InteliDrive DCU Marine - 3.0.0 Global Guide
132
Setpoint group
Engine params
Related FW
3.0.0
Range [units]
0,0 .. 100,0 [%/s]
Default value
5
Step
0,1
Comm object
9984
Related applications
All
Config level
Standard
Setpoint visibility
Always
Description
Speed ramp setting for BI Speed Up / Down, not for Analog input request.
BI Speed Ramp
Setpoint group
Engine params
Related FW
3.0.0
Range [units]
0,0 .. 100,0 [%]
Default value
50,0
Step
0,1 % of Requested RPM range.
Comm object
10008
Related applications
PRP
Config level
Standard
Setpoint visibility
Always
Description
When Binary input
Fire Speed
is closed the binary output
Clutch Connect
opens (this action deactivates
loadsharing mode if it was activated before) and
Loadsharing: ThrottlePos
is set to
Engine params:
FireAlarmSpeed
value.
FireAlarmSpeed
Setpoint group
Engine params
Related FW
3.0.0
Range [units]
[ENABLED, DISABLED]
Default value
DISABLED
Step
[-]
Comm object
10098
Related applications
All
Config level
Standard
Setpoint visibility
Always
Description
ENABLED:
Engine Values: Speed Request
is defined by
Engine params: Local speed
setpoint that can
be modified by Fast edit function from front panel (4 sec Enter, / ¯, Enter).
DISABLED:
Engine Values: Speed Reques
t is changed via Binary inputs
Speed Up
,
Speed Down
or via
Logical Analog input
Requested RPM
.see
t charts for
and
modes.
EnLocalSpeed
Summary of Contents for InteliDrive DCU Marine
Page 29: ...InteliDrive DCU Marine 3 0 0 Global Guide 29 Protection delay and blocking ...
Page 51: ...InteliDrive DCU Marine 3 0 0 Global Guide 51 4 2 2 Electronic engine without redundancy line ...
Page 255: ...InteliDrive DCU Marine 3 0 0 Global Guide 255 Analog inputs from J1939 configuration ...
Page 265: ...InteliDrive DCU Marine 3 0 0 Global Guide 265 Engine Values ...
Page 285: ...InteliDrive DCU Marine 3 0 0 Global Guide 285 6 back to Appendix 6 back to Table of contents ...