ID-FLX Lite & Telecom Global Guide
75
Events
specification
Protection
type
Information on binary
output available
195)
Description
protection comes active if the
running hours of the engine reach
this value.
ChrgAlternFail
WRN
YES
Failure of alternator for charging the
battery.
SprinklActive
WRN
NO
The protection is active if the output
Sprinkler is closed.
Wrn RA15 fail
WRN
NO
Warning alarm in case of lost
connection to remote annunciator
module.
Wrn ECU Alarm
WRN
NO
ECU alarm list is not empty.
Low BackupBatt
WRN
NO
RTC backup battery is flat.
6.2 History file
ID-Lite stores a record of each important event into the history file. The history file seats 255 records. When the
history file is full, the oldest records are removed.
Note:
To force history download in LiteEdit (direct, modem or internet) open History window and select History |
Read history command.
6.2.1 Record structure
Abbreviation
Historical value
Num
Number of historical event
Reason
Event specification
Date
Date of historical event in format DD/MM/YY
Time
Time of historical event in format HH:MM:SS
RPM
Engine speed
RPM3
Engine speed detected on BI3
UBat
Battery voltage
OilP
ID-Lite analog input 1 value (default Oil pressure)
EngT
ID-Lite analog input 2 value (default Water temperature)
FLvl
ID-Lite analog input 3 value (default Fuel level)
AI4
ID-Lite analog input 4 value
AI5
ID-Lite analog input 5 value
AI6
ID-Lite analog input 6 value
AI7
ID-Lite analog input 7 value
AI8
ID-Lite analog input 8 value
Summary of Contents for ID-Lite
Page 16: ...ID FLX Lite Telecom Global Guide 16 4 3 Terminal diagram and dimension...
Page 18: ...ID FLX Lite Telecom Global Guide 18 Example Default analog output curves...
Page 19: ...ID FLX Lite Telecom Global Guide 19 Example Wiring for Dacon gauges and IL NT AOUT8...
Page 41: ...ID FLX Lite Telecom Global Guide 41 5 2 Binary inputs and outputs...
Page 54: ...ID FLX Lite Telecom Global Guide 54 5 14 Display screens and pages structure...