ID-FLX Lite & Telecom Global Guide
118
Setpoint group
Engine parameters
Related FW
2.5.0
Range [units]
0.0 .. 300.0 [s]
Default value
0.5
-
Step
0.1
Comm object
10525
Related applications
Description
This setpoint adjusts the Fuel solenoid output activation in relation to Starter output when Fuel solenoid =
GAS. Setpoint values mean that fuel valve is opened after the Starter. FuelSol offset has effect for both Fuel
solenoid = DIESEL or GAS.
Engine starting procedure when
= GAS
Note:
A new feature has been added which prolongs the last cranking attempt by 25% of MaxCrank time
with closed Fuel valve (Fuel Solenoid binary output) in order to ventilate the remaining gas, as is
implemented in IG/IS-NT. This function is valid only when
= GAS
Note:
Is modified functionality of the Ignition binary output. The Ignition binary output will close 1 second
(fixed value) after activation of binary output Fuel solenoid (when Fuel solenoid = GAS setting is active).
Generally, the output closes after reaching value of CrankRPM = 30RPM (fixed value). The output opens
after stopping of the engine or during crank fail pauses among crank attempts.
FuelSol offset