InteliDrive Lite - 1.2.1 Global guide
135
Setpoint group
Engine params 2
Related FW
1.2.1
Range [units]
0 - 3600 [s]
Default value
0 s
Force value
Step
1 s
Comm object
8662
Related applications
Config level
Standard
Setpoint visibility
Always
Description
Run time of engine after cooling pump. Binary output Cooling pump is closed when the engine starts and
opens AfterCool time delayed after engine stops.
AfterCool time
Setpoint group
Engine params 2
Related FW
1.2.1
Range [units]
[-]
Default value
DIESEL
Force value
Step
[-]
Comm object
9100
Related applications
Config level
Standard
Setpoint visibility
Always
Description
Setpoint setting determines behavior of the Binary output FUEL SOLENOID.
DIESEL: Output closes 1 sec before Binary output STARTER.
The output opens if Emergency stop comes or Cooled engine is stopped and in pause between repeated
starts.
GAS: In this mode of operation the output closes to open the gas valve and enable the engine to start. The
delay of Fuel solenoid output activation in relation to Starter output is defined by FuelSol offset. The output
closes only if RPM > 30 (i.e. the starter motor is engaged).
The output opens if there is any reason to stop the engine or in pause between repeated starts.
Note:
In the case of gas engine, the underspeed protection cannot be blocked by the Sprinkler function.
Note:
For gas engines, it is strongly recommended to use the pick-up sensor, as non-zero RPM
detection is required during the start procedure.
Fuel solenoid