ID-FLX Lite & Telecom Global Guide
130
Setpoint group
Load limit
Related FW
2.5.0
Range [units]
CU:AI1, CU:AI2, CU:AI3, CU:AI4, CU:AI5, CU:AI6, CU:AI7, CU:AI8, CU:AI9,
AIO:IA1, AIO:AI2, AIO:AI3, AIO:AI4, RPM-BI3 [-]
Default value
CU:AI1
YES
Step
-
Comm object
11839
Related applications
Description
This is comparator with hysteresis analog input selection from controller analog inputs or from extension
module inputs. It is also possible to use Binary input 3 in function of RPM detection.
Reg CMP Input
Setpoint group
Load limit
Related FW
2.5.0
Range [units]
-10000 .. +10000 [-]
Default value
0
YES
Step
1
Comm object
11841
Related applications
Description
Limit to close
Value of this Setpoint should be given in value of quantity without decimal point.
Example:
When AIN is configured in such way that Load limit set on 5 V to maintain the value
8.54 bar, then the value inserted to this Setpoint is 854.
Reg CMP On