InteliDrive Lite - 1.2.1 Global guide
134
Setpoint group
Engine params 2
Related FW
1.2.1
Range [units]
5 - 1500 [RPM]
Default value
350 RPM
Force value
Step
1 RPM
Comm object
9095
Related applications
Config level
Standard
Setpoint visibility
Always
Description
“Firing” speed when InteliDrive IPC controller stops cranking (starter goes OFF).
Sd Underspeed protection is activated when RPM drops back below the Starting RPM for more than 5
second the engine starting procedure.
RPM meas fail indication
Can appears during "Cranking state" i.e. Starter (or J1939 Start command) is activated then one running
condition was detected (D+ was activated or (POil > Starting POil) condition was filled) - i.e. Starter was
switched off based on previous condition and within time (Cranking time and fix 5s) minimum RPM does not
appear (RPM > Starting RPM), then is activated RPM meas fail.
Note:
Limit is ignored when Gear teeth = 0 i.e. in engine operation without speed pickup (running state is
indicated from D+ or Starting POil.
Starting RPM
Setpoint group
Engine params 2
Related FW
1.2.1
Range [units]
0 - 10 [Bar]
Default value
10Bar
Force value
Step
0.1 Bar
Comm object
9681
Related applications
Config level
Standard
Setpoint visibility
Always
Description
Controller stops cranking (starter goes OFF) when Oil Pressure (typically measured on AIN1) is over
Starting POil.
Note:
Oil Pressure can be also measured on binary sensor. Then is necessary adjust AIN1 as Binary
input and Starting POil=1.
Note:
There are three conditions for stop cranking: Starting RPM (just in case the Gear teeth > 0),
StartingPOil and D+ (if enabled). Starter goes off when any of these conditions is valid.
Starting POil