuel rate L h coola...

Page 393: ...erature C intake temperature C oil pressure bar boost pressure bar load oil temperature C etc 6 back to List of values ECU AIN 12 Value group Engine Related FW 1 3 0 Units Depends on ECU value Comm object 10164 Related applications AMF MRS Description This is one of the inputs which are defined by ECU Order of values depends on type of ECU Note Usually there are engine speed RPM fuel rate L h cool...

Page 394: ...erature C intake temperature C oil pressure bar boost pressure bar load oil temperature C etc 6 back to List of values ECU AIN 16 Value group Engine Related FW 1 3 0 Units Depends on ECU value Comm object 10168 Related applications AMF MRS Description This is one of the inputs which are defined by ECU Order of values depends on type of ECU Note Usually there are engine speed RPM fuel rate L h cool...

Page 395: ...erature C intake temperature C oil pressure bar boost pressure bar load oil temperature C etc 6 back to List of values ECU AIN 20 Value group Engine Related FW 1 3 0 Units Depends on ECU value Comm object 10172 Related applications AMF MRS Description This is one of the inputs which are defined by ECU Order of values depends on type of ECU Note Usually there are engine speed RPM fuel rate L h cool...

Page 396: ...erature C intake temperature C oil pressure bar boost pressure bar load oil temperature C etc 6 back to List of values ECU AIN 24 Value group Engine Related FW 1 3 0 Units Depends on ECU value Comm object 10172 Related applications AMF MRS Description This is one of the inputs which are defined by ECU Order of values depends on type of ECU Note Usually there are engine speed RPM fuel rate L h cool...

Page 397: ...erature C intake temperature C oil pressure bar boost pressure bar load oil temperature C etc 6 back to List of values ECU AIN 28 Value group Engine Related FW 1 3 0 Units Depends on ECU value Comm object 10172 Related applications AMF MRS Description This is one of the inputs which are defined by ECU Order of values depends on type of ECU Note Usually there are engine speed RPM fuel rate L h cool...

Page 398: ...ature C intake temperature C oil pressure bar boost pressure bar load oil temperature C etc 6 back to List of values ECU AIN 32 Value group Engine Related FW 1 3 0 Units Depends on ECU value Comm object 10172 Related applications AMF MRS Description This is one of the inputs which are defined by ECU Order of values depends on type of ECU Note Usually there are engine speed RPM fuel rate L h coolan...

Page 399: ...gnal expressed in Speed request Requested speed Accelerator pedal position 0 1350 RPM 0 50 1500 RPM 50 100 1650 RPM 100 Note Accelerator pedal position will be 0 if the engine is not running or loaded 6 back to List of values Requested RPM Value group Engine Related FW 1 3 0 Units RPM Comm object 10006 Related applications AMF MRS Description This value contains the speed which is currently reques...

Page 400: ...o List of values Group Generator Generator Frequency Value group Generator Related FW 1 3 0 Units Hz Comm object 8210 Related applications AMF MRS Description Frequency of generator 6 back to List of values Generator Voltage L1 L2 Value group Generator Related FW 1 3 0 Units V Comm object 9628 Related applications AMF MRS Description Generator phase to phase voltage between L1 and L2 phases 6 back...

Page 401: ...nits V Comm object 8193 Related applications AMF MRS Description Generator voltage on phase 2 6 back to List of values Generator Voltage L3 L1 Value group Generator Related FW 1 3 0 Units V Comm object 9630 Related applications AMF MRS Description Generator phase to phase voltage between L3 and L1 phases 6 back to List of values Generator Voltage L3 N Value group Generator Related FW 1 3 0 Units V...

Page 402: ...ion type page 209 Autodetect 6 back to List of values Nominal Power Value group Generator Related FW 1 3 0 Units V Comm object 9018 Related applications AMF MRS Description Generator nominal power Note Visible only when Connection type page 209 Autodetect 6 back to List of values Nominal Voltage Value group Generator Related FW 1 3 0 Units V Comm object 9917 Related applications AMF MRS Descriptio...

Page 403: ...r in phase L1 6 back to List of values Load P L2 Value group Load Related FW 1 3 0 Units kW Comm object 8525 Related applications AMF MRS Description Load active power in phase L2 6 back to List of values Load P L3 Value group Load Related FW 1 3 0 Units kW Comm object 8526 Related applications AMF MRS Description Load active power in phase L3 6 back to List of values Load Q Value group Load Relat...

Page 404: ...e power in phase L2 6 back to List of values Load Q L3 Value group Load Related FW 1 3 0 Units kVAr Comm object 8529 Related applications AMF MRS Description Load reactive power in phase L3 6 back to List of values Load S Value group Load Related FW 1 3 0 Units kVA Comm object 8565 Related applications AMF MRS Description Apparent power of Load 6 back to List of values Load S L1 Value group Load R...

Page 405: ...Factor Load Load Related FW 1 3 0 Units Comm object 9025 Related applications AMF MRS Description Load power factor 6 back to List of values Load Character Value group Generator Related FW 1 3 0 Units Comm object 8395 Related applications AMF MRS Description Character of the generator load L means inductive load C is capacitive and R is resistive load power factor 1 6 back to List of values Load P...

Page 406: ...Units Comm object 8534 Related applications AMF MRS Description Load power factor in phase L2 6 back to List of values Load Character L2 Value group Load Related FW 1 3 0 Units Comm object 8627 Related applications AMF MRS Description Character of the generator load in the L2 phase L means inductive load C is capacitive and R is resistive load power factor 1 6 back to List of values Load Power Fac...

Page 407: ...rrent L1 Value group Generator Related FW 1 3 0 Units A Comm object 8198 Related applications AMF MRS Description Current phase L1 of Load 6 back to List of values Load Load Current L2 Value group Generator Related FW 1 3 0 Units A Comm object 8199 Related applications AMF MRS Description Current phase L2 of Load 6 back to List of values Load Current L3 Value group Generator Related FW 1 3 0 Units...

Page 408: ...back to List of values Mains Voltage L2 N Value group Mains Related FW 1 3 0 Units V Comm object 8196 Related applications AMF Description Mains voltage on phase 2 6 back to List of values Mains Voltage L3 N Value group Mains Related FW 1 3 0 Units V Comm object 8197 Related applications AMF Description Mains voltage on phase 3 6 back to List of values Mains Voltage L1 L2 Value group Mains Related...

Page 409: ...ses 6 back to List of values Group Controller I O Battery Volts Value group Controller I O Related FW 1 3 0 Units V Comm object 8213 Related applications AMF MRS Description Controller supply voltage 6 back to List of values D Value group Controller I O Related FW 1 3 0 Units V Comm object 10603 Related applications AMF MRS Description D terminal voltage 6 back to List of values Analog Input 1 Val...

Page 410: ...e analog input 3 of the controller 6 back to List of values Binary Inputs Value group Controller I O Related FW 1 3 0 Units Comm object 8235 Related applications AMF MRS Description State of the binary inputs of the controller 6 back to List of values E Stop Value group Controller I O Related FW 1 3 0 Units Comm object 15780 Related applications AMF MRS Description Shows number of E STOP input the...

Page 411: ...n set active power 6 back to List of values Genset kVArh Value group Statistics Related FW 1 3 0 Units kVArh Comm object 8539 Related applications AMF MRS Description Counter of Gen set reactive power 6 back to List of values Conditioned Running Hours 1 Value group Statistics Related FW 1 3 0 Units h Comm object 20292 Related applications AMF MRS Description This value contains counted hours of ru...

Page 412: ...kWh Value group Statistics Related FW 1 3 0 Units kWh Comm object 11025 Related applications AMF Description Counter of mains active power 6 back to List of values Mains kVArh Value group Statistics Related FW 1 3 0 Units kVArh Comm object 11026 Related applications AMF Description Counter of mains reactive power 6 back to List of values Maintenance Timer 1 RunHours Value group Statistics Related ...

Page 413: ... Countdown until next maintenance 2 Statistic value for Maintenance Timer 2 RunHours page 257 6 back to List of values Maintenance Timer 2 Interval Value group Statistics Related FW 1 3 0 Units days Comm object 16388 Related applications AMF MRS Description Countdown until next maintenance 2 Statistic value for Maintenance Timer 2 Interval page 258 6 back to List of values Maintenance Timer 3 RunH...

Page 414: ...istics Related FW 1 3 0 Units Comm object 11196 Related applications AMF MRS Description Shutdown alarms counter This counter counts all occurrences of a shutdown alarm not only real shutdowns of the Gen set i e the counter is increased by 2 if two shutdown alarms appear simultaneously 6 back to List of values Total Fuel Consumption Value group Statistics Related FW 1 3 0 Units L Comm object 9040 ...

Page 415: ... 1 PAGE 455 function Note Maximum value is 1000000 6 back to List of values Pulse Counter 2 Value group Statistics Related FW 1 3 0 Units Comm object 10987 Related applications AMF MRS Description This is the value of PULSE COUNTER 2 PAGE 456 function Note Maximum value is 1000000 6 back to List of values Running Hours Value group Statistics Related FW 1 3 0 Units hours Comm object 8206 Related ap...

Page 416: ...ontains actual application in controller Example AMF25 AMF20 AMF9 AMF8 or MRS16 6 back to List of values Breaker State Value group Info Related FW 1 3 0 Units Comm object 9245 Related applications AMF MRS Description The value contains actual breaker state message which is shown on the main screen of the controller 6 back to List of values Connection Type Value group Info Related FW 1 3 0 Units Co...

Page 417: ...al branch of firmware in controller 6 back to List of values FW Version Value group Info Related FW 1 3 0 Units Comm object 24339 Related applications AMF MRS Description Major and minor firmware version number 6 back to List of values HW Version Value group Info Related FW 1 3 0 Units Comm object Related applications AMF MRS Description Major and minor hardware version number 6 back to List of va...

Page 418: ...which is inserted in slot A 6 back to List of values SPI Module B Value group Info Related FW 1 3 0 Units Comm object 14448 Related applications AMF MRS Description The name of plug in module which is inserted in slot B 6 back to List of values Timer Text Value group Info Related FW 1 3 0 Units Comm object 10040 Related applications AMF MRS Description The value contains the Current process timer ...

Page 419: ...e of binary outputs 6 back to List of values Log Bout 3 Value group Log Bout Related FW 1 3 0 Units Comm object 9145 Related applications AMF MRS Description State of binary outputs 6 back to List of values Log Bout 4 Value group Log Bout Related FW 1 3 0 Units Comm object 9146 Related applications AMF MRS Description State of binary outputs 6 back to List of values Log Bout 5 Value group Log Bout...

Page 420: ... 3 0 Units Comm object 9149 Related applications AMF MRS Description State of binary outputs 6 back to List of values Log Bout 8 Value group Log Bout Related FW 1 3 0 Units Comm object 9150 Related applications AMF MRS Description State of binary outputs 6 back to List of values Log Bout 9 Value group Log Bout Related FW 1 3 0 Units Comm object 11896 Related applications AMF MRS Description State ...

