Setpoint group
Engine protect
Related FW
1.2.1
Range [units]
[-]
Default value
DISABLED
Force value
Step
[-]
Comm object
14603
Related applications
Config level
Standard
Setpoint visibility
Always
Description
The setting ENABLED disables all engine protections. They are just displayed on alarm list and recorded to
historry, but they have no influence to running engine. The setting ENABLED is indicated in tha alarm list as
warning
SdOverride Act
and recorded to history as record
SdOverride Act
.
Sd Override
Setpoint group
Engine protect
Related FW
1.2.1
Range [units]
[-]
Default value
ENABLED
Force value
Step
[-]
Comm object
14653
Related applications
Config level
Standard
Setpoint visibility
Always
Description
The setting DISABLED disables all configured protections, except Overspeed and Emergency Stop. It is
indicated in the alarm list by warning Prot AIN1 dis. Each configuration change is recorded in history,
records: Prot AIN1 dis and Prot AIN1 ena.
Setpoint name depends on setting of AIN1 (maximum length is 14 characters).
AIN1 prot
Setpoint group
Engine protect
Related FW
1.2.1
Range [units]
-10 - +1000 [Bar]
Default value
2 Bar
Force value
Step
0.1 Bar
Comm object
8369
Related applications
Config level
Standard
Setpoint visibility
Always
Description
Warning limit level for ANALOG INPUT 1
Setpoint name depends on setting of AIN1 (maximum length is 14 characters).
AIN1 Wrn