ID-Mobile Global Guide
93
Setpoint group
Engine protection
Related FW
2.6.0
Range [units]
0 .. 60 [s]
Default value
40
Step
1 s
Comm object
10129
Related applications
Config level
Standard
Setpoint visibility
Always
Description
Delay for Force block protection activation after Binary input Force block is opened. Protection deactivation
is without delay. Protection is activated/deactivated independent on engine running or not running state.
ForceBlock Del
Setpoint group
Engine protection
Related FW
2.6.0
Range [units]
0 .. 200 [%]
Default value
110
Step
1 % of Nominal RPM
Comm object
8263
Related applications
Config level
Standard
Setpoint visibility
Always
Description
Threshold for engine over speed protection.
Note:
Underspeed alarm is activated when engine is running and actual RPM is below 30 RPM.
Overspeed