Setpoint group
Engine protection
Related FW
2.5.0
Range [units]
0 .. 3600 [s]
Default value
10
-
Step
1
Comm object
13349
Related applications
Description
High level protection delay for Wrn and Sd of AIN7.
Note:
In the alarm list is only displayed Wrn/Sd alarm on the appropriate analog input. There is not
resolution Low/High alarm.
Note:
Analog input 7 is fully configurable and it is voltage type of input with range 0-10 V.
AIN7 HighDel
Setpoint group
Engine protection
Related FW
2.5.0
Range [units]
0 .. 10000 [U14]
Default value
20
-
Step
1
Comm object
9265
Related applications
Description
Warning limit level for AIN8.
AIN8 Level 1
Setpoint group
Engine protection
Related FW
2.5.0
Range [units]
0 .. 10000 [U14]
Default value
20
-
Step
1
Comm object
9266
Related applications
Description
Shutdown limit level for AIN8.
AIN8 Level 2