InteliMains
NT
, SW version 3.0
InteliMains-NT-BTB-3.0-Reference Guide.pdf,
©ComAp – June 2013
290
SHAIN
-
-
4
-
Shared (virtual) Analog Input module
2
SHAOUT
-
-
-
4
Shared (virtual) Analog OUTput
module
2
PLC
x
x
x
x
Programmable (internal) logic module.
1
N
OTE
:
Maximum number of configured modules (both extension and virtual) is given by available addresses.
The numbers in the table are valid in the case that no other modules are configured.
15.2 Table of Binary Output functions
15.2.1.1
Binary output: BTB Close/Open
Related
FW
3.0
Descriptio
n
This output is intended for control of the BTB if a
contactor
is used as BTB. The output
provides continuous signal while the BTB has to be closed. See timing diagram of all
available breaker control outputs at the bottom of this description.
N
OTE
:
Use
invert
function when configuring the output in GenConfig to obtain
inverted function
of the output, i.e. output is closed while the BTB has to be open.
There are also other outputs availabe for BTB control: