InteliMains
NT
, SW version 3.0
InteliMains-NT-BTB-3.0-Reference Guide.pdf,
©ComAp – June 2013
167
12.2.8.28
Setpoint: #MinRunPower 3
Group
Power Management
Range [units]
0 .. 65000 [kW]
Related FW
3.0
Description
This setpoint is used to adjust certain minimum value of the sum of nominal
power of all running gen-sets. If the function is active, then the gen-sets
would not be stopped, although the reserve for stop is fulfiled, if the total
remaining nominal power dropped below this minimal value.
There are 3 different
MinRunPower
setpoints, this particular one is activated
by the input MinRun power 3 which is in MINT application (in InteliMains it is
for compatibility purposes only).
N
OTE
:
When more than one binary input MinRunPower is activated then
MinRunPower with the highest number is active.
N
OTE
:
# sign in the name of this setpoint marks that this setpoint is shared among
all controllers connected by CAN2 bus.
12.2.8.29
Setpoint: #RunHrsMaxDiff
Group
Pwr management
Range [units]
0 .. 65000 [h]
Related FW
3.0
Description
This setpoint adjusts the "deadband" for the
running hours equalization
function. The priorities are swapped not until the relative engine hours (RHE)
difference is higher than this deadband.
N
OTE
:
# sign in the name of this setpoint marks that this setpoint is shared among
all controllers connected by CAN2 bus.
12.2.8.30
Setpoint: #PwrBandContr 1
Group
Pwr management
Range [units]
1, 2, 1+2, 3, 1+3, 2+3, 1+2+3 [-]