![ComAp ID-Lite Global Manual Download Page 156](http://html1.mh-extra.com/html/comap/id-lite/id-lite_global-manual_2638907156.webp)
ID-FLX Lite & Telecom Global Guide
156
Setpoint group
Engine protection
Related FW
2.5.0
Range [units]
0 .. 180 [s]
Default value
10
-
Step
1
Comm object
9270
Related applications
Description
Delay for Wrn/Sd AIN9 alarm.
Note:
Analog input 9 is configurable with basic two levels protection and it is voltage type of input with
range 0-10 V.
AIN9 Del
Setpoint group
Engine protection
Related FW
2.5.0
Range [units]
0 .. 65535 [h]
Default value
10000
YES
Step
1
Comm object
9648
Related applications
Description
Counting down when engine is running, from the moment of setting up the value of working hours in
LiteEdit/controller. This value is counting and changing in LiteEdit/controller as well. Service time alarm
appears if reaches zero, until non-zero value is set.
Note:
Set the NextServTime = 65535 h to disable count down. The setpoint stays constant, but
Statistics value (visible in LiteEdit) displays #### invalid value.
NextServTime
Setpoint group
Engine protection
Related FW
2.5.0
Range [units]
0.0 .. 5.0 [RPM]
Default value
0.0
-
Step
0.1
GearBoxRatio
Summary of Contents for ID-Lite
Page 16: ...ID FLX Lite Telecom Global Guide 16 4 3 Terminal diagram and dimension...
Page 18: ...ID FLX Lite Telecom Global Guide 18 Example Default analog output curves...
Page 19: ...ID FLX Lite Telecom Global Guide 19 Example Wiring for Dacon gauges and IL NT AOUT8...
Page 41: ...ID FLX Lite Telecom Global Guide 41 5 2 Binary inputs and outputs...
Page 54: ...ID FLX Lite Telecom Global Guide 54 5 14 Display screens and pages structure...