ID-FLX Lite & Telecom Global Guide
186
Related FW
2.5.0
Related applications
Comm object
184
Description
Binary input has no function. Use this option when binary input is not connected.
Not used
Related FW
2.5.0
Related applications
Comm object
172
Description
Binary input is used for external request for engine run in AUT mode only.
Rem start/stop
Related FW
2.5.0
Related applications
Comm object
40
Description
If the input is opened, shut down is immediately activated. Input is inverted (normally closed) in default
configuration.
Note:
In case of controller hardware or software fail, safe stop of the engine doesn’t have to be ensured.
To back-up the Emergency stop function it is recommended to connect separate circuit for disconnection
of Fuel solenoid and Starter signals.
Emergency stop
Related FW
2.5.0
Related applications
Comm object
44
Description
If the input is closed all alarms are disabled except the binary input Emergency stop and "engine overspeed
protection".
All ID-Lite alarms are detected,
ID-Lite front panel RED LED blinks or lights,
Alarm is recorded on the ID-Lite alarm list screen,
BUT engine remains running.
Note:
Warning SprinklActive is indicated in the Alarm list if sprinkler mode active to inform the operator
that the engine is not protected.
Sprinkler
Summary of Contents for ID-Lite
Page 16: ...ID FLX Lite Telecom Global Guide 16 4 3 Terminal diagram and dimension...
Page 18: ...ID FLX Lite Telecom Global Guide 18 Example Default analog output curves...
Page 19: ...ID FLX Lite Telecom Global Guide 19 Example Wiring for Dacon gauges and IL NT AOUT8...
Page 41: ...ID FLX Lite Telecom Global Guide 41 5 2 Binary inputs and outputs...
Page 54: ...ID FLX Lite Telecom Global Guide 54 5 14 Display screens and pages structure...