InteliDrive DCU Industrial 3.4.0 Global Guide
206
Related FW
3.4.0
Related applications
AS, SS
Comm object
280
Description
Indicates Ready state for Remote engine start.
RdyForRemStart
Related FW
3.4.0
Related applications
AS, SS
Comm object
116
Description
The output closes at the beginning of prestart and opens if the engine shall be stopped. This output can be
used to indicate when the ECU should be powered up i.e. only while the engine is running.
This output also influences evaluation of communication failure with ECU and related alarms from analog
inputs read from the ECU. If the output is configured (which means configured on physical binary output or
VBOUT output), announcement of the communication error is blocked if the engine is switched off including
the stopping procedure as shown in the figure.
Note:
The LBO must be configured on physical binary output or VBOUT output. It is not enough to
configure it as a PLC input for example.
Note:
If the LBO: ECUPowerRelay is used to energize ECU unit during the start procedure, the
initialization of the ECU unit might take slightly longer time and Wrn CommError(x)/Sd CommError(x)
might appear. In this case is recommended to use
, please see this LBI.
ECU PowerRelay
Related FW
3.4.0
Related applications
AS, SS
Comm object
281
Description
1 sec pulse is generated after panel Start button is pressed.
StartButtEcho
Summary of Contents for InteliDrive DCU Industrial
Page 5: ...InteliDrive DCU Industrial 3 4 0 Global Guide 5 8 2 13 Theory of binary inputs and outputs 347...
Page 29: ...InteliDrive DCU Industrial 3 4 0 Global Guide 29...
Page 97: ...InteliDrive DCU Industrial 3 4 0 Global Guide 97 8 Appendix 6 back to Table of contents...
Page 246: ...InteliDrive DCU Industrial 3 4 0 Global Guide 246 Analog inputs from J1939 configuration...
Page 263: ...InteliDrive DCU Industrial 3 4 0 Global Guide 263 6 back to List of setpoints...