Page 421: ...1 3 0 Units Comm object 20745 Related applications AMF MRS Description Values of LBO Fixed Protections State 6 back to List of values Fixed Protections States 3 Value group Fixed Protection States Related FW 1 3 0 Units Comm object 20746 Related applications AMF MRS Description Values of LBO Fixed Protections State 6 back to List of values Fixed Protections States 4 Value group Fixed Protection St...

Page 422: ...o List of values Group CM 4G GPS Signal Strength Value group CM 4G GPS Related FW 1 3 0 Units Comm object 24302 Related applications AMF MRS Description This value contains information about relative strength of the cellular signal received by the CM2 4G GPS module It is a relative value helping to find the best signal and for troubleshooting cases 6 back to List of values Network Status Value gro...

Page 423: ...d can t be send 7 Command can t be send 8 HELO command was refused 11 AUTH LOGIN command was refused 12 Wrong user name 13 Wrong password 14 MAIL FROM command was refused 15 RCPT TO command was refused 16 DATA command was refused 17 Sending of email failed 18 SMTP server refused the data of email 19 SMTP server refused the data of email 20 QUIT command was refused 21 Lost of connection 23 Error du...

Page 424: ... of data connection 6 back to List of values GPS Status Value group CM 4G GPS Related FW 1 3 0 Units Comm object 23973 Related applications AMF MRS Description Value describing the GPS signal Code Description Undefined GPS signal is not available Check antenna connection Searching Looking up for signal from available satellites Fixed GPS signal available 6 back to List of values Latitude Value gro...

Page 425: ... Description Number of available satellites for GPS location 6 back to List of values Speed Value group CM 4G GPS Related FW 1 3 0 Units Comm object 24227 Related applications AMF MRS Description Actual speed of the controller calculated from the GPS coordinates 6 back to List of values HomePosDist Value group CM 4G GPS Related FW 1 3 0 Units km Comm object 11680 Related applications AMF MRS Descr...

Page 426: ...ected inoperable Conn operable Connected operable Susp AGkeyEmpty AirGate is not set in the controller AirGate Status 6 back to List of values AirGate ID Value group CM 4G GPS Related FW 1 3 0 Units Comm object 24309 Related applications AMF MRS Description Identification string generated by AirGate server for the purpose of establishing communication via InteliConfig or any other supported PC too...

Page 427: ... CM Ethernet Related FW 1 3 0 Units Comm object 24100 Related applications AMF MRS Description Backup domain name server 6 back to List of values Modem Status Value group CM 4G GPS Related FW 1 3 0 Units Comm object 24288 Related applications AMF MRS Description The text of this value represents the status of the modem Code Description OK Module successfully initialized and connected to the cellul...

Page 428: ...ng text E08 Modem configuration error E09 It is not possible to get signal strength E10 It is not possible to get operator name E11 Loss of registration into cellular network was detected E12 Data error E13 Data error E14 Modem was restarted E SMS send It is not possible to send SMS Possible reasons Wrong number SIM doesn t support SMS E18 Modem hardware configuration error E conn lost Loss of con...

Page 429: ...subnet mask 6 back to List of values Current Gateway Value group CM Ethernet Related FW 1 3 0 Units Comm object 24182 Related applications AMF MRS Description Current gateway address 6 back to List of values Primary DNS Value group CM Ethernet CM 4G GPS Related FW 1 3 0 Units Comm object 24181 Related applications AMF MRS Description Current domain name server 6 back to List of values Secondary DN...

Page 430: ... applications AMF MRS Description IP address of AirGate 2 node to which the module is currently attached 6 back to List of values AirGate Status Value group CM Ethernet Related FW 1 3 0 Units Comm object 24344 Related applications AMF MRS Description Diagnostic code for AirGate connection Helps in troubleshooting Code Description Not defined Setpoint AirGate Connection is Disabled Wait to connect ...

Page 431: ...efused 12 Wrong user name 13 Wrong password 14 MAIL FROM command was refused 15 RCPT TO command was refused 16 DATA command was refused 17 Sending of email failed 20 QUIT command was refused 25 It is impossible to create data for command DATA 26 It is impossible to read data for command DATA 27 Email address can t be read 30 SMTP server address translation error from DNS server 31 Error reading em...

Page 432: ...ated FW 1 3 0 Units DD MM YYYY Comm object 24553 Related applications AMF MRS Description Shows setup date 6 back to List of values Time Value group Date Time Related FW 1 3 0 Units HH MM SS Comm object 24554 Related applications AMF MRS Description Shows setup time 6 back to List of values Time Mode Value group Date Time Related FW 1 3 0 Units HH MM SS Comm object 20252 Related applications AMF M...

Page 433: ...W 1 3 0 Units Comm object 14292 Related applications AMF MRS Description Binary inputs from extension module in slot B 6 back to List of values Group PLC PLC BOUT 1 Value group PLC Related FW 1 3 0 Units Comm object 10424 Related applications AMF MRS Description State of binary outputs of PLC 6 back to List of values PLC BOUT 2 Value group PLC Related FW 1 3 0 Units Comm object 10425 Related appli...

Page 434: ...uts of PLC 6 back to List of values PLC BOUT 5 Value group PLC Related FW 1 3 0 Units Comm object 10428 Related applications AMF MRS Description State of binary outputs of PLC 6 back to List of values PLC BOUT 6 Value group PLC Related FW 1 3 0 Units Comm object 10429 Related applications AMF MRS Description State of binary outputs of PLC 6 back to List of values PLC BOUT 7 Value group PLC Related...

Page 435: ... to List of values PLC Resource 3 Value group PLC Related FW 1 3 0 Units Comm object 10506 Related applications AMF MRS Description Internal state of PLC countdowns e g state of block Timer etc 6 back to List of values PLC Resource 4 Value group PLC Related FW 1 3 0 Units Comm object 10507 Related applications AMF MRS Description Internal state of PLC countdowns e g state of block Timer etc 6 back...

Page 436: ... to List of values PLC Resource 7 Value group PLC Related FW 1 3 0 Units Comm object 10510 Related applications AMF MRS Description Internal state of PLC countdowns e g state of block Timer etc 6 back to List of values PLC Resource 8 Value group PLC Related FW 1 3 0 Units Comm object 10511 Related applications AMF MRS Description Internal state of PLC countdowns e g state of block Timer etc 6 back...

Page 437: ...uts for binary values and functions Alphabetical groups of Logical binary inputs LBI A 439 LBI C 443 LBI D 445 LBI E 445 LBI F 448 LBI G 449 LBI H 451 LBI I 451 LBI M 451 LBI O 454 LBI P 454 LBI R 456 LBI S 460 LBI T 463 For a full list of Logical binary inputs go to the chapter Logical binary inputs alphabetically page 438 ...

Page 438: ...nk 445 ECU Red Lamp Solid 446 ECU Speed Down 446 ECU Speed Up 446 ECU Wait To Start Blink 446 ECU Wait To Start Fast Blink 446 ECU Wait To Start Solid 447 ECU Yellow Lamp Blink 447 ECU Yellow Lamp Fast Blink 447 ECU Yellow Lamp Solid 447 Emergency MAN 448 Emergency Stop 448 Fault Reset Button 448 Fuel Pump On Off 449 GCB Button 449 GCB Disable 449 GCB Feedback 450 Geo Home Position 450 Geo Fencing...

Page 439: ...is binary input is active setpoints in Alternate Config group are switched to the third set setpoints with number 3 IMPORTANT If LBO ECU POWER RELAY PAGE 474 is used change of alternate configuration can be made only in prestart phase So prestart has to be set up for enough long time Alternate Config 3 6 back to Logical binary inputs alphabetically Related FW 1 3 0 Related applications AMF MRS Com...

Page 440: ...Description When this LBI is active there is active alarm Wrn ATT DEF Level Lamp page 534 in alarmlist and ATT DEF Level Lamp icon in Aftertreatment HMI screen is blinking fast ATT DEF Level Lamp Fast Blink 6 back to Logical binary inputs alphabetically Related FW 1 3 0 Related applications AMF MRS Comm object 1075 Description When this LBI is active there is active alarm Wrn ATT DEF Level Lamp pa...

Page 441: ...80 Description Aftertreatment Regeneration Force Switch User manually activates regeneration function Push button control function activated by pulse signals longer than 5 seconds will be carried as long as the input is active ATT Force Regen 6 back to Logical binary inputs alphabetically Related FW 1 3 0 Related applications AMF MRS Comm object 1070 Description When this LBI is active there is ac...

Page 442: ...ct 1079 Description When this LBI is active there is active alarm Wrn ATT Inhibited Lamp page 534 in alarmlist and Inhibited Lamp icon in Aftertreatment HMI screen is blinking ATT Inhibited Lamp Blink 6 back to Logical binary inputs alphabetically Related FW 1 3 0 Related applications AMF MRS Comm object 1080 Description When this LBI is active there is active alarm Wrn ATT Inhibited Lamp page 534...

Page 443: ... Logical binary inputs alphabetically Related FW 1 3 0 Related applications AMF MRS Comm object 1074 Description When this LBI is active there is active alarm Wrn ATT SCR Error Lamp page 534 in alarmlist and SCR Error Lamp icon in Aftertreatment HMI screen is blinking fast ATT SCR Error Lamp Fast Blink 6 back to Logical binary inputs alphabetically Related FW 1 3 0 Related applications AMF MRS Com...

Page 444: ...alphabetically Related FW 1 3 0 Related applications AMF MRS Comm object 946 Description Logical binary input CHOKE INHIBIT prevent Choke functionality when logical binary output CHOKE PAGE 471 is activated If CHOKE INHIBIT is activated when CHOKE LBO is active CHOKE LBO is deactivated immediately and vice versa if LBI CHOKE INHIBIT is deactivated and LBO CHOKE should be active then is activated C...

Page 445: ...o switch on ECU POWER RELAY PAGE 474 when engine start is not requested It is intended to enable engine values reading when engine doesn t run When this binary input is active binary output ECU POWER RELAY PAGE 474 is active too When this binary input is inactive function of ECU POWER RELAY PAGE 474 is not affected ECU Key Switch 6 back to Logical binary inputs alphabetically Related FW 1 3 0 Rela...

Page 446: ...object 165 Description This binary input is used to set the setpoint ECU Speed Adjustment page 255 by binary inputs When the LBI is activated the setpoint is increase by 2 ECU Speed Up 6 back to Logical binary inputs alphabetically Related FW 1 3 0 Related applications AMF MRS Comm object 1064 Description When this LBI is active there is active alarm Wrn ECU Wait To Start page 533 in alarmlist and...

Page 447: ...amp icon in Aftertreatment HMI screen is blinking ECU Yellow Lamp Blink 6 back to Logical binary inputs alphabetically Related FW 1 3 0 Related applications AMF MRS Comm object 1059 Description When this LBI is active there is active alarm Wrn ECU Yellow Lamp page 533 in alarmlist and ECU Yellow Lamp icon in Aftertreatment HMI screen is blinking fast ECU Yellow Lamp Fast Blink 6 back to Logical bi...

