ID-FLX Lite Global Guide
191
Related FW
2.5.0
Related applications
Comm object
45
Description
If the input is activated the controller behaves like when switched to OFF mode and opens all binary outputs.
There is one exception – Stop solenoid doesn’t activate on this transition.
Detection of running engine and subsequent alarm message "Sd Stop fail" is blocked.
The controller shows “Emerg Man” state and the engine can not be started.
After the input is open again, the controller recovers to previous state and behaves according to the actual
situation.
Function is active in any controller mode.
Emerg. manual
Related FW
2.5.0
Related applications
Comm object
189
Description
Binary input has the same function as Start button on the ID-Lite front panel. It is active in MAN mode only.
StartButton
Related FW
2.5.0
Related applications
Comm object
190
Description
Binary input has the same function as Stop button on the ID-Lite front panel. It is active in MAN mode only.
StopButton
Related FW
2.5.0
Related applications
Comm object
191
Description
Binary input has the same function as Fault reset button on the ID-Lite front panel.
FaultResButton
Related FW
2.5.0
Related applications
Comm object
192
Description
Binary input has the same function as Horn reset button on the ID-Lite front panel.
HornResButton
Summary of Contents for InteliDrive FLX LITE
Page 19: ...ID FLX Lite Global Guide 19 4 3 Terminal diagram and dimension ...
Page 21: ...ID FLX Lite Global Guide 21 Example Default analog output curves ...
Page 22: ...ID FLX Lite Global Guide 22 Example Wiring for Dacon gauges and IL NT AOUT8 ...
Page 44: ...ID FLX Lite Global Guide 44 5 2 Binary inputs and outputs ...
Page 57: ...ID FLX Lite Global Guide 57 5 14 Display screens and pages structure ...
Page 83: ...ID FLX Lite Global Guide 83 7 Communication 6 back to Table of contents ...