Setpoint group
Engine protection
Related FW
2.5.0
Range [units]
0 .. 3600 [s]
Default value
0
-
Step
1
Comm object
13084
Related applications
Description
Seven setpoints are dedicated for separately adjustment of the delay for each of binary inputs according to
the Class B protection standard.
Note:
The corresponding BIN protection has to be configured as Running only in LiteEdit.
BIN7 Prot Del
Setpoint group
Engine protection
Related FW
2.5.0
Range [units]
0 .. 150 [%]
Default value
10
-
Step
1
Comm object
13178
Related applications
Description
Diesel Exhaust Fluid level protection activates
when received level (J1939 -
SCR - Selective Catalytic Reduction message) is below DEF Level Min for more than (fix) 3 s delay. This
function is active for IVECO NEF&&Cursor engine. LBO can be active for running engine only.
DEF Level Min
Setpoint group
Engine protection
Related FW
2.5.0
Range [units]
0 .. 150 [%]
Default value
90
-
Step
1
Comm object
13379
Related applications
Description
Diesel Exhaust Fluid level protection deactivates
when received level (J1939
- SCR - Selective Catalytic Reduction message) is above DEF Level Max for more than (fix) 3 s delay. This
function is active for IVECO NEF&&Cursor engine.
Note:
DEF Level is usual signage of Urea tank level, which is more often used in United States.
DEF Level Max
Summary of Contents for ID-Lite
Page 16: ...ID FLX Lite Telecom Global Guide 16 4 3 Terminal diagram and dimension...
Page 18: ...ID FLX Lite Telecom Global Guide 18 Example Default analog output curves...
Page 19: ...ID FLX Lite Telecom Global Guide 19 Example Wiring for Dacon gauges and IL NT AOUT8...
Page 41: ...ID FLX Lite Telecom Global Guide 41 5 2 Binary inputs and outputs...
Page 54: ...ID FLX Lite Telecom Global Guide 54 5 14 Display screens and pages structure...