ID-FLX Lite Global Guide
69
Input
Analog input
CU: AI1-AI9
AIO: AI1-AI4
Binary output
Load Switch
Setpoints
Load limit
Load CMP Input = AI1
Load CMP On = 90
Load CMP Off = 80
Engine load limitation with On/Off output
Purpose: Protect the engine against overload by reducing (switching On/Off) the load.
Description: CMPH (Comparator with Hysteresis) detect the RPM decrease below the Down limit, activates
the Binary output Load switch that reduces (slow down feeder) the load. There are expected corresponding
droop characteristics on the engine.
Input
RPM from pickup (or ECU)
Binary output
Load Switch
Setpoints
Load limit
Load CMP Input = RPM
Load CMP On = e.g. 2000
Load CMP Off = e.g. 2200
Speed switch
Purpose: Switch on/off some device depends on RPM level.
Description: Depends on setpoint settings the CMPH (Comparator with Hysteresis) activates/deactivates the
Binary output Load switch that switch off some device when RPM is below adjusted limit.