InteliDrive Lite - 1.2.1 Global guide
144
Setpoint group
Engine params 2
Related FW
1.2.1
Range [units]
0 - 50 [%/h]
Default value
0 %/h
Force value
Step
1 %/h
Comm object
12373
Related applications
Config level
Standard
Setpoint visibility
Always
Description
This is setting protection against the fuel leakage or theft.
Function monitors the AIN3 Fuel level value in percentage scale without decimals. The alarm and history
record “Wrn FuelTheft” is activated when Fuel level change is faster than setpoint limit. Function is switched
off when Max Fuel Drop = 0 %/h.
The drop out limit on stopped engine is 5% to avoid unwanted Alarm activation due to AIN3: Fuel level
fluctuations.
Active alarm "Wrn FuelTheft" can be sent via SMS and displayed by WebSupervisor (if used).
Note:
Set 0 to disable Fuel Theft Protection function into MaxFuelDrop setpoint.
MaxFuelDrop
10.1.9 Group: Regulator
Note:
Following setpoints are available from Controller and LiteEdit/InteliMonitor.