4 Putting it into operation
4.1 How to install
To ensure proper function:
Wiring for binary inputs and analog inputs must not be run with power cables.
Analog and binary inputs should use shielded cables, especially when length >3m.
N
OTE
:
During the configuration of controller or setpoints changes is required a password to the controller.
The default password from ComAp is “0”.
4.1.1 Grounding
To ensure proper function:
Use cable min. 2,5mm
2
.
Brass M4x10 screw with star washer securing ring type grounding terminal shall be used.
The negative “-“ terminal of the battery has to be properly grounded.
Switchboard and engine has to be grounded in common spot.
Use cable as short as possible to the grounding point.
4.1.2 Wiring
Tightening torque, allowable wire size and type, for the Field-Wiring Terminals:
Based on terminal type:
PA256:
Specified tightening torque 0.5Nm (4.4 In-lb)
2EDGK:
Specified tightening torque 0.4Nm (3.5 In-lb)
For field type terminals:
Use only diameter 2.0-0.5mm (12-
26AWG) conductor, rated for 75°C minimum.
For Generator Voltage terminals
Use only diameter 2.0-0.5mm (12-
26AWG) conductor, rated for 90°C minimum.
Use copper conductors only.
4.1.3 Power supply
Use minimally power supply cable of 1.5mm
2
.
CAUTION!
Maximum continuous DC power supply voltage is 36VDC.