Page 448: ...ng to the situation in the moment of deactivation i e the Gen set remains running loaded if it was running and GCB was closed in the moment the input was deactivated Emergency MAN 6 back to Logical binary inputs alphabetically Related FW 1 3 0 Related applications AMF MRS Comm object 40 Description The shutdown procedure will start immediately when this input is activated Note In case of controlle...

Page 449: ...ontrol by this binary input IMPORTANT It is necessary to configure analog input FUEL LEVEL PAGE 508 for proper function of this binary input Fuel Pump On Off 6 back to Logical binary inputs alphabetically LBI G Related FW 1 3 0 Related applications AMF MRS Comm object 193 Description Binary input has the same function as the GCB button on the InteliLite 4 front panel It is evaluated in MAN mode on...

Page 450: ... do not configure the feedback to binary inputs GCB Feedback 6 back to Logical binary inputs alphabetically Related FW 1 3 0 Related applications AMF MRS Comm object 219 Description This binary input can be used to adjust home position of gen set In case that binary input is active setpoints Home Latitude page 324 and Home Longitude page 325 are adjusted automatically from actual coordinates from ...

Page 451: ...ogical binary inputs alphabetically LBI I Related FW 1 3 0 Related applications AMF MRS Comm object 624 Description This binary input changes cooling speed from nominal to idle Idle Speed 6 back to Logical binary inputs alphabetically LBI M Related FW 1 3 0 Related applications AMF MRS Comm object 622 Description If the input is active the automatic start of the Gen set at Mains failure is blocked...

Page 452: ...ion 6 back to Logical binary inputs alphabetically Related FW 1 3 0 Related applications AMF MRS Comm object 194 Description This binary input has the same function as MCB button on the InteliLite 4 front panel It is evaluated in MAN mode only MCB Button 6 back to Logical binary inputs alphabetically Related FW 1 3 0 Related applications AMF MRS Comm object 124 Description When this LBI is active ...

Page 453: ...is input for indication whether the mains circuit breaker is open or closed Image 8 27 MCB Feedback 1 Image 8 28 MCB Feedback 2 Note InteliLite 4 controller can work even without breaker feedbacks in this case do not configure the feedback to binary inputs MCB Feedback 6 back to Logical binary inputs alphabetically ...

Page 454: ...when LBI is active then oil pressure is OK and is higher than starting oil pressure Note In case that you want to use binary input Oil Pressure just for protection please create new binary input with User protection Oil Pressure 6 back to Logical binary inputs alphabetically LBI P Related FW 1 3 0 Related applications AMF MRS Comm object 42 Description While this LBI is active Gen set skips presta...

Page 455: ...ed off ExtDisabled protection is turned off by LBI Protection Force Disable 6 back to Logical binary inputs alphabetically Related FW 1 3 0 Related applications AMF MRS Comm object 87 Description This is the input of the Pulse Counter 1 function The module counts pulses at the input and if the input pulses counter reaches value given by the setpoint Conversion Coefficient Pulse 1 page 254 the coun...

Page 456: ...mm object 61 Description Closing of the GCB in MRS or transferring of the load from the mains to Gen set in AMF Application TEST Remote TEST On Load MRS Gen set started and running until the TEST mode deactivated Active Gen set is put to TEST mode On the top of it the GCB is closed The same behavior like the REMOTE START STOP PAGE 459 Inactive Gen set comes back to the original mode and behaves ac...

Page 457: ...ically Related FW 1 3 0 Related applications AMF MRS Comm object 4 Description If the input is active the controller will not accept any actions regarding the system control e g writing of commands and setpoint changes via remote communication interfaces Remote Ctrl Lock 6 back to Logical binary inputs alphabetically Related FW 1 3 0 Related applications AMF MRS Comm object 618 Description The con...

Page 458: ...ller is switched to the OFF mode there are four modes OFF MAN AUTO TEST when this binary input is active When opens controller is switched back to previous mode Remote control priority Remote OFF Highest priority Remote TEST Remote MAN Remote AUTO Lowest Priority Remote OFF 6 back to Logical binary inputs alphabetically ...

Page 459: ...ker closed Gen set remains running as long as binary input Rem Start Stop is active For more details see timing diagram below Image 8 29 Remote Start Stop Taken action in AMF application AUTO Mode Active Start the Gen set and stay running with opened GCB if Mains OK Go to Island if Mains fails due to AMF function If Mains is not OK the AMF function starts the Gen set to Island anyway Inactive Stop...

Page 460: ... in the alarm list but they will not take effect regarding the Gen set control Note Sd Override page 460 is indicated in the alarm list if Sd Override mode is active to inform the operator that the engine is not protected IMPORTANT MISUSE OF THIS INPUT CAN CAUSE DAMAGE TO THE GEN SET Note User protection Sd Override is not blocked Sd Override 6 back to Logical binary inputs alphabetically Related ...

Page 461: ...Related applications AMF MRS Comm object 1112 Description When the first rising edge appears on the binary input the MODE is changed to AUTO Falling edge has no effect and controller stays in AUTO MODE There is no blocking between these Switch To LBIs Example CU is in OFF mode LBI Switch To AUTO is activated CU goes to AUTO Mode LBI stays active Then LBI SWITCH TO MAN PAGE 462 is activated CU goes...

Page 462: ... below GO to control priority Highest OFF MAN Lowest AUTO Switch To MAN 6 back to Logical binary inputs alphabetically Related FW 1 3 0 Related applications AMF MRS Comm object 1110 Description When the first rising edge appears on the binary input the MODE is changed to OFF Falling edge has no effect and controller stays in OFF MODE There is no blocking between these Switch To LBIs Example CU is ...

Page 463: ...ine and opening all breakers Activation of Total Emergency Stop leads to Alarm Total Emergency Stop is activated and history record TOTAL EMERGENCY STOP is created Controller will open MCB and GCB Controller will keep MCB and GCB open as long as alarm is present in alarm list Engine is stopped Total Emergency Stop 6 back to Logical binary inputs alphabetically ...

Page 464: ...for binary values and functions Alphabetical groups of Logical binary outputs LBO A 466 LBO C 471 LBO D 472 LBO E 473 LBO F 477 LBO G 479 LBO H 486 LBO I 487 LBO L 489 LBO M 489 LBO N 495 LBO P 496 LBO R 498 LBO S 499 LBO V 504 For a full list of Logical binary inputs go to the chapter Logical binary outputs alphabetically page 465 ...

Page 465: ...e Timer 2 476 Exercise Timer 3 476 Exercise Timer 4 476 FltRes Button Echo 477 FltRes Button State 477 Frequency Select 477 Fuel Pump 477 Fuel Solenoid 477 GCB Button Echo 479 GCB Button State 479 GCB Close Open 480 GCB OFF Coil 481 GCB ON Coil 482 GCB UV Coil 482 Gen set Active 483 Generator Healthy 484 Glow Plugs 484 Heartbeat 486 Horn 486 HornRes Button Echo 486 HornRes Button State 486 Idle No...

Page 466: ...cally Related FW 1 3 0 Related applications AMF MRS Comm object 9 Description Output is activated when any BOC alarm appears The output opens if No BOC alarm is active and Fault reset button is pressed AL Common BOC 6 back to Logical binary outputs alphabetically Related FW 1 3 0 Related applications AMF MRS Comm object 6 Description Output is activated when any sensor fail alarm appears The outpu...

Page 467: ...utputs alphabetically Related FW 1 3 0 Related applications AMF MRS Comm object 1267 Description This output is active generator frequency warning alarm is present in alarmlist or isn t confirm AL Gen Freq Wrn 6 back to Logical binary outputs alphabetically Related FW 1 3 0 Related applications AMF MRS Comm object 1266 Description This output is active when at least one generator frequency alarm i...

Page 468: ...ted applications AMF MRS Comm object 1271 Description This output is active when at least one mains frequency BOC or Sd alarm is present in alarmlist or isn t confirm AL Mains Frequency 6 back to Logical binary outputs alphabetically Related FW 1 3 0 Related applications AMF MRS Comm object 1270 Description This output is active when at least one mains voltage BOC or Sd alarm is present in the ala...

Page 469: ...6 back to Logical binary outputs alphabetically Related FW 1 3 0 Related applications AMF MRS Comm object 109 Description This output is active when the BOC Overcurrent IDMT page 573 or BOC Short Circuit page 572 alarm is present in alarmlist or isn t confirm AL Overcurrent 6 back to Logical binary outputs alphabetically Related FW 1 3 0 Related applications AMF MRS Comm object 2 Description The o...

Page 470: ...tion This output is active when ATT Inhibited Lamp is active ATT Inhibited Lamp 6 back to Logical binary outputs alphabetically Related FW 1 3 0 Related applications AMF MRS Comm object Description This output is active when ATT Interlock Status is active ATT Interlock Status 6 back to Logical binary outputs alphabetically Related FW 1 3 0 Related applications AMF MRS Comm object 2153 Description ...

Page 471: ... 501 is activated Output is deactivated when one of these conditions is fulfilled Choke Time is elapsed Generator voltage is higher than Choke Voltage Logical binary input Choke Inhibit is activated Or when some of these situations during start occurs Any second level alarm Emergency stop Stop command Cranking pause Choke 6 back to Logical binary outputs alphabetically Related FW 1 3 0 Related app...

Page 472: ...re is at least one unconfirmed Alarms level 1 page 521 in the alarmlist Common Alarm Level 1 6 back to Logical binary outputs alphabetically Related FW 1 3 0 Related applications AMF MRS Comm object 16 Description This output is closed when there is at least one unconfirmed Alarms level 2 page 552 in the alarmlist Common Alarm Level 2 6 back to Logical binary outputs alphabetically LBO D Related F...

Page 473: ...ed FW 1 3 0 Related applications AMF MRS Comm object 1443 Description This LBO is used to activate corresponding stage of external load bank Dummy Load Stage 5 6 back to Logical binary outputs alphabetically LBO E Related FW 1 3 0 Related applications AMF MRS Comm object 347 Description This output is active when an ECU is configured connected and the communication with the ECU is established Note...

Page 474: ...n of Sd ECU Communication Fail page 559 or Wrn ECU Communication Fail page 532 alarms With configured LBO ECU Power Relay these alarms are evaluated only when this LBO is active Without configured LBO ECU Power Relay these alarm are evaluated all the time ECU Power Relay 6 back to Logical binary outputs alphabetically Related FW 1 3 0 Related applications AMF MRS Comm object 350 Description This o...

Page 475: ...al malfunction This flag is taken from the DM1 frame on standard J1939 ECUs Some ECUs provide this flag in their own proprietary frames and some do not provide the flag at all ECU Yellow Lamp 6 back to Logical binary outputs alphabetically Related FW 1 3 0 Related applications AMF MRS Comm object 2410 Description LBO Electrical Alarm is active when any of generator protections of any alarm level t...

