ID-FLX Lite & Telecom Global Guide
114
Setpoint group
Engine parameters
Related FW
2.5.0
Range [units]
OFF/CU: AI1 .. CU: AI9/AIO: AI1 .. AIO: AI4 [-]
Default value
OFF
-
Step
-
Comm object
15989
Related applications
N/A
Description
This setpoint is used for selection of analog input, which is used for temperature measurement used for
variable preheating time calculation. See description of
.
PreheatSensor
Setpoint group
Engine parameters
Related FW
2.5.0
Range [units]
1 .. 60 [s]
Default value
5
-
Step
1
Comm object
8256
Related applications
Description
This setpoint is giving maximum time limit of engine cranking.
MaxCrank time
Setpoint group
Engine parameters
Related FW
2.5.0
Range [units]
5 .. 60 [s]
Default value
8
-
Step
1
Comm object
8257
Related applications
Description
Pause between crank (engine start) attempts.
CrnkFail pause
Setpoint group
Engine parameters
Related FW
2.5.0
Range [units]
1 .. 10 [-]
Default value
3
-
Step
1
Comm object
8255
Related applications
Description
Maximum number of crank (engine start) attempts.
Crank attempts
Summary of Contents for ID-Lite
Page 16: ...ID FLX Lite Telecom Global Guide 16 4 3 Terminal diagram and dimension...
Page 18: ...ID FLX Lite Telecom Global Guide 18 Example Default analog output curves...
Page 19: ...ID FLX Lite Telecom Global Guide 19 Example Wiring for Dacon gauges and IL NT AOUT8...
Page 41: ...ID FLX Lite Telecom Global Guide 41 5 2 Binary inputs and outputs...
Page 54: ...ID FLX Lite Telecom Global Guide 54 5 14 Display screens and pages structure...