Setpoint group
Engine parameters
Related FW
2.5.0
Range [units]
0 .. 3000 [RPM]
Default value
0
-
Step
1
Comm object
11125
Related applications
Description
Limit for Speed Request transformation from RPM to % range for ECU engines using % format.
Example:
If ECU is configured, then on one of the measurement screen you can see two lines SpeedReq Abs
and SpeedReq Rel.
In default setting:
0 RPM = 0 %
800 RPM = 33.3 %
2400 RPM = 100 %
Different setting:
800 RPM = 0 %
1200 RPM = 33.3 %
2400 RPM = 100 %
It is possible easily configure own output curve and use it for analog output Speed Request.
0%ofSpeedReq
Setpoint group
Engine parameters
Related FW
2.5.0
Range [units]
0 .. 4000 [RPM]
Default value
2000
-
Step
1
Comm object
11126
Related applications
Description
Limit for Speed Request transformation from RPM to % range for ECU engines using % format.
100%ofSpeedReq
Setpoint group
Engine parameters
Related FW
2.5.0
Range [units]
0 .. 600 [s]
Default value
7
-
Step
1
Comm object
11835
Related applications
Description
Horn time before the conveyor output starts.
Conveyor horn
Summary of Contents for ID-Lite
Page 16: ...ID FLX Lite Telecom Global Guide 16 4 3 Terminal diagram and dimension...
Page 18: ...ID FLX Lite Telecom Global Guide 18 Example Default analog output curves...
Page 19: ...ID FLX Lite Telecom Global Guide 19 Example Wiring for Dacon gauges and IL NT AOUT8...
Page 41: ...ID FLX Lite Telecom Global Guide 41 5 2 Binary inputs and outputs...
Page 54: ...ID FLX Lite Telecom Global Guide 54 5 14 Display screens and pages structure...