ID-FLX Lite & Telecom Global Guide
135
Setpoint group
ATT settings
Related FW
2.5.0
Range [units]
0.0 .. 100.0 [%]
Default value
0
YES
Step
0.1
Comm object
11858
Related applications
Description
This setpoint is giving Load limit integration factor.
Load Integral
Setpoint group
Load limit
Related FW
2.5.0
Range [units]
RPM, ECU:Load, CU:AI1, CU:AI2, CU:AI3, CU:AI4, CU:AI5, CU:AI6, CU:AI7,
CU:AI8, CU:AI9, AIO:IA1, AIO:AI2, AIO:AI3, AIO:AI4 [-]
Default value
RPM
YES
Step
-
Comm object
11859
Related applications
Description
This setpoint is for Load limit comparetor with hysteresis analog input selection. Source can be adjusted
from controller RPM pick-up, ECU, analog inputs or from extension module inputs.
Value of this Setpoint should be given in value of quantity without decimal point.
Example:
When AIN is configured in such way that Load limit set on 5 V to maintain the value
8.54 bar, then the value inserted to this Setpoint is 854.
Load CMP Input
Setpoint group
ATT settings
Related FW
2.5.0
Range [units]
-10000 .. +10000 [-]
Default value
95
YES
Step
1
Comm object
11860
Related applications
Description
Limit to close
Value of this Setpoint should be given in value of quantity without decimal point.
Example:
When AIN is configured in such way that Load limit set on 5 V to maintain the value
8.54 bar, then the value inserted to this Setpoint is 854.
Load CMP Off
Summary of Contents for ID-Lite
Page 16: ...ID FLX Lite Telecom Global Guide 16 4 3 Terminal diagram and dimension...
Page 18: ...ID FLX Lite Telecom Global Guide 18 Example Default analog output curves...
Page 19: ...ID FLX Lite Telecom Global Guide 19 Example Wiring for Dacon gauges and IL NT AOUT8...
Page 41: ...ID FLX Lite Telecom Global Guide 41 5 2 Binary inputs and outputs...
Page 54: ...ID FLX Lite Telecom Global Guide 54 5 14 Display screens and pages structure...