Setpoint group
Engine params
Related FW
3.0.0
Range [units]
CMB, EME: 0 .. 200 [-], AUX, PRP: 1 .. 200 [-]
Default value
3
Step
1
Comm object
8255
Related applications
All
Config level
Standard
Setpoint visibility
Always
Description
Max number of crank attempts.
CMB, EME: Setting to 0 means unlimited number of starting attempts.
Note:
There is one start attempt only in case of panel Start button or Binary input Remote Start
activation. Number of Cranking attempts based on this setpoint is accepted when start is activated by
Binary input RemRepStart (PRP) or Blackout Start (AUX, EME and HRB) only. The setpoint is not
followed if Sd Override is active, crank attempts number is then unlimited in case of Blackout Start.
Together with request of unlimited start attempts was created LBI PrestartOverride - activation means
immediate transition from state Prestart to Cranking.
Same function was applied to second push of START button. First press of START button activates state
Prestart, second press of START button skips prestart period.
Crank Attempts
Setpoint group
Engine params
Related FW
3.0.0
Range [units]
Starting RPM.. Nominal RPM [RPM]
Default value
500
Step
1
Comm object
9946
Related applications
PRP
Config level
Standard
Setpoint visibility
Always
Description
Default Idle speed (should be the same as Idle speed set with engine ECU).
Idle RPM
Summary of Contents for InteliDrive DCU Marine
Page 29: ...InteliDrive DCU Marine 3 0 0 Global Guide 29 Protection delay and blocking ...
Page 51: ...InteliDrive DCU Marine 3 0 0 Global Guide 51 4 2 2 Electronic engine without redundancy line ...
Page 255: ...InteliDrive DCU Marine 3 0 0 Global Guide 255 Analog inputs from J1939 configuration ...
Page 265: ...InteliDrive DCU Marine 3 0 0 Global Guide 265 Engine Values ...
Page 285: ...InteliDrive DCU Marine 3 0 0 Global Guide 285 6 back to Appendix 6 back to Table of contents ...