175
Setpoint group
Engine protect 2
Related FW
1.2.1
Range [units]
50 - 150 [%]
Default value
120 %
Force value
Step
1 %
Comm object
13340
Related applications
Config level
Standard
Setpoint visibility
Always
Description
Limit for engine ShutDown overspeed protection. Protection is active during start process of the engine and
Idle time.
Note:
The engine can spasmodically reach higher than Overspeed level during start, but for normal
running state would be this protection too high. This setpoint allows the overspeed protection during
irregular starting condition.
StartOverspeed