InteliDrive DCU Industrial 3.4.0 Global Guide
109
Comms settings
Setpoint group
Communication
Settings
Related FW
3.4.0
Range [units]
[ENABLE, DISABLE]
Default value
ENABLE
Force value
Alternative config
Step
[-]
Comm object
24399
Related applications
AS, SS
Description
The parameter switches the address for a 5th ID-DCU Industrial display, the fifth ID-DCU Industrial display
occupies a modem address if ENABLE is set. ENABLE is a default value.
5thRemPan
Setpoint group
Communication
Settings
Related FW
3.4.0
Range [units]
[32C, 8C]
Default value
32C
Force value
Alternative config
Step
[-]
Comm object
24499
Related applications
AS, SS
Description
Inter-controller, IG-IB, IB-NT CAN2 bus speed selection.
32C: High speed CAN (250 kBd) applicable with up to 32 controllers, CAN bus limited up to 200 meters.
8C: Low speed CAN (50 kBd) applicable with up to 8 controllers, CAN bus limited up to 900 meters.
Note:
Low speed CAN2 bus use for long distance connection only. Set all connected controllers to the
same speed. Other units IG-IB, IB-NT detect CAN bus speed automatically.
Note:
If the controller is connected to IB-NT, set the mode to 8C - verified stable communication speed.
CAN Bus Mode
Summary of Contents for InteliDrive DCU Industrial
Page 5: ...InteliDrive DCU Industrial 3 4 0 Global Guide 5 8 2 13 Theory of binary inputs and outputs 347...
Page 29: ...InteliDrive DCU Industrial 3 4 0 Global Guide 29...
Page 97: ...InteliDrive DCU Industrial 3 4 0 Global Guide 97 8 Appendix 6 back to Table of contents...
Page 246: ...InteliDrive DCU Industrial 3 4 0 Global Guide 246 Analog inputs from J1939 configuration...
Page 263: ...InteliDrive DCU Industrial 3 4 0 Global Guide 263 6 back to List of setpoints...