InteliDrive DCU Industrial 3.4.0 Global Guide
327
* each analog input can be software configured to:
Measuring range
Accuracy
From
To
Resistance
0 Ω
2400 Ω
± 0.5 %
0 Ω
250 Ω
± 1.0 %
Current
Passive
0/4 mA
20 mA
± 0.5 %
Active
4 mA
20 mA
± 0.5 %
Active
0 mA
± 20 mA
± 0.5 %
Voltage
Thermocouples J, K, L type
± 0.2 %
0 mV
100 mV
± 0.2 %
- 1000 mV
+ 1000 mV
± 0.5 %
0 mA
2500 mV
± 0.5 %
Standard conformity
Low Voltage Directive
EN 61010-1:95 +A1:97
Electromagnetic Compatibility
EN 50081-1:94, EN 50081-2:96
EN 50082-1:99, EN 50082-2:97
8.2.7 IS-AIN8TC
Description
IS-AIN8 is input extension module equipped with 8 analog inputs dedicated for thermocouple sensors only. The
module can be used for ID, IGS-NT controller. IS-AIN8TC can be configured to:
Summary of Contents for InteliDrive DCU Industrial
Page 5: ...InteliDrive DCU Industrial 3 4 0 Global Guide 5 8 2 13 Theory of binary inputs and outputs 347...
Page 29: ...InteliDrive DCU Industrial 3 4 0 Global Guide 29...
Page 97: ...InteliDrive DCU Industrial 3 4 0 Global Guide 97 8 Appendix 6 back to Table of contents...
Page 246: ...InteliDrive DCU Industrial 3 4 0 Global Guide 246 Analog inputs from J1939 configuration...
Page 263: ...InteliDrive DCU Industrial 3 4 0 Global Guide 263 6 back to List of setpoints...