Page 476: ... has a higher priority than Subgroup Timer 2 page 300 Exercise Timer 2 6 back to Logical binary outputs alphabetically Related FW 1 3 0 Related applications AMF MRS Comm object 1946 Description This is an output from the Exercise timer 3 This output makes it easy to make periodic tests of the Gen set and its activation depends on the setpoints in the Subgroup Timer 3 page 308 subgroup This output ...

Page 477: ... 1815 Description The Frequency select output is active when Nominal Frequency Frequency Settings is equal to 50 Hz and is deactivated when Nominal Frequency Frequency Settings is equal to 60 Hz Frequency Select 6 back to Logical binary outputs alphabetically Related FW 1 3 0 Related applications AMF MRS Comm object 1253 Description Output is activated when the value of Fuel Level lies under the v...

Page 478: ...s setting is done by Fuel Solenoid page 225 setpoint in Engine Settings group Diesel The output is activated before binary output STARTER PAGE 501 The lead time is adjusted by setpoint Fuel Solenoid Lead page 235 Image 8 32 Fuel Solenoid 1 Image 8 33 Fuel Solenoid 2 The output is deactivated when Emergency Stop comes Cooled Gen set is stopped In pause between repeated starts ...

Page 479: ...applications AMF MRS Comm object 35 Description This output provides 1s pulse when GCB button is pressed on the controller front facia or GCB button is pressed on any of external local remote terminals or GCB command is received via communication line or the input GCB BUTTON is activated GCB Button Echo 6 back to Logical binary outputs alphabetically Related FW 1 3 0 Related applications AMF MRS C...

Page 480: ...eaker position requested by the controller The breaker must react within 5 seconds to a close or open command otherwise an alarm is issued Note InteliLite 4 controller can work even without breaker feedbacks in this case do not configure the feedback to binary inputs Image 8 35 GCB Close command Image 8 36 GCB Open command GCB Close Open 6 back to Logical binary outputs alphabetically ...

Page 481: ...he output is intended for control of open coil of generator circuit breaker The output gives a pulse in the moment the breaker has to be opened The pulse lasts until the feedback deactivates but at least for 5 seconds Image 8 37 GCB OFF Coil command GCB OFF Coil 6 back to Logical binary outputs alphabetically ...

Page 482: ...ker has to be closed Image 8 38 GCB ON Coil close command GCB ON Coil 6 back to Logical binary outputs alphabetically Related FW 1 3 0 Related applications AMF MRS Comm object 44 Description The output is intended for control of undervoltage coil of generator circuit breaker The output is active the whole time when the generator is running The output is deactivated for at least 5 seconds in the mo...

Page 483: ...ated applications AMF MRS Comm object 60 Description The output is closed at the beginning of the Prestart Time period and opens when the Gen set is fully stopped If the Gen set fails to start then this output is opened after last cranking attempt The output also closes if the engine begins to rotate spontaneously Gen set Active 6 back to Logical binary outputs alphabetically ...

Page 484: ...the voltage frequency voltage unbalance has got out of limits when GCB is closed Generator Healthy 6 back to Logical binary outputs alphabetically Related FW 1 3 0 Related applications AMF MRS Comm object 1252 Description This output is dedicated for diesel engine only This output will be active for exact time pre set by setpoint Glow Plugs Time page 228 before every starting attempt The output is...

Page 485: ...226 as long as Cranking Fail Pause page 226 Image 8 42 Glow Plugs in Cranking Fail Pause 1 When the Glow Plugs Time page 228 is shorter than Cranking Fail Pause page 226 then the Glow Plugs Time page 228 in Cranking Fail Pause page 226 as long as the normal Glow Plugs Time page 228 Image 8 43 Glow Plugs in Cranking Fail Pause 2 6 back to Logical binary outputs alphabetically ...

Page 486: ...lt reset is pressed Horn reset is pressed Horn Timeout page 220 has elapsed Horn 6 back to Logical binary outputs alphabetically Related FW 1 3 0 Related applications AMF MRS Comm object 31 Description This output provides 1s pulse when Horn Reset button is pressed on the controller front facia or Horn Reset button is pressed on any of external local remote terminals or Horn Reset command is recei...

Page 487: ...r reaching Starting RPM page 227 A Start Fail protection occurs if the RPM drop below 2RPM during idle Image 8 44 Idle Nominal Note Connect binary output Idle Nominal to speed governor to switch the speed opened Idle closed Nominal for normally open contact type Idle Nominal 6 back to Logical binary outputs alphabetically Related FW 1 3 0 Related applications AMF MRS Comm object 37 Description Thi...

Page 488: ...e engine doesn t start or Sd or E Stop is active Note This function is the same as ECU POWER RELAY PAGE 474 Ignition ON stays there from historical reasons Ignition On 6 back to Logical binary outputs alphabetically Related FW 1 3 0 Related applications AMF MRS Comm object 1222 Description This output is activated when the engine proceeded through initialization phase Initialization phase is resta...

Page 489: ... deactivated load is being reconnected in the order 5 4 3 2 1 The load disconnected by the LBO Nr 1 is the less essential load of these three possible loads instances Load Shedding Stage 2 6 back to Logical binary outputs alphabetically LBO M Related FW 1 3 0 Related applications AMF MRS Comm object 78 Description This output is active while mains failure is not detected and mains voltage and freq...

Page 490: ...rminals or MCB command is received via communication line or the input MCB BUTTON is activated MCB Button Echo 6 back to Logical binary outputs alphabetically Related FW 1 3 0 Related applications AMF MRS Comm object 2697 Description LBO is active as long as it s button is pressed or it s LBI is active MCB Button State 6 back to Logical binary outputs alphabetically Related FW 1 3 0 Related applic...

Page 491: ...InteliLite4 AMF20 Global Guide 491 Image 8 47 MCB Close command Image 8 48 MCB Close command 6 back to Logical binary outputs alphabetically ...

Page 492: ...The output is intended for control of open coil of mainsbus circuit breaker The output gives a pulse in the moment the breaker has to be opened The pulse lasts until the feedback deactivates but at least for 5 seconds Image 8 49 MCB OFF Coil command MCB OFF Coil 6 back to Logical binary outputs alphabetically ...

Page 493: ...omm object 46 Description The output is intended for control of close coil of mainsbus circuit breaker The output gives at least 5 second pulse in the moment the breaker has to be closed Image 8 50 MCB ON Coil close command MCB ON Coil 6 back to Logical binary outputs alphabetically ...

Page 494: ...undervoltage coil of mainsbus circuit breaker The output is active the whole time when the controller is switched on The output is deactivated for at least 5 seconds in the moment the breaker has to be switched off Image 8 51 MCB UV Coil close command Image 8 52 MCB UV Coil open command MCB UV Coil 6 back to Logical binary outputs alphabetically ...

Page 495: ... 17 Description This output is active whenever the controller is in OFF mode Mode OFF 6 back to Logical binary outputs alphabetically Related FW 1 3 0 Related applications AMF MRS Comm object 20 Description This output is active whenever the controller is in TEST mode Mode TEST 6 back to Logical binary outputs alphabetically LBO N Related FW 1 3 0 Related applications AMF MRS Comm object 1248 Desc...

Page 496: ... specific CAN module Peripheral Module Comm Fail 6 back to Logical binary outputs alphabetically Related FW 1 3 0 Related applications AMF MRS Comm object 36 Description This output can be used for control of any device which has to be activated just before start the output is active for time period of Prestart Time page 227 The output is deactivated 100 ms before the STARTER PAGE 501 output is ac...

Page 497: ...6 is long as Cranking Fail Pause page 226 minus 100 ms Image 8 54 Prestart in Cranking Fail Pause 1 When the Prestart Time page 227 is shorter than Cranking Fail Pause page 226 then the Prestart Time page 227 in Cranking Fail Pause page 226 is long as normal Prestart Time page 227 Image 8 55 Prestart in Cranking Fail Pause 2 6 back to Logical binary outputs alphabetically ...

Page 498: ...in AUTO controller mode and no red alarm is present in the alarmlist when the red alarm is confirmed during Stop Valve and other requirements are fulfilled then the LBO is still inactive until the state ready Ready To AMF 6 back to Logical binary outputs alphabetically Related FW 1 3 0 Related applications AMF MRS Comm object 58 Description the output is active whenever the GCB is closed or can be...

Page 499: ...deactivated The out remains active until engine stop and cooling period elapses Image 8 56 Running Running 6 back to Logical binary outputs alphabetically LBO S Related FW 1 3 0 Related applications AMF MRS Comm object 962 Description The output is active if SD OVERRIDE PAGE 460 input is active and open if SD OVERRIDE PAGE 460 input is inactive This output is usually used to send information about...

Page 500: ...pressed on any of external local remote terminals or Start command is received via communication line or the input START BUTTON is activated Start Button Echo 6 back to Logical binary outputs alphabetically Related FW 1 3 0 Related applications AMF MRS Comm object 2693 Description LBO is active as long as it s button is pressed or it s LBI is active Start Button State 6 back to Logical binary outp...

Page 501: ... cranking is exceeded request to stop comes up D value is higher than D Threshold page 243 Oil pressure value is higher than Starting Oil Pressure page 228 Generator voltage 25 of Nominal Voltage Ph N page 211 or Nominal Voltage Ph Ph page 211 any phase Starter 6 back to Logical binary outputs alphabetically Related FW 1 3 0 Related applications AMF MRS Comm object 26 Description Logical binary ou...

Page 502: ...s alphabetically Related FW 1 3 0 Related applications AMF MRS Comm object 2694 Description LBO is active as long as it s button is pressed or it s LBI is active Stop Button State 6 back to Logical binary outputs alphabetically Related FW 1 3 0 Related applications AMF MRS Comm object 25 Description Output is active for 1 second after STOP SOLENOID PAGE 502 output activation This signal is sent to...

Page 503: ... and is deactivated 12 s after last running engine indication went off i e engine is stopped Image 8 59 Stop Solenoid 1 Image 8 60 Stop Solenoid 2 Note If Additional running engine indications page 114 went off during 5 s pause than Stop Solenoid is not activated again otherwise stop solenoid is activated again 6 back to Logical binary outputs alphabetically ...

Page 504: ...ly when EMERGENCY STOP PAGE 448 or E Stop is activated or when controller is switched to OFF mode Note The output is intended for control of an engine room ventilation fan engine container ventilation fan container louvres or similar running gen set technology Ventilation 6 back to Logical binary outputs alphabetically Related FW 1 3 0 Related applications AMF MRS Comm object 2090 Description This...

Page 505: ...al Guide 505 Note The output is intended for control of an engine room ventilation fan engine container ventilation fan container louvres or similar running gen set technology 6 back to Logical binary outputs alphabetically ...

Page 506: ...ical analog inputs are Logical analog inputs are inputs for analog values Alphabetical groups of Logical analog inputs LAI C 508 LAI F 508 LAI N 508 LAI O 508 LAI R 509 For a full list of Logical analog inputs go to the chapter Logical analog inputs alphabetically page 507 ...

