ID-FLX Lite Global Guide
144
Setpoint group
Engine protection
Related FW
2.5.0
Range [units]
-100 .. 10000 [°C]
Default value
90
-
Step
1
Comm object
8376
Related applications
Description
Shutdown limit level for ANALOG INPUT 2.
AIN2 Level 2
Setpoint group
Engine protection
Related FW
2.5.0
Range [units]
0 .. 180 [s]
Default value
5
-
Step
1
Comm object
8371
Related applications
Description
Delay for ANALOG INPUT 2 alarm.
Note:
Analog input 2 is usually determined to Engine Temperature measurement and it is resistive type
of input with range 0-2500 Ω.
AIN2 Del
Setpoint group
Engine protection
Related FW
2.5.0
Range [units]
-100 .. +10000 [%]
Default value
20
-
Step
1
Comm object
8381
Related applications
Description
Warning limit level for ANALOG INPUT 3.
AIN3 Level 1
Setpoint group
Engine protection
Related FW
2.5.0
Range [units]
-100 .. 10000 [%]
Default value
10
-
Step
10
Comm object
8382
Related applications
Description
Shutdown limit level for ANALOG INPUT 3.
AIN3 Level 2
Summary of Contents for InteliDrive FLX LITE
Page 19: ...ID FLX Lite Global Guide 19 4 3 Terminal diagram and dimension ...
Page 21: ...ID FLX Lite Global Guide 21 Example Default analog output curves ...
Page 22: ...ID FLX Lite Global Guide 22 Example Wiring for Dacon gauges and IL NT AOUT8 ...
Page 44: ...ID FLX Lite Global Guide 44 5 2 Binary inputs and outputs ...
Page 57: ...ID FLX Lite Global Guide 57 5 14 Display screens and pages structure ...
Page 83: ...ID FLX Lite Global Guide 83 7 Communication 6 back to Table of contents ...