InteliDrive Lite - 1.2.1 Global guide
94
State
Condition of the
transition
Action
Next state
Start request
READY TO LOAD on
Running
Stop
RPM = 0, Oil
pressure not
detected, D+ not
active
Ready
60 sec. Elapsed
Stop (Stop fail)
1
The start-up sequence can be interrupted in any time by coming stop request
2
Fuel solenoid is switched on with advance of 1s fixed before starter motor is switched on.
Note:
Threshold level for D+ input is 80% supply voltage; activation delay is 1s (to override short firings during
cranking – for example in cold conditions).
Speed request:
Engine speed is constant or set manually using
Engine params
setpoints and Binary inputs.
9.4 AUT mode
The controller does not respond to
,
buttons. Engine start/stop request is given by binary input REM
START/STOP.
Engine speed request is sourced from PI loop (see below function 3) in AUT mode.
PI loop and Hysteresis comparator functions can be used both for Engine Load Limitation or any other control
function.
Speed request:
Engine speed is adjusted automatically by internal PID loops (when active) -
Regulator
setpoints group.
9.5 Engine without pickup operation
The RPM pickup input is ignored when
Engine params
: Gear teeth = 0. The engine running state is then
detected based on
Engine params
: Starting POil or
Engine params
: D+ function = ENABLED.
Starting Poil
signal can be analog or binary. Even the binary signal is to be connected to AIN1 input. In LiteEdit,
window
Modify
, input
Oil Pressure
, check off the option
Binary
. The setpoint
Starting Poil
set to 1.
9.6 Engine timer
9.6.1 MAN mode
Set the
Engine params
:
Running Timer
. Start engine in MAN mode by START button. Engine stops itself after
Running Timer
is over. The STOP button cancels timer (forces cooling), the second STOP cancels cooling
(forces engine stop). Engine stays running when
Running Timer
= 0.