Page 507: ...Logical analog inputs alphabetically Coolant Temp 508 Fuel Level 508 Not Used 508 Oil Pressure 508 Oil Temp 509 RPM pickup 509 6 back to Controller objects InteliLite4 AMF20 Global Guide 507 ...

Page 508: ...n percentage Fuel Level 6 back to Logical analog inputs alphabetically LAI N Related FW 1 3 0 Related applications AMF MRS Comm object 230 Description Input has no function Not Used 6 back to Logical analog inputs alphabetically LAI O Related FW 1 3 0 Related applications AMF MRS Comm object 9 Description Logical analog input designed for oil pressure value received from analog sensor Note This an...

Page 509: ...Logical analog input designed for oil temperature value received from analog sensor Oil Temp 6 back to Logical analog inputs alphabetically LAI R Related FW 1 3 0 Related applications AMF MRS Comm object 8 Description This LAI selects the source of RPM RPM pickup 6 back to Logical analog inputs alphabetically ...

Page 510: ...C List of PLC blocks Group Basic logical functions OR AND 511 Ext XOR RS 513 Group Comparison of analog inputs Comparator With Hysteresis 514 Comparator With Delay 515 Group Time functions Timer 516 Delay 518 Group Other functions Decomposer 520 ...

Page 511: ...Guide 511 Group Basic Logical functions PLC group Basic logical functions Related FW 1 3 0 Related applications AMF MRS Comm object 1 Inputs Input Type Negation Range Function Input 1 8 Binary Yes 0 1 Inputs 1 8 Outputs OR AND ...

Page 512: ...l operation OR AND of 2 8 binary operands The inputs as well as the output can be inverted Input 1 Input 2 Output 0 0 0 0 1 1 1 0 1 1 1 1 Function OR Input 1 Input 2 Output 0 0 0 0 1 0 1 0 0 1 1 1 Function AND There have to be at least 2 inputs every time There may be up to 8 inputs configured Image 8 61 Configuration of OR AND block 6 back to List of PLC blocks ...

Page 513: ...ption The block provides logical function of two values XOR or RS flip flop Both inputs and output can be inverted Input 1 Input 2 Output 0 0 0 0 1 1 1 0 1 1 1 0 Function XOR The block contains a setting for RS dominance This setting is available in the block dialog window i e this setting is constantly set by configuration and cannot be changed dynamically in operation Input 1 S Input 2 R R latch...

Page 514: ...tion Range Function Input Analog No Any Compared value Input ON Analog No Same as Input Comparative level for switching on Input OFF Analog No Same as Input Comparative level for switching off Outputs Output Type Negation Range Function Output Binary No 0 1 Comparator output Description The block compares the input value with the comparative levels The behavior depends on whether the ON level is h...

Page 515: ...rom controller IMPORTANT In case that the values on inputs have different decimal numbers then the values are converted and the name of block is red It is strongly recommended to use values with the same decimal numbers 6 back to List of PLC blocks PLC group Comparison of analog inputs Related FW 1 3 0 Related applications AMF MRS Comm object 4 Inputs Comparator With Delay ...

Page 516: ...ion The block works as an analog switch It compares the input value with the comparative level The output will switch on if the input is equal or higher than the comparative level for time longer than the delay Image 8 65 Principle of delay Image 8 66 Configuration of Comp Time block Note Input 2 and Delay can be constants or values from controller 6 back to List of PLC blocks Group Time functions...

Page 517: ...creased by 1 every PLC cycle The timer initial value is adjustable by the Reload value input The timer is automatically reloaded with the initial value when it reaches zero or it can be reloaded at any other time using the reload input The timer remains at reload value until the reload input is deactivated The timer output is inverted always when the timer is reloaded Image 8 67 Principle of timer...

Page 518: ...ut to logical 0 The output remains in logical 0 until new rising edge appears on Input when Input reset is deactivated already Outputs Output Type Negation Range Function Output Binary No 0 1 Output signal Description This block can work in two modes of operation Delay mode the rising edge at the output is generated with delay of input time up when a rising edge at the input is detected The fallin...

Page 519: ...on of Delay block Note If Input time up or Input time down value is 0 this input is internally set to zero Note Input time up and Input time down values can be constants or values from controller Note Use Pulse on edge option to choose between delay and pulse mode 6 back to List of PLC blocks ...

Page 520: ...ng to selected group of bits Output 2 Binary Yes 0 1 Bit 1 5 9 13 17 21 25 29 according to selected group of bits Output 3 Binary Yes 0 1 Bit 2 6 10 14 18 22 26 30 according to selected group of bits Output 4 Binary Yes 0 1 Bit 3 7 11 15 19 23 27 31 according to selected group of bits Description The block converts the input analog value to binary form and provides selected bits as binary outputs ...

Page 521: ...ms For more information see Alarm management on page 128 8 2 1 Alarm levels in the controller 8 2 2 Alarms level 1 521 8 2 3 Alarms level 2 552 8 2 2 Alarms level 1 What alarms level 1 are The level 1 alarm indicates that a value or parameter is out of normal limits but has still not reached critical level ...

Page 522: ...larm SMS 1 Fail 531 Wrn Alarm SMS 2 Fail 531 Wrn Alarm SMS 3 Fail 531 Wrn Alarm SMS 4 Fail 531 Wrn SNMP TRAP 1 Fail 532 Wrn SNMP TRAP 2 Fail 532 Wrn ECUDiagBlocked 532 Wrn ECU Communication Fail 532 Wrn PasswEnterBlock 533 Wrn ECU Yellow Lamp 533 Wrn ECU Red Lamp 533 Wrn ECU Wait To Start 533 Wrn ATT DPF Lamp 534 Wrn ATT HEST Lamp 534 Wrn ATT SCR Error Lamp 534 Wrn ATT DEF Level Lamp 534 Wrn ATT I...

Page 523: ...sg 6 546 Wrn Al Hist msg 7 546 Wrn Al Hist msg 8 546 Wrn Al Hist msg 9 547 Wrn Al Hist msg 10 547 Wrn Al Hist msg 11 547 Wrn Al Hist msg 12 547 Wrn Al Hist msg 13 547 Wrn Al Hist msg 14 548 Wrn Al Hist msg 15 548 Wrn Al Hist msg 16 548 ALI Start Blocking 548 ALI Gen Ph L1 Inverted 548 ALI Gen Ph L2 Inverted 549 ALI Gen Ph L3 Inverted 549 ALI Gen Ph Rotation Opposite 549 ALI Mains Ph L1 Inverted 54...

Page 524: ...Alarm Type WRN Alarmlist message Module Slot 3 Alarm evaluated All the time Related applications AMF MRS Description This alarm is issued if controller will not be able to communicate with preconfigured module 3 Wrn Module Slot 3 6 back to List of alarms level 1 Alarm Type WRN Alarmlist message Module slotA fake module Alarm evaluated All the time Related applications AMF MRS Description This alar...

Page 525: ...ed All the time Related applications AMF MRS Description This alarm indicates that two same communication modules are inserted in slots and one of them will be inactive Wrn Module slotA unattended 6 back to List of alarms level 1 Alarm Type WRN Alarmlist message Module slotB unattended Alarm evaluated All the time Related applications AMF MRS Description This alarm indicates that two same communic...

Page 526: ...e is unconfigured and has to be configured for proper function Wrn Module slotA unexpected 6 back to List of alarms level 1 Alarm Type WRN Alarmlist message Module slotB unexpected Alarm evaluated All the time Related applications AMF MRS Description This alarm indicates that in slot is inserted different module than which is configured or the module is unconfigured and has to be configured for pr...

Page 527: ...rms level 1 Alarm Type WRN Alarmlist message EM B configuration mistake Alarm evaluated All the time Related applications AMF MRS Description This alarm indicates that there is a problem with configuration of binary input or output of module in slot Wrn EM B configuration mistake 6 back to List of alarms level 1 Alarm Type WRN Alarmlist message EM A insufficient Alarm evaluated All the time Relate...

Page 528: ... module is configured in slot Wrn EM B missing or damaged 6 back to List of alarms level 1 Alarm Type WRN Alarmlist message Event Email 1 Fail Alarm evaluated All the time Related applications AMF MRS Description The alarm indicates that there was a request to send an event email to email address which is adjusted in setpoint Email Address 1 page 366 and email wasn t send Wrn Event Email 1 Fail 6 ...

Page 529: ...ated All the time Related applications AMF MRS Description The alarm indicates that there was a request to send an event SMS to telephone number which is adjusted in setpoint Telephone Number 1 page 350 and SMS wasn t send Wrn Event SMS 1 Fail 6 back to List of alarms level 1 Alarm Type WRN Alarmlist message Event SMS 2 Fail Alarm evaluated All the time Related applications AMF MRS Description The...

Page 530: ... address which is adjusted in setpoint Email Address 1 page 366 and email wasn t send Wrn Alarm Email 1 Fail 6 back to List of alarms level 1 Alarm Type WRN Alarmlist message Alarm Email 2 Fail Alarm evaluated All the time Related applications AMF MRS Description The alarm indicates that there was a request to send an alarm email to email address which is adjusted in setpoint Email Address 2 page ...

Page 531: ... page 350 and SMS wasn t sent Wrn Alarm SMS 1 Fail 6 back to List of alarms level 1 Alarm Type WRN Alarmlist message Alarm SMS 2 Fail Alarm evaluated All the time Related applications AMF MRS Description The alarm indicates that there was a request to send an alarm SMS to telephone number which is adjusted in setpoint Telephone Number 2 page 350 and SMS wasn t sent Wrn Alarm SMS 2 Fail 6 back to L...

Page 532: ...RAP will not be able to reach server or in case there is no reply for the server Wrn SNMP TRAP 2 Fail 6 back to List of alarms level 1 Alarm Type ALI Alarmlist message ECUDiagBlocked Alarm evaluated All the time Related applications AMF MRS Description LBO ALARM PAGE 469 is not activated after deactivation of lamp alarm automatically disappears Wrn ECUDiagBlocked 6 back to List of alarms level 1 A...

Page 533: ... disappears Wrn ECU Yellow Lamp 6 back to List of alarms level 1 Alarm Type AHI Alarmlist message Wrn ECU Red Lamp Alarm evaluated All the time Related applications AMF MRS Description This alarm is activated when ECU send information that ECU Red lamp is activated LBO ALARM PAGE 469 is not activated after deactivation of lamp alarm automatically disappears Note This lamp can be ignored during pre...

Page 534: ...y disappears Wrn ATT HEST Lamp 6 back to List of alarms level 1 Alarm Type AHI Alarmlist message Wrn ATT SCR Error Lamp Alarm evaluated All the time Related applications AMF MRS Description This alarm is activated when ECU send information that ECU ATT SCR Error Lamp is activated LBO ALARM PAGE 469 is not activated after deactivation of lamp alarm automatically disappears Wrn ATT SCR Error Lamp 6 ...

