InteliDrive Lite - 1.2.1 Global guide
137
Setpoint group
Engine params 2
Related FW
1.2.1
Range [units]
[-]
Default value
DISABLED
Force value
Step
[-]
Comm object
9683
Related applications
Config level
Standard
Setpoint visibility
Always
Description
ENABLED: The D+ terminal is used for both functions - “running engine” detection and charge fail detection.
CHRGFAIL: The D+ terminal is used for charge fail detection only.
DISABLED: The D+ terminal is not used. Defult state.
Note:
The magnetization current is provided independently on this setpoint value.
Note:
The D+ charge fail protection becomes active after Engine params 2: Idle time reaches zero.
D+ function
Setpoint group
Engine params 2
Related FW
1.2.1
Range [units]
[-]
Default value
DEFAULT
Force value
Step
[-]
Comm object
10266
Related applications
Config level
Standard
Setpoint visibility
Always
Description
This setpoint should be used only for Volvo and Scania engines.
Volvo – “Volvo Aux” is selected in ECU configuration:
Primary or secondary engine speed is set by Frequency select bits in VP Status frame.
Scania – “Scania S6 Singlespeed” is selected in ECU configuration:
Nominal engine speed is chosen by Nominal speed switch 1 and 2 from DLN1 frame when the engine is
running on nominal speed, i.e. binary output Idle/Nominal is active. When the output is not active (engine is
running on Idle speed), the setpoint ECU FreqSelect is not taken into account.
ECU FreqSelect