ID-FLX Lite & Telecom Global Guide
184
9.1.4 Logical binary inputs
Note:
Any binary input can be configured to any ID-Lite controller terminal or changed to different function by
LiteEdit PC tool. There is adjustable delay when any binary input is configured as protection.
Binary inputs InteliDrive Lite – default configuration
BI1 – Rem start/stop
BI2 – Access lock
BI3 – Emergency stop
BI4 – Remote OFF
BI5 – Sprinkler
BI6 – RemControlLock
BI7 – Not used
Configuration of binary inputs
Each binary input can be configured in several ways. The settings can be made in the PC program LiteEdit, in
window Modify. After choosing a concrete binary input, its window appears where the user can choose if the
binary input will be used to protect (option Alarm) or control (option Control).
Binary Alarm configuration items – see the picture and the table with explanations.
Name
14 characters ASCII string
Contact type
NC
Normally closed
NO
Normally opened
Alarm type
Warning
Shut down
Alarm active
All the time
Engine running only