Page 535: ...st ATT Force Regen Active Alarm evaluated All the time Related applications AMF MRS Description This message is written in the history when LBI ATT FORCE REGEN PAGE 441 is active LBO ALARM PAGE 469 is not activated after deactivation of lamp alarm automatically disappears Hst ATT Force Regen Active 6 back to List of alarms level 1 Alarm Type AHI Alarmlist message Hst ATT Inhib Regen Active Alarm e...

Page 536: ...rmlist message All the time Alarm evaluated Wrn Coolant Temp Low Related applications AMF MRS Description Warning alarm for Coolant Temp Low user protection Wrn Coolant Temp Low 6 back to List of alarms level 1 Alarm Type WRN Alarmlist message All the time Alarm evaluated Wrn Fuel Level Related applications AMF MRS Description Warning alarm for Coolant Temp Low user protection Wrn Fuel Level 6 bac...

Page 537: ...d Related applications AMF MRS Description This alarm occurs if the Gen set shall be stopped but some symptom indicates that it is not stopped The period when the Gen set shall be stopped begins after the FUEL SOLENOID PAGE 477 has been switched off and time delay Stop Time page 240 has elapsed and lasts for the entire time the FUEL SOLENOID PAGE 477 or STARTER PAGE 501 are off Image 8 72 Stop Fai...

Page 538: ...urs Alarm evaluated All the time Related applications AMF MRS Description The alarm is active when the value Maintenance Timer 2 RunHours page 413 reaches 0 The value is adjustable by setpoint Maintenance Timer 2 RunHours page 257 unit is hours h and it counts down in hours while engine is running Setpoint Maintenance Timer 2 Protection page 258 has to be set to Warning Wrn Maintenance Timer 2 Run...

Page 539: ...to List of alarms level 1 Alarm Type WRN Alarmlist message Wrn MCB Fail Alarm evaluated All the time Related applications AMF MRS Description This alarm will occur when the MCB FEEDBACK PAGE 453 input does not match the expected position given by the MCB CLOSE OPEN PAGE 490 output It stays active until the mismatch between the output and feedback disappears If there was no command issued by the co...

Page 540: ...tpoints are related to it Generator Overvoltage Wrn page 264 Generator Voltage Delay page 266 Wrn Generator L2 Overvoltage 6 back to List of alarms level 1 Alarm Type WRN Alarmlist message Generator L3 Voltage Alarm evaluated Generator excited only Related applications AMF MRS Description This alarm evaluates the generator phase voltage in phase 3 The following setpoints are related to it Generato...

Page 541: ...rator phase to phase voltage between phases 3 and 1 The following setpoints are related to it Generator Overvoltage Wrn page 264 Generator Voltage Delay page 266 Wrn Generator L3L1 Overvoltage 6 back to List of alarms level 1 Alarm Type WRN Alarmlist message Generator L1 Voltage Alarm evaluated Generator excited only Related applications AMF MRS Description This alarm evaluates the generator phase...

Page 542: ...MF MRS Description This alarm evaluates the generator phase to phase voltage between phases 1 and 2 The following setpoints are related to it Generator Undervoltage Wrn page 265 Generator Voltage Delay page 266 Wrn Generator L1L2 Undervoltage 6 back to List of alarms level 1 Alarm Type WRN Alarmlist message Generator L2L3 Voltage Alarm evaluated Generator excited only Related applications AMF MRS ...

Page 543: ... Alarm Type WRN Alarmlist message Generator Frequency Alarm evaluated Generator excited only Related applications AMF MRS Description This alarm evaluates the generator underfrequency in the phase L1 The following setpoints are related to it Generator Underfrequency Wrn page 267 Generator Frequency Delay page 268 Wrn Generator Uderfrequency 6 back to List of alarms level 1 Alarm Type WRN Alarmlist...

Page 544: ...larm Type WRN Alarmlist message Wrn Password reset e mail addr is not set Alarm evaluated All the time Related applications AMF MRS Description This alarm is active when there is no email address set in the controller and simultaneously controller administrator password is not the default password Note When default password is changed the Wrn Password reset e mail addr is not set will be active af...

Page 545: ...otection Active Alarm evaluated All the time Related applications AMF MRS Description This alarm is activated when account break protection detects possible attack and at least one account is blocked according to Account break protection page 172 rules Wrn Brute Force Protection Active 6 back to List of alarms level 1 Alarm Type WRN Alarmlist message Al Hist msg 1 Alarm evaluated All the time Rela...

Page 546: ...luated All the time Related applications AMF MRS Description This alarm is issued when history event 5 will trigger Wrn Al Hist msg 5 6 back to List of alarms level 1 Alarm Type WRN Alarmlist message Al Hist msg 6 Alarm evaluated All the time Related applications AMF MRS Description This alarm is issued when history event 6 will trigger Wrn Al Hist msg 6 6 back to List of alarms level 1 Alarm Type...

Page 547: ... 10 will trigger Wrn Al Hist msg 10 6 back to List of alarms level 1 Alarm Type WRN Alarmlist message Al Hist msg 11 Alarm evaluated All the time Related applications AMF MRS Description This alarm is issued when history event 11 will trigger Wrn Al Hist msg 11 6 back to List of alarms level 1 Alarm Type WRN Alarmlist message Al Hist msg 12 Alarm evaluated All the time Related applications AMF MRS...

Page 548: ...list message Al Hist msg 16 Alarm evaluated All the time Related applications AMF MRS Description This alarm is issued when history event 16 will trigger Wrn Al Hist msg 16 6 back to List of alarms level 1 Alarm Type ALI Alarmlist message ALI Gen Ph L3 Inverted Alarm evaluated All the time Related applications AMF MRS Description This alarm is active if LBI START BLOCKING PAGE 460 is closed before...

Page 549: ...e ALI Gen Ph Rotation Opposite Alarm evaluated All the time Related applications AMF MRS Description This alarm is issued if generator phases are wired in wrong order ALI Gen Ph Rotation Opposite 6 back to List of alarms level 1 Alarm Type ALI Alarmlist message ALI Mains Ph L1 Inverted Alarm evaluated All the time Related applications AMF MRS Description This alarm is issued if mains phase L1 is i...

Page 550: ...st phase voltage at any given time The following setpoints are related to it Mains Voltage Unbalance page 276 adjusts the maximum allowed difference between the highest and lowest phase voltage at any given time Mains Voltage Unbalance Delay page 277 adjusts the alarm delay Mains Voltage Unbalance ph n 6 back to List of alarms level 1 Alarm Type MP Alarmlist message Mains Voltage Unbalance ph ph A...

Page 551: ...s Frequency Delay page 281 Mains Underfrequency 6 back to List of alarms level 1 Alarm Type WRN Alarmlist message Wrn Mains Voltage Detected Alarm evaluated Gen set is running Related applications AMF MRS Description This alarm occurs when setpoint Default Application Select page 217 is adjusted to MRS and voltage is detected on mains Wrn Mains Voltage Detected 6 back to List of alarms level 1 Ala...

Page 552: ...t Geo Fencing page 324 Fence 1 Protection page 326 Fence 1 Radius page 327 Wrn Fence 1 Alarm 6 back to List of alarms level 1 Alarm Type WRN Alarmlist message Wrn Fence 2 Alarm Alarm evaluated All the time Related applications AMF MRS Description This alarm evaluates the GPS position of Gen set The following setpoint are related to it Geo Fencing page 324 Fence 2 Protection page 328 Fence 2 Radius...

Page 553: ...ge 562 Sd Generator L2L3 Overvoltage 563 Sd Generator L3L1 Overvoltage 563 BOC Generator L1 Undervoltage 563 BOC Generator L2 Undervoltage 563 BOC Generator L3 Undervoltage 564 BOC Generator L1L2 Undervoltage 564 BOC Generator L2L3 Undervoltage 564 BOC Generator L3L1 Undervoltage 564 Sd Oil Pressure 565 BOC Coolant Temp 565 BOC Coolant Temp 565 BOC Generator L1 Undervoltage 565 BOC Generator L2 Un...

Page 554: ... Timer 2 RunHours 573 BOC Maintenance Timer 2 Interval 574 BOC Maintenance Timer 3 RunHours 574 BOC Maintenance Timer 3 Interval 574 Sd Fence 1 Alarm 575 BOC Fence 1 Alarm 575 Sd Fence 2 Alarm 575 BOC Fence 2 Alarm 575 Sd Parallel Work 576 6 back to Alarms InteliLite4 AMF20 Global Guide 554 ...

Page 555: ... Alarm Type SD Alarmlist message Module Slot 3 Alarm evaluated All the time Related applications AMF MRS Description This alarm is issued if controller will not be able to communicate with preconfigured module 3 Sd Module Slot 3 6 back to List of alarms level 2 Alarm Type SD Alarmlist message Module slotA fake module Alarm evaluated All the time Related applications AMF MRS Description This alarm ...

Page 556: ...ed All the time Related applications AMF MRS Description This alarm indicates that two same communication modules are inserted in slots and one of them will be inactive Sd Module slotA unattended 6 back to List of alarms level 2 Alarm Type SD Alarmlist message Module slotB unattended Alarm evaluated All the time Related applications AMF MRS Description This alarm indicates that two same communicat...

Page 557: ...le is unconfigured and has to be configured for proper function Sd Module slotA unexpected 6 back to List of alarms level 2 Alarm Type SD Alarmlist message Module slotB unexpected Alarm evaluated All the time Related applications AMF MRS Description This alarm indicates that in slot is inserted different module than which is configured or the module is unconfigured and has to be configured for pro...

Page 558: ...arms level 2 Alarm Type SD Alarmlist message EM B configuration mistake Alarm evaluated All the time Related applications AMF MRS Description This alarm indicates that there is a problem with configuration of binary input or output of module in slot Sd EM B configuration mistake 6 back to List of alarms level 2 Alarm Type SD Alarmlist message EM A insufficient Alarm evaluated All the time Related ...

Page 559: ...Sd ECU Communication Fail Alarm evaluated With configured LBO ECU POWER RELAY PAGE 474 only when this LBO is active Without configured LBO ECU POWER RELAY PAGE 474 all the time Related applications AMF MRS Description This alarm occurs when an ECU is configured but the communication with the ECU is not established or has dropped out Sd ECU Communication Fail 6 back to List of alarms level 2 Alarm ...

Page 560: ...lar to the red battery alarm indicator on a vehicle dashboard The setpoint has to be in Charge Fail or Enabled position to enable this alarm Sd Charging Alternator Fail 6 back to List of alarms level 2 Alarm Type SD Alarmlist message Sd Overspeed Alarm evaluated All the time Related applications AMF MRS Description This alarm occurs immediately when the engine speed has exceeded the limit The beha...

Page 561: ...when starter motor is energized that it causes controller reset Sd Battery Flat 6 back to List of alarms level 2 Alarm Type SD Alarmlist message Sd Start Fail Alarm evaluated When the gen set is being started Related applications AMF MRS Description This alarm will be issued after all attempts to start the gen set have run out but the Gen set did not start The following setpoints are related to th...

