![ComAp ID-FLX-Lite-PC Global Manual Download Page 180](http://html1.mh-extra.com/html/comap/id-flx-lite-pc/id-flx-lite-pc_global-manual_2638902180.webp)
InteliDrive Lite - 1.2.1 Global guide
180
Setpoint group
Engine protect 2
Related FW
1.2.1
Range [units]
1-1000 [RPM]
Default value
1000 RPM
Force value
Step
1 RPM
Comm object
10143
Related applications
Config level
Standard
Setpoint visibility
Always
Description
RPM-BI3 Sd underspeed protection limit or Sd difference limit between RPM-BI3 and RPM transferred via
GearBoxRatio. See description in GearBoxRatio setpoint. In alarm list appears text Sd RPMdiff.
Message: Wrn RPMdiff
RPMdiff Sd
Setpoint group
Engine protect 2
Related FW
1.2.1
Range [units]
1 - 1000 [RPM]
Default value
1000 RPM
Force value
Step
1 RPM
Comm object
10141
Related applications
Config level
Standard
Setpoint visibility
Always
Description
RPM-BI3 Wrn underspeed protection limit or Wrn difference limit between RPM-BI3 and RPM transferred
via GearBoxRatio. See description in GearBoxRatio setpoint. In alarm list appears text Wrn RPMdiff.
Message: Wrn RPMdiff
RPMdiff Wrn
Setpoint group
Engine protect 2
Related FW
1.2.1
Range [units]
0 - 600 [s]
Default value
5 s
Force value
Step
1 s
Comm object
10150
Related applications
Config level
Standard
Setpoint visibility
Always
Description
Delay for RPMdiff protections above. See description in GearBoxRatio setpoint.
RPMdiff delay