Setpoint group
Date/Time
Related FW
1.2.1
Range [units]
all dates
Default value
actual date
Force value
Step
one day
Comm object
10043
Related applications
Config level
Standard
Setpoint visibility
Always
Description
Setting of the date when is activated Timer 1 with set Timer1 repeat = ONCEATDATE.
Timer1OnceDate
Setpoint group
Date/Time
Related FW
1.2.1
Range [units]
[-]
Default value
No Func
Force value
Step
[-]
Comm object
11661
Related applications
Config level
Standard
Setpoint visibility
Always
Description
No Func: Operates just corresponding LBO Timer2 according the Timer2 setting, see Timer2 repeat, Time2
ON time, Timer2Duration. Function operates in all OFF-MAN-AUT modes. Default state.
AutoRun: Engine automatically starts and stops in AUT mode (similar to LBI Rem start/stop, the same
record in the history) according the Timer2 setting.
AutoRegCMP: Start and stop engine in AUT mode according to the LBO Speed switch - see Regulator: Reg
CMP setpoints. The comparator function (output) works opposite when Regulator: Reg CMP On < Reg
CMP Off. The Date/Time: Timer2 repeat, Timer2 ON time, Timer2Duration settings are not important in this
case.
AutoBatt: Engine starts when actual Battery voltage < Engine protect: Batt und Batt volt del and
stays running for Date/Time: Timer2 Duration. Function operates in AUT mode.
AutoStop: Engine is switched from AUT to MAN and stopped or stopped from MAN mode (like by STOP
button) when engine runs longer then Date/Time: Timer2Duration on actual RPM less or equal Engine
params: Idle speed + 5% (fix limit). Function is not active during engine start.
Timer2Function