Page 562: ...AMF MRS Description This alarm evaluates the generator phase voltage in phase 2 The following setpoints are related to it Generator Overvoltage Sd page 264 Generator Voltage Delay page 266 Sd Generator L2 Overvoltage 6 back to List of alarms level 2 Alarm Type SD Alarmlist message Sd Generator L3 Voltage Alarm evaluated Generator excited only Related applications AMF MRS Description This alarm eva...

Page 563: ...e Alarm evaluated Generator excited only Related applications AMF MRS Description This alarm evaluates the generator phase to phase voltage between phases 3 and 1 The following setpoints are related to it Generator Overvoltage Sd page 264 Generator Voltage Delay page 266 Sd Generator L3L1 Overvoltage 6 back to List of alarms level 2 Alarm Type BOC Alarmlist message Sd Generator L1 Voltage Alarm ev...

Page 564: ...level 2 Alarm Type BOC Alarmlist message Sd Generator L1L2 Voltage Alarm evaluated Generator excited only Related applications AMF MRS Description This alarm evaluates the generator phase to phase voltage between phases 1 and 2 The following setpoints are related to it Generator Undervoltage BOC page 265 Generator Voltage Delay page 266 BOC Generator L1L2 Undervoltage 6 back to List of alarms leve...

Page 565: ...2 Alarm Type BOC Alarmlist message BOC Coolant Temp Alarm evaluated All the time Related applications AMF MRS Description Breaker Open and Stop alarm for Coolant Temp user protection BOC Coolant Temp 6 back to List of alarms level 2 Alarm Type BOC Alarmlist message BOC Coolant Temp Alarm evaluated All the time Related applications AMF MRS Description Breaker Open and Stop alarm for Fuel Level user...

Page 566: ...lated to it Generator Undervoltage BOC page 265 Generator Voltage Delay page 266 BOC Generator L3 Undervoltage 6 back to List of alarms level 2 Alarm Type BOC Alarmlist message BOC Generator L1L2 Voltage Alarm evaluated Generator excited only Related applications AMF MRS Description This alarm evaluates the generator phase to phase voltage between phases 1 and 2 The following setpoints are related...

Page 567: ...ighest and lowest phase to phase voltage at any given time The following setpoints are related to it Voltage Unbalance BOC page 266 adjusts the maximum allowed difference between the highest and lowest phase voltage at any given time Voltage Unbalance BOC Delay page 266 adjusts the alarm delay BOC Gen Voltage Unbalance Ph Ph 6 back to List of alarms level 2 Alarm Type BOC Alarmlist message BOC Gen...

Page 568: ...in the phase L1 The following setpoints are related to it Generator Underfrequency BOC page 268 Generator Voltage Delay page 266 BOC Generator Underfrequency 6 back to List of alarms level 2 Alarm Type MP Alarmlist message No Alarm evaluated All the time Related applications AMF MRS Description This alarm evaluates the Mains phase voltage in phases The following setpoints are related to it Mains O...

Page 569: ...in phases The following setpoints are related to it Mains Undervoltage page 274 Mains Undervoltage Delay page 276 Mains L2 Undervoltage 6 back to List of alarms level 2 Alarm Type MP Alarmlist message No Alarm evaluated All the time Related applications AMF MRS Description This alarm evaluates the Mains phase voltage in phases The following setpoints are related to it Mains Overvoltage page 272 Ma...

Page 570: ...ains phase voltage in phases L1 and L2 The following setpoints are related to it Mains Undervoltage page 274 Mains Undervoltage Delay page 276 Mains L1L2 Undervoltage 6 back to List of alarms level 2 Alarm Type MP Alarmlist message No Alarm evaluated All the time Related applications AMF MRS Description This alarm evaluates the Mains phase voltage in phases L2 and L3 The following setpoints are re...

Page 571: ...All the time Related applications AMF MRS Description This alarm evaluates the Mains phase voltage in phases L3 and L1 The following setpoints are related to it Mains Undervoltage page 274 Mains Undervoltage Delay page 276 Mains L3L1 Undervoltage 6 back to List of alarms level 2 Alarm Type MP Alarmlist message No Alarm evaluated All the time Related applications AMF MRS Description This alarm eval...

Page 572: ...lay page 263 adjusts the alarm delay BOC Current Unbalance 6 back to List of alarms level 2 Alarm Type BOC Alarmlist message BOC Overload Alarm evaluated All the time Related applications AMF MRS Description The alarm is issued when the gen set power is over the limit for time period longer than the delay The behavior of the overload alarm is adjusted by the following setpoints Overload BOC page 2...

Page 573: ...RS Description The alarm is active when the value Maintenance Timer 1 RunHours page 412 reaches 0 The value is adjustable by setpoint Maintenance Timer 1 RunHours page 256 unit is hours h and it counts down while engine is running Setpoint Maintenance Timer 1 Protection page 257 has to be set to BOC BOC Maintenance Timer 1 RunHours 6 back to List of alarms level 2 Alarm Type BOC Alarmlist message ...

Page 574: ...ning BOC Maintenance Timer 2 Interval 6 back to List of alarms level 2 Alarm Type BOC Alarmlist message BOC Maintenance Timer 3 RunHours Alarm evaluated All the time Related applications AMF MRS Description The alarm is active when the value Maintenance Timer 3 RunHours page 413 reaches 0 The value is adjustable by setpoint Maintenance Timer 3 RunHours page 259 unit is hours h and it counts down w...

Page 575: ...elated applications AMF MRS Description This alarm evaluates the GPS position of Gen set The following setpoint are related to it Geo Fencing page 324 Fence 1 Protection page 326 Fence 1 Radius page 327 BOC Fence 1 Alarm 6 back to List of alarms level 2 Alarm Type Shutdown Alarmlist message Sd Fence 2 Alarm Alarm evaluated All the time Related applications AMF MRS Description This alarm evaluates ...

Page 576: ...6 back to List of alarms level 2 8 3 Modules 8 3 1 Plug in modules The available communication plug in modules are CM RS232 485 communication module for connection via RS232 or RS485 line CM2 4G GPS communication module for connection via 4G CM3 Ethernet communication module for internet connection via Ethernet The available extension plug in modules are EM BIO8 EFCP extension module with 8 binary...

Page 577: ...on This is required for computer or Modbus connection The CM RS232 485 is a dual port module with RS232 and RS485 interfaces at independent COM channels The RS232 is connected to COM1 and RS485 to COM2 Image 8 73 CM RS232 485 interface IMPORTANT Any manipulation with plug in module shall be done with disconnected power supply to controller Image 8 74 Pinout of RS232 line ...

Page 578: ...Power consumption 40 mA 8 VDC 26 mA 12 VDC 14 mA 24 VDC 10 mA 36 VDC Isolation Galvanic separation Technical data Firmware upgrade Download the newest FW of module from ComAp website in form of PSI file or installation package Install package to computer or open PSI to install it into InteliConfig Plug the module into the controller and power the controller on Open a connection with controller via...

Page 579: ...et 10 100 Mbit interface in RJ45 connector It provides an interface for connecting a PC through ethernet internet network for sending active e mails and for integration of the controller into a building management MODBUS TCP and SNMP protocols Image 8 77 CM3 Ethernet interface IMPORTANT Any manipulation with plug in module shall be done with disconnected power supply to controller Use an Ethernet ...

Page 580: ...dule can not obtain IP address from DHCP 10 Hz Green firmware is currently being programmed Red no firmware present in the module Status LED Firmware upgrade Download the newest FW of module from ComAp website in form of PSI file or installation package Install package to computer or open PSI to install it into InteliConfig Plug the module into the controller and power the controller on Open a con...

Page 581: ...ction technology to make internet access as simple as possible CM2 4G GPS module also works like GPS locator Geo fencing function can be used with this module 4G module types If the anthenna is CELLULAR only and has 1 cable OT1A4GXXMCX it is connected to the 4G MAIN connector If the anthenna is CELLULAR only and has 2 cables cables are connected to the 4G MAIN or 4G DIV connectors does not matter ...

Page 582: ...SS Supported networks and frequency bands 2G GSM GPRS EDGE Quad band 850 900 1800 1900 MHz 3G UMTS HSPA Seven band 800 BdXIX 850 BdV 900 BdVIII AWS BdIV 1800 BdIX 1900 BdII 2100MHz BdI 4G LTE Twelve band 700 Bd12 MFBI Bd17 Bd28 800 Bd18 Bd19 Bd20 850 Bd5 900 Bd8 AWS Bd4 1800 Bd3 1900 Bd2 2100 Bd1 2600MHz Bd7 Antenna interface 2x SMA female Main and Diversity Cellular SIM card settings SIM card mus...

Page 583: ... connect an active GPS antenna to the GPS antenna connector Switch off the controller Insert CM2 4G GPS module into controller Power up the controller Activate CM2 4G GPS module by switching the setpoint Internet Connection page 333 to enabled Enter correct Access Point Name this information is provided by Mobile Operator Setpoint can be set on controller s front panel or by InteliConfig Wait for ...

Page 584: ...sible reasons Setpoint Access Point Name is not correctly set wrong text E08 Modem configuration error E09 It is not possible to get signal strength E10 It is not possible to get operator name E11 Loss of registration into cellular network was detected E12 Data error E13 Data error E14 Modem was restarted E SMS send It is not possible to send SMS Possible reasons Wrong number SIM doesn t support S...

Page 585: ...rocess may be performed via any kind of connection including connection via the same module in which the firmware is to be updated The connection is re established again automatically when the update process is finished Extension modules EM BIO8 EFCP 585 EM BIO8 EFCP EM BIO8 EFCP is optional plug in card Through this card the controller can accommodate one AC current CT measuring input 1A or 5A in...

Page 586: ...M BIO8 EFCP Image 8 84 EM BIO8 EFCP wiring Note Current inputs are supported only in MRS 16 and AMF 25 and AMF9 controllers EM BIO8 EFCP technical data Power supply range 8 36 VDC Power consumption 40 mA 8 VDC 27 mA 12 VDC 22 mA 24 VDC 19 mA 36 VDC Power supply ...

Page 587: ...lug the module into the controller and power the controller on Open a connection with controller via InteliConfig Go the menu Tools Firmware upgrade select the Plug in modules tab and select the appropriate firmware you want to program into the module in InteliConfig Press the OK button to start upgrade of firmware The firmware update process may be performed via any kind of connection including c...

Page 588: ...thout analog outputs Analog outputs of these CAN modules are supported only in slot 1 and 2 It is possible to add up to 80 binary inputs or up to 68 binary outputs or up to 32 analog inputs on CAN modules Extension modules Inteli AIN8 588 Inteli IO8 8 594 IGS PTM 601 Inteli AIN8TC 607 Inteli AIO9 1 611 IGL RA15 616 Inteli AIN8 Inteli AIN8 module is an extension module equipped with analog inputs I...

Page 589: ...InteliLite4 AMF20 Global Guide 589 Image 8 85 Inteli AIN8 Image 8 86 Inteli AIN8 dimensions Note All dimensions are in mm ...

