InteliDrive Lite - 1.2.1 Global guide
129
Setpoint group
Engine params
Related FW
1.2.1
Range [units]
0 - 600 [s]
Default value
10 s
Force value
Step
1 s
Comm object
8394
Related applications
Config level
Standard
Setpoint visibility
Always
Description
Time of the PRESTART output closed prior to the engine start – i.e. before the binary outputs Fuel solenoid
and Starter are closed and opens when Starting RPM speed is reached. Set to zero if you want to leave the
output PRESTART opened.
Prestart time
Setpoint group
Engine params
Related FW
1.2.1
Range [units]
0 - 600 [s]
Default value
0 s
Force value
Step
1 s
Comm object
11836
Related applications
Config level
Standard
Setpoint visibility
Always
Description
Time of the PREGLOW output closed prior to the engine start. Set to zero if you want to leave the output
PREGLOW opened.
Note:
Function with shorter period (Prestart time or Preglow time) starts later to finish both in the same
time – when Starting RPM speed is reached.
Preglow time
Setpoint group
Basic settings
Related FW
1.2.1
Range [units]
1 - 60 [s]
Default value
5 s
Force value
Step
1 s
Comm object
8256
Related applications
Config level
Standard
Setpoint visibility
Always
Description
This setpoint is giving maximum time limit of engine cranking.
MaxCrank time