InteliDrive Lite - 1.2.1 Global guide
131
Setpoint group
Engine params
Related FW
1.2.1
Range [units]
0 - 600 [s]
Default value
30 s
Force value
Step
1 s
Comm object
9097
Related applications
Config level
Standard
Setpoint visibility
Always
Description
Idle time delay starts when RPM exceeds Start RPM. Start fail is detected when during Idle state RPM
decreases below 2.
During the Idle time timer running the binary output IDLE/NOMINAL is opened, when it expires the
IDLE/NOMINAL output closes. Binary output IDLE/NOMINAL opens during Cooling period again.
Note:
Engine can be switched between Idle and Running state by Binary input Nominal/Idle in MAN
mode.
Idle time
Setpoint group
Engine params
Related FW
1.2.1
Range [units]
Starting RPM – MinSpeedLimit [RPM]
Default value
800 RPM
Force value
Step
1 RPM
Comm object
9946
Related applications
Config level
Standard
Setpoint visibility
Always
Description
Speed request in engine Idle state i.e. after engine start or when switched to Idle in MAN mode by Binary
input Nominal/Idle and after Engine ShutDown.
Idle speed