InteliDrive Lite - 1.2.1 Global guide
190
Setpoint group
Date/Time
Related FW
1.2.1
Range [units]
1 - 1440 [min]
Default value
5 min
Force value
Step
1 min
Comm object
10201
Related applications
Config level
Standard
Setpoint visibility
Always
Description
Adjusts duration of Timer 2 output.
Timer2Duration
Setpoint group
Date/Time
Related FW
1.2.1
Range [units]
all dates
Default value
actual date
Force value
Step
one day
Comm object
10200
Related applications
Config level
Standard
Setpoint visibility
Always
Description
Setting of the date when is activated Timer 2 with set Timer1 repeat = ONCEATDATE.
Timer2OnceDate
10.1.16 Group: Sensor spec
Setpoint group
Sensor spec
Related FW
1.2.1
Range [units]
-1000 - +1000 [Bar]
Default value
0 Bar
Force value
Step
1 Bar
Comm object
8431
Related applications
Config level
Standard
Setpoint visibility
Always
Description
Calibrate the constant to adjust the measured value of InteliDrive IPC analog inputs. Physical dimension of
calibrating constant is corresponding to Analog input.
Note:
Calibration constants have to be adjusted when measured value is near the alarm level.
Calibr AI1