Page 590: ...tive in position ON switch both switches Note Impulse input is not supported Analog inputs 8 channels can be configured as resistor three wire input current input voltage input All inputs can be configured to any logical function or protection IMPORTANT Impulse input is not supported in controller Supported sensors Sensors User curves NI100 F fix 0 5 V PT100 C fix NI1000 F fix 0 10 V PT1000 C fix ...

Page 591: ...als from the unit 2 Remove the top cover of module 3 Put the TEST jumper on pins 4 Connect the unit with PC via RS232 null modem cable and AT Link conv 5 Connect power supply of the module status LED lights continuously 6 Launch FlashPgr exe PC software version 4 2 or higher 7 In FlashPrg program choose card Inteli AIN8 and load FW for the module 8 Set the proper COM port connected with the unit a...

Page 592: ...ded LED indication LED status Description Dark Fw in module does not work correctly Flashing Module does not communicate with controller in case non zero CAN address Lights Power supply is in the range and the communication between Inteli AIN8 and controller works properly Or power supply is in range and zero CAN address is set in case zero CAN address module doesn t communicate with the controlle...

Page 593: ...Lite4 AMF20 Global Guide 593 Resistance sensor 2 wires Note Ranges Pt100 Pt1000 Ni100 Ni1000 0 2400 Ω 0 10 kΩ Current sensor active Note Ranges 20 mA 4 20 mA Current sensor passive Note Ranges 0 20 mA 4 20 mA ...

Page 594: ...istive Range 0 10 kΩ Accuracy 0 5 of actual value 2 Ω Analog inputs Inteli IO8 8 Inteli IO8 8 module is an extension module equipped with binary inputs binary outputs and analog outputs Inteli IO8 8 is the name of the module but it is possible to configure the module by internal switch to two configurations Inteli IO8 8 8 binary inputs 8 binary outputs and 2 analog outputs Inteli IO16 0 16 binary ...

Page 595: ...InteliLite4 AMF20 Global Guide 595 Image 8 87 Inteli IO8 8 Image 8 88 Inteli IO8 8 dimensions Note All dimensions are in mm ...

Page 596: ...inary output indication CAN LED Indication transmitted or received data Status LED indication of correct function CAN terminator Terminating CAN resistor active in position ON switch both switches Inputs and outputs Binary inputs 8 channels can be configured as pull up pull down All 8 inputs are configured to one type together All inputs can be configured to any logical function or protection Bina...

Page 597: ...larm are issued type of the alarm is set by Protection upon module failure No protection Warning Shutdown This function is designed for short circuit or other failure which causes change of set state of binary output CAN address In Inteli IO8 8 mode CAN address for binary inputs is determined by DIP switch A CAN address for binary output and analog outputs is determined by DIP switch B In Inteli I...

Page 598: ... is correct Module has power supply no CAN bus connection status LED lights continuously 10 After successful programming disconnect AT Link conv remove TEST jumper and disconnect power supply 11 Connect power supply again status LED should blink 12 Module FW is upgraded LED indication Binary input Each binary input has an LED which indicates input signal LED is shining when input signal is set and...

Page 599: ... following diagrams show the correct connection of inputs and outputs Binary inputs pull up There are two options of wiring On upper picture you can see example of binary input is connected between BIN2 and COM COM is connected internally to the GND dashed line In lower picture is an example of wiring between BIN2 and GND Both ways are correct Binary inputs pull down There are two options of wirin...

Page 600: ...uts low side When low side setting of outputs is chosen binary output must be connected to the positive potential of power supply directly Negative potential is connected internally dashed line Analog outputs Note Limit of analog ground AGND is 100 mA IMPORTANT Terminator for analog output has special analog ground AGND which must not be connected to the GND Technical data Power supply 8 to 36 V D...

Page 601: ...og outputs Number of channels 8 for Inteli IO8 8 16 for Inteli IO16 0 Input resistance 4400 Ω Input range 0 to 36 V DC Switching voltage level for open contact indication 0 to 2 V DC Max voltage level for close contact indication 6 to 36 V DC Binary inputs Number of channels 8 for Inteli IO8 8 0 for Inteli IO16 0 Max current 500 mA Max switching voltage 36 V DC Binary outputs IGS PTM IGS PTM modul...

Page 602: ...InteliLite4 AMF20 Global Guide 602 Image 8 89 IGS PTM Image 8 90 IGS PTM dimensions ...

Page 603: ...wer Power supply Analog inputs Analog inputs can be configured for Resistance measurement Current measurement Voltage measurement The type of analog input is configured via jumpers RUI located on lower PCB RUI Analog input configuration 1 2 Resistance measuring 2 3 Current measuring no jumper Voltage measuring Supported sensors Sensors PT100 C fix User curves NI100 C fix 0 100 mV PT100 F fix 0 240...

Page 604: ...necessary to close jumper BOOT RESET jumper is used to reset the device Close jumper to reset the device For programming FlashProg PC tool should be used LED indication Binary input Each binary input has an LED which indicates input signal LED is shining when input signal is set and LED is dark while input signal has other state Binary output Each binary output has an LED which indicates output si...

Page 605: ...nary outputs Resistance sensor Note Range 0 2400 Ω IMPORTANT Physical analog input range is 0 250 Ω In sensor configuration in PC tool it is necessary to chose 0 2400 Ω sensor HW type to ensure proper function of analog input Voltage sensor Note Range 0 100 mV ...

Page 606: ...o 20 mA 0 33 mA Technical data Power supply 8 to 36 V DC Current consumption 100 mA at 24V 500 mA Interface to controller CAN1 Protection IP20 Storage temperature 40 C to 80 C Operating temperature 30 C to 70 C Dimensions WxHxD 95 96 43 mm 3 7 3 8 1 7 General data Number of channels 8 Voltage Range 0 100 mV Accuracy 1 5 1 mV out of measured value Current Range 0 20 mA Accuracy 2 5 0 5 Ω out of mea...

Page 607: ...er of channels 8 Voltage Range 0 100 mV Accuracy 1 5 1 mV out of measured value Current Range 0 20 mA Accuracy 2 5 0 5 Ω out of measured value Resistive Range 0 250 Ω Accuracy 1 2 Ω out of measured value Binary outputs Inteli AIN8TC Inteli AIN8TC module is an extension module equipped with 8 analog inputs dedicated for thermocouple sensors only The detection of communication speed is indicated by ...

Page 608: ...InteliLite4 AMF20 Global Guide 608 Image 8 91 Inteli AIN8TC Image 8 92 Inteli AIN8TC dimensions ...

Page 609: ... indication of correct function CAN terminator Terminating CAN resistor active in position ON TEST jumper Upgrade of SW AT LINK Connector for AT LINK Analog inputs 8 channels can be configured as thermocouple sensors only Supported sensors Sensors Thermocpl J C fix Thermocpl K C fix Thermocpl L C fix Thermocpl J F fix Thermocpl K F fix Thermocpl L F fix Thermocpl nc J C fix ...

Page 610: ...AT link TTL For programming it is necessary to close jumper TEST For programming FlashProg PC tool version 4 2 or higher must be used LED indication LED status Description Dark FW in module does not work correctly Flashing Module does not communicate with controller in case non zero CAN address Fast flashing Detection of CAN communication speed Lights Power supply is in the range and the communica...

Page 611: ...puts are not galvanic separated between channels Power supply 8 to 36 V DC Protection IP20 Current consumption 35 mA at 24 V 100 mA at 8 V Storage temperature 40 C to 80 C Operating temperature 30 C to 70 C Heat radiation 2 W Thermocouples which are galvanically separated and galvanically non separated are supported Inteli AIO9 1 Inteli AIO9 1 module is an extension module equipped with analog inp...

Page 612: ...InteliLite4 AMF20 Global Guide 612 Image 8 93 Inteli AIO9 1 Image 8 94 Inteli AIO9 1 dimensions ...

Page 613: ...ator Terminating CAN resistor active in position ON TEST jumper Upgrade of SW AT LINK Connector for AT LINK Upgrade of SW Analog inputs 4 channels AIN1 AIN4 can be configured as Sensor 65V determined for measurement of battery voltage 4 channels AIN5 AIN8 can be configured as Thermocouples type J K or L in C or F Sensor 75mV DC for connecting current shunts 1 channel AIN9 can be configured as RTD ...

Page 614: ... C fix Thermocpl L C fix Thermocpl nc J C fix Thermocpl nc K C fix Thermocpl nc L C fix Thermocpl nc J F fix Thermocpl nc K F fix Thermocpl nc L F fix Address and DIP switch setting Address configuration DIP switch determinates CAN address for analog inputs and outputs Programming Firmware Firmware upgrade is available via AT link TTL For programming it is necessary to close jumper TEST and switch...

Page 615: ...ress is set in case zero CAN address module doesn t communicate with the controller Wiring The following diagrams show the correct connection of sensors Measuring resistance AIN9 2 wire measurement Ranges Pt1000 Ni1000 0 2400 Ω Analog input 9 is determined for measuring resistance only Technical data Dimension W H D 110 110 46 mm 4 3 4 3 1 8 Weight 248 grams Interface to controller CAN1 galvanic s...

Page 616: ...ted from power supply Analog output I 0 20mA 500Rmax 1 of actual value 200 uA U 0 10V 0 5 of actual value 50 mV PWM 5 V 200 Hz 2 4kHz 15 mA max Galvanic separated from power supply Galvanic separation CAN bus is galvanic separated from the measurement and power supply Power supply 8 to 36 V DC Protection IP20 Current consumption 150 mA at 24 V 400 mA at 8 V Storage temperature 40 C to 80 C Operati...

Page 617: ... Address Jumper A Jumper B 1 OPEN OPEN 5 6 CLOSED OPEN Customer defined CLOSED CLOSED SW changing of CAN1 address is enabled only when both jumpers are closed Any one of these addresses 1 2 or 3 4 or 5 6 or 7 8 can be set via the following steps Switch to programming mode Hold the Horn reset and Lamp test when unit is powering on Status led is yellow ...

Page 618: ...he signals LEDs are handled like binary outputs This means everything that can be configured to binary outputs can be also configured to the LEDs of IGL RA15 LED status Description Lights Configured logical output is active on the controller Dark green LED Configured logical output is not active on the controller Dark yellow or red LED Configured logical output is not active on the controller and ...

Page 619: ...rn can be silenced By pressing horn reset button or It silences automatically after adjusted time Lamp and horn test Pressing and holding lamp test button for less than 2 s executes the basic lamp test All LEDs light up with the configured color If the button is held longer than 2 s an extended test is started Every LED is tested step by step in green color and then in red color The horn is activa...

Page 620: ...e important especially for maximal 200 meters CAN bus length Nominal Velocity of Propagation min 75 max 4 4 ns m Wire crosscut min 0 25 mm 2 Maximal attenuation at 1 MHz 2 dB 100 m Recommended Industrial Automation Process Control Cables BELDEN www belden com 3082A DeviceBus for Allen Bradley DeviceNet 3083A DeviceBus for Allen Bradley DeviceNet 3086A DeviceBus for Honeywell SDS 3087A DeviceBus fo...

Reviews: