5.3.14.4. LED Indication
Green LED is located near the power supply connector.
I-AOUT8 module state
LED Pwr
No power supply
Dark
Memory fail
Fast blink (100/100 ms)
Communication fail
Slow blink (300/300 ms)
OK
Continuous light
5.3.14.5. Wiring and jumper setting example
Voltage
output
0 to 10 VDC
Current
output
0 to 20 mA
Current
output
0 to 20 mA
Pwm output
5V, max 10 mA
AGND
AOUT
AGND
AOUT
max 500ohm
+
+
+
max 5 mA
+
AGND
AOUT
max 500ohm
AGND
AOUT
Pwm output
1200 Hz
Current output
0 to 20 mA
Current output
0 to 20 mA
Voltage output
0 to 10 VDC
5.3.15.
I-LBA
For the connections with 12VDC power supply an I-LBA module can be connected to controller
power terminals in order to allow the controller to continue operation during cranking if the
battery voltage dip occurs.
Controllers which may be supplied from I-LBA module:
Controller
IG-NT/
IG-NT-
BB
IG-NTC/
IG-NTC-
BB
IS-NT-BB/
IS-NTC-
BB
IS-NT
IG-CU
IS-CU
IL-CU/
IL-NT
Connection
applicable
YES
YES
YES
NO
YES
NO
YES
Summary of Contents for IG-NT