Accessory Modules for IL-NT, IC-NT, IA-NT and ID-Lite Global Guide
55
4.13.6 Technical data
Dimension (W×H×D)
66×34×16 mm (2.6´×1.34´×0.63´)
Interface to controller
Direct mounted
Current measuring input
Nominal current
5 A
Max. current
10 A
Current accuracy
2% from nominal
Max. peak current
150A / 1s
Binary inputs
Input resistance
4700ohm
Max. input signal
0 – 36VDC
Logical H (1)
< 0.8 VDC
Logical L (0)
> 2 VDC
Binary open collector outputs
Max current (per output)
0.5 A
Max switching current (common)
2.0 A
Max switching voltage
36 VDC
Storage temperature
- 40 °C to + 80 °C
Operating temperature
- 30 °C to + 70 °C