ID-FLX Lite Global Guide
151
Setpoint group
Engine protection
Related FW
2.5.0
Range [units]
0 .. 3600 [s]
Default value
10
-
Step
1
Comm object
13358
Related applications
Description
High level protection delay for Wrn and Sd of AIN5.
Note:
Analog input 5 is fully configurable and it is voltage type of input with range 0-40 V.
AIN5 HighDel
Setpoint group
Engine protection
Related FW
2.5.0
Range [units]
0 .. 10000 [U12]
Default value
20
-
Step
1
Comm object
9259
Related applications
Description
Warning limit level for AIN6.
AIN6 Level 1
Setpoint group
Engine protection
Related FW
2.5.0
Range [units]
0 .. 10000 [-]
Default value
10
-
Step
1
Comm object
9260
Related applications
Description
Shutdown limit level for AIN6.
AIN6 Level 2
Setpoint group
Engine protection
Related FW
2.5.0
Range [units]
0 .. 3600 [s]
Default value
10
-
Step
1
Comm object
9261
Related applications
Description
Delay for Wrn/Sd AIN6 alarm.
AIN6 Del
Summary of Contents for InteliDrive FLX LITE
Page 19: ...ID FLX Lite Global Guide 19 4 3 Terminal diagram and dimension ...
Page 21: ...ID FLX Lite Global Guide 21 Example Default analog output curves ...
Page 22: ...ID FLX Lite Global Guide 22 Example Wiring for Dacon gauges and IL NT AOUT8 ...
Page 44: ...ID FLX Lite Global Guide 44 5 2 Binary inputs and outputs ...
Page 57: ...ID FLX Lite Global Guide 57 5 14 Display screens and pages structure ...
Page 83: ...ID FLX Lite Global Guide 83 7 Communication 6 back to Table of contents ...