ID-FLX Lite & Telecom Global Guide
97
Setpoint group
Basic settings
Related FW
2.5.0
Range [units]
50.00 .. 200.00 [-]
Default value
1
-
Step
0.01
Comm object
8420
Related applications
Description
The constant of this setpoint multiplies the speed value obtained from the controller input RPM.
Note:
The default value is and must be 1, when the classical pick-up speed sensor is used to measure
the engine speed.
The setpoint is usefull when the engine does not have the speed sensor and the speed is measured by
the W terminal of the charging alternator. The setpoint allows tuning the ratio between the frequency and
the RPM value which can not to correspond to the entire values of teeth numbers (because of the
different non-integral ratio of the engine and alternator pulleys).
RPMbyWterminal
Setpoint group
Basic settings
Related FW
2.5.0
Range [units]
100 .. 4000 [RPM]
Default value
-
Step
1
Comm object
8253
Related applications
Description
Nominal engine speed, base for overspeed protection and scale on RPM gauges.
Nominal RPM
Summary of Contents for ID-Lite
Page 16: ...ID FLX Lite Telecom Global Guide 16 4 3 Terminal diagram and dimension...
Page 18: ...ID FLX Lite Telecom Global Guide 18 Example Default analog output curves...
Page 19: ...ID FLX Lite Telecom Global Guide 19 Example Wiring for Dacon gauges and IL NT AOUT8...
Page 41: ...ID FLX Lite Telecom Global Guide 41 5 2 Binary inputs and outputs...
Page 54: ...ID FLX Lite Telecom Global Guide 54 5 14 Display screens and pages structure...