InteliDrive DCU Industrial 3.4.0 Global Guide
101
Password
There are three levels of password protection.
User level allows change of non-protected setpoints only.
Operator level allows change of setpoints protected by Operator level.
Master level allows change of setpoints protected by Operator and Master level.
Supervisor highest level allows all setpoints or configuration changes, firmware upgrade.
Note:
The asterisk mark “*” appears before a setpoint name (on controller screen) if the setpoint is password
protected.
The asterisk mark is removed only when the password is set from controller’s front panel.
The asterisk mark is still visible on controller screen even if the password is set from InteliMonitor.
Note:
Even though one level may have been set from the front panel, the affected setpoints are not accessible
from InteliMonitor (direct or Modem) until this level is set in InteliMonitor (direct or Modem). Setpoints opened
from front panel are automatically closed 15 minutes after the last key has been depressed or when wrong value
of setpoint is set.
Note:
It is possible to protect remote Start, Stop commands from InteliMonitor as well. This three level
command protection can be configured from DriveConfig.
EnterPassword
Password is a four-digit number. Only setpoints associated with the entered password level can be modified.
Use ↑ or ↓ to select the desired password and then hit enter.
ChangePassword 1
ChangePassword 2
ChangePassword 3
Note:
Any password can be changed once that level password or higher has been entered if the change is
made from InteliMonitor PC tool.
Password level 3 must be entered at first to change any password if the change is made by controller
front panel buttons.
To change password protection of Setpoint or Command:
1. Open DriveConfig
2. Select Setpoints or Commands window
3. Set desired protection level: 0 or 1 or 2 or 3
Access code
Can be changed from InteliMonitor software only (Monitor – Change Access code).
Has to be set before remote modem or SMS connection is opened.
Can be up to 16 ASCII characters
At first
Password 3
has to be entered before the new Access code can be changed.
Summary of Contents for InteliDrive DCU Industrial
Page 5: ...InteliDrive DCU Industrial 3 4 0 Global Guide 5 8 2 13 Theory of binary inputs and outputs 347...
Page 29: ...InteliDrive DCU Industrial 3 4 0 Global Guide 29...
Page 97: ...InteliDrive DCU Industrial 3 4 0 Global Guide 97 8 Appendix 6 back to Table of contents...
Page 246: ...InteliDrive DCU Industrial 3 4 0 Global Guide 246 Analog inputs from J1939 configuration...
Page 263: ...InteliDrive DCU Industrial 3 4 0 Global Guide 263 6 back to List of setpoints...