143
Setpoint group
Engine protect
Related FW
3.0.0
Range [units]
0 .. 600 [s]
Default value
10
Step
1
Comm object
9947
Related applications
PRP
Config level
Standard
Setpoint visibility
Always
Description
Delay for Overload RPM protection limit.
Overload Del
Setpoint group
Engine protect
Related FW
3.0.0
Range [units]
0 .. 65535 [h]
Default value
65535
Step
1
Comm object
9648
Related applications
All
Config level
Standard
Setpoint visibility
Always
Description
Running hours count down counter is decremented when engine is running. Service alarm is indicated in
Alarm list and History record is done when counter reaches zero. Service time setpoint is initial counter
value and it is gradually decrement when engine runs.
Note:
Once the service time has elapsed the Service time will have to be adjusted to non-zero value to
clear the alarm and begin a new countdown.
Service Time
Setpoint group
Engine protect
Related FW
3.0.0
Range [units]
[DEFAULT, ALARM ONLY]
Default value
DEFAULT
Step
[-]
Comm object
15813
Related applications
All
Config level
Standard
Setpoint visibility
Always
Description
DEFAULT: LBO: Common Wrn is activated , if ECU alarm is received by controller.
ALARM ONLY: LBO: Common Wrn is not activated, if ECU alarm is received by controller.
ECUAlarmMode
Summary of Contents for InteliDrive DCU Marine
Page 29: ...InteliDrive DCU Marine 3 0 0 Global Guide 29 Protection delay and blocking ...
Page 51: ...InteliDrive DCU Marine 3 0 0 Global Guide 51 4 2 2 Electronic engine without redundancy line ...
Page 255: ...InteliDrive DCU Marine 3 0 0 Global Guide 255 Analog inputs from J1939 configuration ...
Page 265: ...InteliDrive DCU Marine 3 0 0 Global Guide 265 Engine Values ...
Page 285: ...InteliDrive DCU Marine 3 0 0 Global Guide 285 6 back to Appendix 6 back to Table of contents ...