InteliLite4 AMF20 Global Guide
238
Maximal Stabilization Time
Setpoint group
Engine settings
Related FW
1.3.0
Range [units]
Minimal Stabilization Time (page 237)
.. 3600 [s]
Default value
10 s
Alternative config
NO
Step
1 s
Comm object
8313
Related applications
AMF, MRS
Config level
Advanced
Setpoint visibility
Always
Description
When the Gen-set has been started and the idle timer has elapsed, the generator voltage and frequency
must get within limits within this period of time, otherwise an appropriate shutdown alarm (generator
voltage and/or frequency) is issued.
Note:
When starting the engine, setpoint should be set >300 s.
Image 8.6 Maximal Stabilization Time