9 Binary input functions
H
INT
Any Binary input can be configured to any InteliDrive Lite controller terminal or changed to different
function by LiteEdit PC tool. There is adjustable delay when any binary input is configured as
protection.
9.1 Binary inputs InteliDrive Lite - default configuration
BI1
Rem start/stop
BI2
Access lock
BI3
Emergency stop
BI4
Remote OFF
BI5
Sprinkler
BI6
RemControlLock
BI7
Not used
9.2 Configuration of binary inputs
Each binary input can be configured in several ways. The settings can be made in the PC program
LiteEdit, in window Modify. After choosing a concrete binary input, its window appears where the user
can choose if the binary input will be used to protect (option Alarm) or control (option Control).
Binary Alarm configuration items
– see the picture and the table with explanations.
Name
14 characters ASCII string
Contact type
NC
Normally closed
NO
Normally opened
Alarm type
Warning
Shut down
Alarm active
All the time
Engine
running
only