ID-FLX Lite Global Guide
155
Setpoint group
Engine protection
Related FW
2.5.0
Range [units]
NORMAL, CLASS C [-]
Default value
NORMAL
-
Step
-
Comm object
13077
Related applications
Description
NORMAL
Protection behaves according to the standard configuration of Wrn/Sd alarm in
LiteEdit AINx configuration screen. Default state.
CLASS C
The protection is type “Running only” and does not depend on Running only tick in
LiteEdit AINx Alarm properties configuration window. Protection (Class C) is
working after AINx Del or sooner when appropriate value increases over AINx Wrn
limit +3 seconds - after engine start. Warning/ShutdDown protection is activated
with fix delay 0.5 s.
Note:
Class C protection is working and corresponding setpoints are visible only when corresponding
AIN is configured in Modify->Alarm properties-> Direction-> Window prot.
AIN7 Eval
Setpoint group
Engine protection
Related FW
2.5.0
Range [units]
0 .. 10000 [U13]
Default value
20
-
Step
1
Comm object
13362
Related applications
Description
Low Warning limit level for AIN7.
AIN7 LowWrn
Setpoint group
Engine protection
Related FW
2.5.0
Range [units]
0 .. 10000 [U13]
Default value
10
-
Step
1
Comm object
13363
Related applications
Description
Low ShutDown limit level for AIN7.
AIN7 LowSd
Summary of Contents for InteliDrive FLX LITE
Page 19: ...ID FLX Lite Global Guide 19 4 3 Terminal diagram and dimension ...
Page 21: ...ID FLX Lite Global Guide 21 Example Default analog output curves ...
Page 22: ...ID FLX Lite Global Guide 22 Example Wiring for Dacon gauges and IL NT AOUT8 ...
Page 44: ...ID FLX Lite Global Guide 44 5 2 Binary inputs and outputs ...
Page 57: ...ID FLX Lite Global Guide 57 5 14 Display screens and pages structure ...
Page 83: ...ID FLX Lite Global Guide 83 7 Communication 6 back to Table of contents ...